Example: air traffic controller

Bussmann series Quik-Spec Power Module Switch …

Effective July 2016. technical Data 1145 Supersedes January 2016. Bussmann series Quik-Spec Power Module Switch elevator disconnect Agency information UL 98 enclosed and dead-front Switch - Guide WIAX, WIAX7 (Canada), File E182262. cULus, NEMA 1, UL 50, Listed enclosure cUL. per Canadian Standards , No. 0-M91-CAN/. CSA , No. 4-M89 enclosed Switch and seismic qualified, and approved Features: 30-400 amp 600 Vac 3-phase fused Power Switch 200kA RMS Short-Circuit Current Rating (SCCR). Shunt trip 120V. Fire safety interface relay Fire alarm voltage monitoring relay (to monitor shunt trip voltage). Ground lug Catalog symbol: Class J fuse mounting only1. Mechanically interlocked auxiliary contacts for PS_ hydraulic elevators with battery backup (5 amp 120 Vac rated).

Technical Data 1145 Effective July 2016 Supersedes January 2016 Bussmann series Quik-Spec Power Module Switch elevator disconnect Catalog symbol: • …

Tags:

  Series, Switch, Technical, Power, Spec, Module, Elevator, Disconnect, Quik, Bussmann, Bussmann series quik spec power, Bussmann series quik spec power module switch elevator disconnect

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Bussmann series Quik-Spec Power Module Switch …

1 Effective July 2016. technical Data 1145 Supersedes January 2016. Bussmann series Quik-Spec Power Module Switch elevator disconnect Agency information UL 98 enclosed and dead-front Switch - Guide WIAX, WIAX7 (Canada), File E182262. cULus, NEMA 1, UL 50, Listed enclosure cUL. per Canadian Standards , No. 0-M91-CAN/. CSA , No. 4-M89 enclosed Switch and seismic qualified, and approved Features: 30-400 amp 600 Vac 3-phase fused Power Switch 200kA RMS Short-Circuit Current Rating (SCCR). Shunt trip 120V. Fire safety interface relay Fire alarm voltage monitoring relay (to monitor shunt trip voltage). Ground lug Catalog symbol: Class J fuse mounting only1. Mechanically interlocked auxiliary contacts for PS_ hydraulic elevators with battery backup (5 amp 120 Vac rated).

2 Description: Eaton Bussmann series Quik-Spec Power Options: Module Switch is an all-in-one elevator disconnect Control Power transformer with fuses and Switch available in configurations to meet virtually blocks any single elevator shutdown and disconnect requirement. Key to test Switch Pilot light ON . Specifications: Isolated neutral lug2. Ratings NEMA 3R, 4, and 12 enclosures Volts - 208, 240, 480, 600 Vac For added protection, use the Bussmann series Amps - 30, 60, 100, 200, 400 SAMI fuse covers3 to improve electrical safety SCCR - 200kA RMS [OSHA (A)(2)(ii)]. See data sheet no. 1204. 1 Class J fuses not included. 2 Oversized 200% rated neutral option available where required by excessive non-linear loads.

3 3 Covers available up to 100A. technical Data 1145 Bussmann series Quik-Spec Power Module Switch Effective July 2016 elevator disconnect Catalog number system: PS 1 T48 R1 K G N1 B F1 U. Prefix Control Key test Neutral lug Fire alarm voltage PS = Power transformer* Switch (optional) (optional) monitoring relay Module T20 = 208V K = Key N6 = 30-60A To monitor shunt Switch T24 = 240V N1 = 100A trip voltage T48 = 480V N2 = 200A F1 = 1-Pole Relay T60 = 600V N4 = 400A F3 = 3-Pole Relay**. Amp rating Fire safety Pilot light ON Auxiliary Enclosur e interface relay (optional) contacts 3 = 30A = Type 1. 6 = 60A (3 PDT, 10A, 12V) G = Green B = 2 NO/NC U = Type 3R. 1 = 100A R1 = 120 Vac Coil R = Red Z = Type 12.

4 2 = 200A R2 = 24 Vdc Coil W = White Y = Type 4. 4 = 400A. * 100VA with primary and secondary fusing (120V secondary). ** For use only with R1 option. Type 1 standard, no suffix designator required. Conductor data: Lineside molded case Switch connection (Al-Cu) Loadside fuse block connection (Al-Cu). Torque Screw Torque Screw Cat. no. Conductor head/ Conductor head/. prefix Amps range Wire size lb-in (N m) style range Wire size lb-in (N m) style #14-10 35 ( ) #14-10 35 ( ). #8 40 ( ) #8 40 ( ). PS3 30 #14-1/0 Slot HD #14-2 Slot HD. #6-4 45 ( ). #6-2 45 ( ). #3-1/0 50 ( ). #14-10 35 ( ) #14-10 35 ( ). #8 40 ( ) #8 40 ( ). PS6 60 #14-1/0 Slot HD #14-2 Slot HD. #6-4 45 ( ). #6-2 45 ( ). #3-1/0 50 ( ).

5 PS1 100 #14-1/0 #14-1/0 50 ( ) Slot HD #14-1/0 #14-1/0 50 ( ) Slot HD. 5/16 hex PS2 200 #4-4/0 #4-4/0 120 ( ) 3/16 hex socket #4-300kcmil #4-300kcmil 275 ( ) socket (2) 1/0-300kcmil (2) 1/0-300kcmil PS41 3/8 hex 400 (2) #2-500kcmil (2) #2-500kcmil 375 ( ) 5/16 hex socket or or 500 ( ) socket (1) 750kcmil (1) 750kcmil 2 Bussmann series Quik-Spec Power Module Switch technical Data 1145. elevator disconnect Effective July 2016. Conductor data: Neutral mains connection (Al-Cu). Torque Cat. no. prefix Amps Conductor range Wire size lb-in (N m) Screw head/style #14-10 35 ( ). PS3 30 #14-2 #8 40 ( ) Slot HD. #6-2 45 ( ). #14-10 35 ( ). PS6 60 #14-2 #8 40 ( ) Slot HD. #6-2 45 ( ). PS1 100 #14-1/0 #14-1/0 50 ( ) Slot HD.

6 PS2 200 #6-250kcmil #6-250kcmil 275 ( ) 5/16 hex socket PS4 400 (2) 1/0-300kcmil or (1) 750kcmil (2) 1/0-300kcmil or (1) 750kcmil 500 ( ) 3/8 hex socket Terminal block data: Torque Screw Catalog no. Wire range (Cu) lb-in (N m) head/style All #22-#10 ( ) Slot Switch maximum horsepower ratings: Ratings are based on three-phase, motor type and time-delay fuses. Switch amp rating Voltage 30A 60A 100A 200A 400A. (Vac) (PS3) (PS6) (PS1) (PS2) (PS4). 208 5 10 15 40 75. 240 5 10 20 40 75. 480 10 25 40 75 150. 600 15 30 50 100 200. The above table can be used for estimating Switch amp ratings for motor loads based upon the motor horsepower. For general applications, excluding wound rotor and DC motors, NEC allows sizing at 175% of motor Full Load Amps (FLA) or the next standard size per NEC If sizing at 175% will not allow the motor to start, NEC will allow the fuses to be sized up to 225% of motor full load amps or the next size down.

7 NOTE: In sizing the fuses, the motor FLA is per NEC table , not per motor nameplate information. Inrush currents of motors may vary, consult motor manufacturer data for correct sizing. On elevator applications, motor load plus auxiliary loads need to be considered. Follow elevator manufacturer's recommendation for correct fuse sizing. Standard shunt trip ratings: For 30-100A, 200A and 400A Power Module Switches. Momentary Voltage Max inrush Max ontime* inrush 120 Vac, 60Hz 4 amps cycles 140VA. * Will handle up to 447VA inrush. 3. technical Data 1145 Bussmann series Quik-Spec Power Module Switch Effective July 2016 elevator disconnect Dimensions in (mm): Catalog no. prefix Amps H W D1 D2 A B. PS3 30.

8 PS6 60 (752) (439) (165) (284) (721) 10 (254). PS1 100. PS2 200 (828) (541) (178) (287) (790) 17 (432). PS4* 400 (1387) (673) (190) (323) (1354) 22 (559). * PS4 dimensions shown are for NEMA 1 enclosure only. Contact factory for availability of other enclosure ratings. D2 B. H A. D1 W. Power Module Switch shipping weights*. Switch catalog number family Weight lbs. (kgs). PS1 58 ( ). PS2 76 ( ). PS3 58 ( ). PS4 198 ( ). PS6 58 ( ). * Weights for each catalog number family are average. 4 Bussmann series Quik-Spec Power Module Switch technical Data 1145. elevator disconnect Effective July 2016. Power Module Switch wiring: 5. technical Data 1145 Bussmann series Quik-Spec Power Module Switch Effective July 2016 elevator disconnect Power Module Switch wiring continued: 6 Bussmann series Quik-Spec Power Module Switch technical Data 1145.

9 elevator disconnect Effective July 2016. Power Module Switch wiring continued: 7. technical Data 1145 Bussmann series Quik-Spec Power Module Switch Effective July 2016 elevator disconnect The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin.

10 Once a product has been selected, it should be tested by the user in all possible applications. Eaton 1000 Eaton Boulevard Cleveland, OH 44122 Eaton, Bussmann , Quik-Spec and SAMI are For Eaton's Bussmann series valuable trademarks of Eaton in the US and product information, other countries. You are not permitted to use Bussmann Division the Eaton trademarks without prior written call 1-855-287-7626 or visit: 114 Old State Road consent of Eaton. Ellisville, MO 63021 United States CSA is a registered trademark of the Canadian Standards Group. NEC is a registered trademark of the National 2016 Eaton Fire Protection Association, Inc. Follow us on social media to get the All Rights Reserved NEMA is a registered trademark of the latest product and support information.