Automatic Transfer Switches Bypass/Isolation Switches

Automatic Transfer SwitchesBypass/ isolation SwitchesModelKBT/KBPG11-81(ModelKBT/KBPB ypass/IsolationSwitch) 10/05gRatingsVoltage208--600 VAC50/60 HzCurrentOpen-Transition150--4000ampsPro grammed-Transition150--4000ampsBypass/Is olationSwitchStandardFeaturesDBypass/iso lationswitchesforuninterruptedpowertothe loadduringswitchmaintenanceandtestingDOp en-transitionorprogrammed-transitionmode sofoperationD2,3,or4polesDElectricallyop erated,mechanicallyheldcontactorDDouble- throw,inherentlyinterlockeddesign(break- before-makepowercontacts)DSolid,switched ,oroverlappingneutral(make-before-breakt ype)DHighwithstandandclosingratingsDFull yratedforuseasamanual3-positiontransfers witchDPermanentlymountedbypassandisolati onhandlesDQuick-make,quick-breakbypasssw itchoperationforloadtransferbetweenlives ourcesDHeavydutymechanicalinterlocksDByp assswitchandcontactorpositionindicatorsD DrawoutcontactorforeaseofmaintenanceDDes ignsuitableforemergencyandstandbyapplica tionsonallclassesofload,100%tungstenrate dthrough400ampsDOpen-transitiontransfert imelessthan100milliseconds(6cycles@60Hz) DReliable,field-provensolenoidmechanismD SwitchingmechanismslubricatedforlifeDMai nshaftauxiliarycontactsDFront-connecteds tyleavailableforsomeamperagesMPAC1000tCo ntrollerStandardFeaturesDMicroprocessorc ontrollerDReal-timeclockDBroadrangevolta gesensing(208--600 VAC)with2%accuracyonbothsourcesDFrequenc ysensingwith1%accuracyonbothsourcesDEnvi ronmentallysealeduserinterfaceDKeypadwit htac

Automatic Transfer Switches Bypass/Isolation Switches Model KBT/KBP G11-81 (Model KBT/KBP Bypass/Isolation Switch) 10/05g Ratings Voltage 208--600 VAC 50/60 Hz

Tags:

  Switch, Isolation, Automatic, Bypass, Transfer, Switches, Automatic transfer switches bypass isolation switches

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Automatic Transfer Switches Bypass/Isolation Switches

1 Automatic Transfer SwitchesBypass/ isolation SwitchesModelKBT/KBPG11-81(ModelKBT/KBPB ypass/IsolationSwitch) 10/05gRatingsVoltage208--600 VAC50/60 HzCurrentOpen-Transition150--4000ampsPro grammed-Transition150--4000ampsBypass/Is olationSwitchStandardFeaturesDBypass/iso lationswitchesforuninterruptedpowertothe loadduringswitchmaintenanceandtestingDOp en-transitionorprogrammed-transitionmode sofoperationD2,3,or4polesDElectricallyop erated,mechanicallyheldcontactorDDouble- throw,inherentlyinterlockeddesign(break- before-makepowercontacts)DSolid,switched ,oroverlappingneutral(make-before-breakt ype)DHighwithstandandclosingratingsDFull yratedforuseasamanual3-positiontransfers witchDPermanentlymountedbypassandisolati onhandlesDQuick-make,quick-breakbypasssw itchoperationforloadtransferbetweenlives ourcesDHeavydutymechanicalinterlocksDByp assswitchandcontactorpositionindicatorsD DrawoutcontactorforeaseofmaintenanceDDes ignsuitableforemergencyandstandbyapplica tionsonallclassesofload,100%tungstenrate dthrough400ampsDOpen-transitiontransfert imelessthan100milliseconds(6cycles@60Hz) DReliable,field-provensolenoidmechanismD SwitchingmechanismslubricatedforlifeDMai nshaftauxiliarycontactsDFront-connecteds tyleavailableforsomeamperagesMPAC1000tCo ntrollerStandardFeaturesDMicroprocessorc ontrollerDReal-timeclockDBroadrangevolta gesensing(208--600 VAC)

2 With2%accuracyonbothsourcesDFrequencysen singwith1%accuracyonbothsourcesDEnvironm entallysealeduserinterfaceDKeypadwithtac tilefeedbackpushbuttonsDLED indicatorsDSelectableoperatingmodesDProg rammableinputsandoutputsDLoad/noloadexer cisefunctionDIn-phasemonitorDAnti-single phasingprotectionDLoadcontrolinputsandou tputsDPhaserotationsensingDTime-stampede ventlogDGold-flashedenginestartcontactsD Modbusrcommunicationwithnetworkandsetupc onnectionsProgrammableFeaturesDSystemvol tageandfrequencyDAdjustableover/undervol tageandover/underfrequencyforthenormalan demergencysourcesDAdjustabletimedelaysDC ommit/nocommittransferDABC/CBAphaserotat ionselectionwitherrordetectionDResettabl ehistoricaldataDPasswordprotectionDSingl e/three-phaseoperation[DOpen/programmed- transitionoperation[DIn-phasemonitor(dis abled)DCalendarmodeexerciser(upto21event s)DProgrammableinputsandoutputsCommunica tionsDSerialportforPCconnectionDModbusrn etworkinterfaceModbusrisaregisteredtrade markofSchneiderElectricG11-81(ModelKBT/K BPB ypass/IsolationSwitch) 10/05gControllerFeaturesStandardControll erFeaturesUser Interface KeypadDStart/endsystemtestDSet/endexerci seDEndtimedelayDLamptest/serviceresetUse r Interface IndicatorsDContactorposition:Normal,Off, EmergencyDSourceavailable:Normal,Emergen cyDServicerequired:immediate,maintenance DNotinautomaticmodeDFour-stagetimedelayr emainingDExercise:load,noload,set/disabl edDTest:load,noloadDLoadcontrolactive.]]

3 Peakshave,loadshed,pre/post-transfersign alDIn-phasemonitoractiveSelectable Operating Modes*D1week/2weekexercise(1week)DDisabl e/enableexercise(enable)DLoad/noloadexer cise(noload)DLoad/noloadtest(load)DEnabl e/disabletransfer(enable)InputsDOneprogr ammableinput,factory-settopeakshave/area protectionDOneprogrammableinputforfactor yuseonly,inhibitstransferduringtravelbet weenTESTandISOLATE positionsOutputsDGeneratorenginestartgol d-flashedcontactrated2amps@30 VDC/250 VACDPre-transferloadcontrol,onenormallyo pencontactrated10amps@30 VDC/250 VACDO neprogrammableoutput,factory-settoloadba nkcontrolrated2amps@30 VDC/250 VACS oftware Event (totalandresettable)DSystemevents(timean ddate-stamped)DSystemfaults(timeanddate- stamped)DLine-to-linevoltageDSystemfrequ encyDTimedelayactiveDTimedelayremainingD SystemstatusDSourceavailableDContactorpo sitionDExerciserschedule,mode,andtimerem ainingonactiveexercise* Factory default settings are shown in parentheses. All settings arestoredinnon-volatilememory.

4 [ ,select, Features*DSystemvoltage[DSystemfrequency [DABCorCBAphaserotation(ABC)DSingle/thre e-phaseoperation[DOpen/programmed-transi tionoperation[DIn-phasemonitor(disabled) DCommit/nocommitswitch(nocommit)DUser-de finedpasswordDCalendarmodeexerciser(upto 21events) InputsDEndtimedelayinput(default)DInhibi ttransferDLowbatteryfaultDLoadshed(force dtransferfromEmergencytoOFF;programmed-t ransitionmodelsonly)DPeakshave/areaprote ctioninput(default)DRemotecommonfaultDRe motetestProgrammable OutputsDAuxiliaryswitchfaultDCommonfault DContactorpositionDExerciseactiveDFailur etoacquirestandbysourceDFailuretotransfe rfaultDGeneratorenginestartDLoadbankcont rol(default)DLoadcontrol(pre/posttransfe r;upto9outputs)DLossofphasefaultDLowback upbatteryDModbusr-controlledrelayoutputs (4maximum)DNotinautomaticmodeDNon-emerge ncytransferDOverandundervoltagefaultsDOv erandunderfrequencyfaultsDPeakshave/area protectionactiveDPhaserotationerrorDSour ceavailableDTestactiveG11-81(ModelKBT/KB PB ypass/IsolationSwitch) 10/05gControllerFeatures,continuedVoltag e and Frequency SensingParameterDefaultAdjustment RangeUndervoltagepickup90%ofnominal85%-- 100%ofnominalUndervoltagedropout90%ofpic kup75%--98%ofpickupOvervoltagedropout110 %ofnominal105%--135%ofnominal*Overvoltag epickup95%ofdropout95%--100% * 690volts,maximumAdjustable Time DelaysTime [ [Post- Transfer [ (programmed-transitiononly) (programmed-transitiononly)1sec.]]]]]]]]

5 [Adjustablein1secondincrements. Solderless Screw-Type Terminalsfor External Power ConnectionsNormal, Emergency, and Load TerminalsSwitchRating(Amps)MaximumNumber ofCables per PoleRange of Wire Sizes,Copper or Aluminum150--400]1#4 AWGto600 MCMKBT]2#1/0 AWGto250 MCM150--40023l1#4 AWGto600 MCM2-,3-poleKBPw2#1/0 AWGto250 MCM150--4004-poleKBPw2#1 AWGto600 MCM600S2#2 AWGto600 MCM600F2#1 AWGto600 MCM800F3#1 AWGto600 MCM800--1200S4#1/0 AWGto750 MCM1600--20006#1/0 AWGto750 MCM2600--300010#1/0 AWGto750 MCM400012#2 AWGto600 MCMF Front-connectedS Standardrear-connected]Open-transitionmo delsonlywProgrammed--transitionmodelsonl yInput and Output Connection SpecificationsComponentNumber of WiresWire Size RangeTerminalstripI/Oterminals1#12--24 AWGI/Omoduleterminals1#14--26 AWGA uxiliary Position Indicating Contacts(rated10amps@32 VDC/250 VAC)Number of contacts indicatingNormal, EmergencySwitch Rating (Amps)Open-TransitionProgrammed-Transiti on150--4003,32,3150--400 ** 7,7600--30008,87,740002,24,3**Programmed transition4-poleEnvironmental SpecificationsOperatingTemperature--20 Cto70 C(--4 Fto158 F)StorageTemperature--40 Cto70 C(--40 Fto158 F)Humidity5%to95%noncondensingAltitude0t o3050m(10000ft.)

6 Without deratingG11-81(ModelKBT/KBPB ypass/IsolationSwitch) 10/05gCodesandStandardsTheATSmeetsorexce edstherequirementsofthefollowingspecific ations:DUnderwritersLaboratoriesUL508,St andardforIndustrialControlEquipmentDUnde rwritersLaboratoriesUL1008,StandardforAu tomaticTransferSwitchesforUseinEmergency StandbySystemsDUnderwritersLaboratoriesI nc.,ListedtoCanadianSafetyStandards(cUL) DNFPA70,NationalElectricalCodeDNFPA99,Es sentialElectricalSystemsforHealthCareFac ilitiesDNFPA110,EmergencyandStandbyPower SystemsDIEEES tandard446,IEEER ecommendedPracticeforEmergencyandStandby PowerSystemsforCommercialandIndustrialAp plicationsDNEMAS tandardIC10--1993(formerlyICS2--447),ACA utomaticTransferSwitchesDEN61000-4-5 SurgeImmunityClass4(voltagesensingandpro grammableinputsonly)DEN61000-4-4 FastTransientImmunitySeverityLevel4 DIECS pecificationsforEMI/EMCI mmunity:dCISPR11,RadiatedEmissionsdIEC10 00-4-2,ElectrostaticDischargedIEC1000-4- 3,RadiatedElectromagneticFieldsdIEC1000- 4-4,ElectricalFastTransients(Bursts)dIEC 1000-4-5,SurgeVoltagedIEC1000-4-6,Conduc tedRFDisturbancesdIEC1000-4-8,MagneticFi eldsdIEC1000-4-11,VoltageVariationsandIn terruptionsWeightsandDimensionsBypass/Is olationSwitchesinNEMA1 EnclosuresDimensions mm (in.)

7 Weight kg (lb.)TransitionAmpsHeightWidthDepth2-Pol e3-Pole4-PoleOpen-150--4001588(63)724( )489(19)*154(340)158(350)163(360)pTransi tion600--800F2286(90)965(38)813(32)[685( 1510)717(1580)748(1650)600--1200S2311(91 )965(38)1219(48)]685(1510)717(1580)748(1 650)1600--20002311(91)965(38)1524(60)] 1070(2360)1152(2540)2600--30002311(91)19 81(78)1829(72)] 1240(2730)1525(3360)40002311(91)2451( )1829(72)w 2858(6300)3130(6900)Programmed-150--4001 892(75)724( )489(19)*154(340)158(350) gTransition150--400F(4-pole)2286(90)965( 38)813(32)[ 340(750)600--800F,S2286(90)965(38)813(32 )[315(695)322(710)340(750)1000--12002311 (91)965(38)1219(48)]928(2045)1027(2265)1 127(2485)1600--20002311(91)965(38)1524(6 0)] 1070(2360)1152(2540)2600--30002311(91)96 5(38)1829(72)] 1325(2920)1611(3550)40002311(91)2451( )1829(72)w 2858(6300)3130(6900)F Front-connectedS Standardrear-connected(notavailablefor15 0--400amp4-poleprogrammed-transition)* Handlesextend89mm( ).[Handlesextend159mm( ). Standardenclosuresfor150--400amp4-polean d600--800ampsizesaresuitablefortopandupp erleftsidecableentranceonly.

8 ]Recommendedclearancetoenclosure: (3ft.)fromrear, (4ft.)fromfront[ (25in.)requiredfortransferswitchdrawout] .wRecommendedclearancetoenclosure: (3ft.)fromrear, (5ft.)fromfront[ (3ft.)requiredfortransferswitchdrawout]. G11-81(ModelKBT/KBPB ypass/IsolationSwitch) 10/05gWithstandandClosingRatings(WCR) *Withstand and Closing Current Ratings in RMS Symmetrical Amperes*Any Circuit BreakerCurrent-Limiting FusesSwitch Rating,AmpsCycles @ 60 HzWCR, Amps@480 VACWCR, Amps @600 VACAmpsVolts,MaxFuse Size,AmpsType15045033500022000480J225400 335,00022,000480600J225--400,,6002254006 006001200350,00050,0001600600--120031850 ,00036,00050,00036,000200,00016001600200 060030001600,20006003000L260030003100,00 0100,0004000L2600,3000330[100,0006500010 0,000650004000400030[65,00065,0004806000 * [Withstandratingonly. (ModelKBT/KBPB ypass/IsolationSwitch) 10/05gRatingswithSpecificManufacturers CircuitBreakersThefollowingchartslistpow erswitchingdevicewithstandandclosingrati ngs(WCR)inRMSsymmetricalamperesforcircui tbreakersfromspecificmanufacturers.]]

9 Ratingsapplytobothopen-andprogrammed-tra nsitionmodels. Circuit BreakersSwitchRating,AmpsVoltage, (WCR),RMS SymmetricalAmpsManufacturerTypeMax. Size,AmpsTEL,THED,THLC1,150 TFL,THLC2225 GeneralElectricSFL,SFLA,SFP250 GeneralElectricSGL4,SGP4,TB4,THLC4,TLB44 00 SGLA,SGL6,SGP6TB6600 CFD6,HFD6250 ITECJD6,HHJD6,HHJXD6,HJD6,SCJD6,SHJD6400 ITECLD6,HHLD6,HHLXD6,HLD6,SHLD6600150480 42,000 SquareDKC,KI25015048042,000 SquareDLC,LI400 HJD,JDC250 CutlerHammerHKD,KDC,LCL,Tri-PacLA400 Cutler-HammerHLD600 Tri-PacNB800 ABBS3150 MerlinGerinCF250250 MerlinGerinCJ400400 TFL,THLC2225 SFL,SFLA,SFP250 GeneralElectricSGL4,SGP4,TB4,THLC4,TLB44 00 GeneralElectricSGLA,SGL6,SGP6,TB6600 SKHA,SKL8,SKP8,TKL800 CFD6,FD6,FXD6,HFD6250 ITECJD6,HHJD6,HHJXD6,HJD6,JD6,JXD6,SCJD6 ,SHJD6,SJD6400 ITECLD6,HHLD6,HHLXD6,HLD6,SCLD6,SHLD6600 225 CMD6,HMD6,HND6,MD6,MXD6,SCMD6,SHMD6,SMD6 ,SND680022526048042,000KC,KI250260 SquareDLC,LI600 SquareDMH800 HJD,JDC250 CutlerHammerHKD,KDC,LCL,Tri-PacLA400 Cutler-HammerHLD600 Tri-PacNB800 ABBS5400 ABBS6600 MerlinGerinCF250250 MerlinGerinCJ400400G11-81(ModelKBT/KBPB ypass/IsolationSwitch)

10 10/05gRatingswithSpecificManufacturers CircuitBreakers,continuedMolded-Case Circuit BreakersSwitchRating,AmpsVoltage,MaxWith stand/ClosingRating (WCR),RMS SymmetricalAmpsManufacturerTypeMax. Size,AmpsSGL4,SGP4,TB4,THLC4,TLB4400 GeneralElectricSGLA,SGL6,SGP6,TB6600 GeneralElectricSKHA,SKL8,SKP8,TKL800 CJD6,HHJD6,HHJXD6,HJD6,SCJD6,SHJD6,400 ITECLD6,HHLD6,HHLXD6,HLD6,SCLD6,SHLD6600 ITECMD6,HMD6,HND6,MD6,MXD6,SCMD6,SHMD6,S MD6,SND680040048042,000 SquareDLC,LI60040048042,000 SquareDMH800 HKD,KDC,LCL,Tri-PacLA400 Cutler-HammerHLD600 CutlerHammerTri-PacNB800 ABBS5400 ABBS6800 MerlinGerinCJ600600 GeneralElectricTB8800 GeneralElectricMicroversatripTKL1200 CLD6,HHLD6,HHLXD6,HLD6,SCLD6,SHLD6600480 65000 ITECMD6,HMD6,SCMD6,SHMD680048065,000 ITECND6,HND6,SCND6,SHND61200 CPD61600600 SquareDMHS eries210006008001000 SquareDSE(LSTrip),SEH(LSTrip)25001000120 0 Tri-PacNB800120060065,000 Cutler-HammerTri-PacPB160060065,000 CutlerHammerRDC2500 ABBS680048042000 ABBS7120048042,000 MerlinGerinCJ600600 MerlinGerinCK12001200 DISTRIBUTED obligation or liability whatsoever.