Transcription of C-mac Programmable converter PCV10 - Industrial …
1 C-mac . Programmable converter PCV10 . AC/DC current inputs from 15 A to 10 A. AC/DC voltage inputs from 10 mV to 1500 V. Frequency monitoring up to 5 kHz Analogue or pulse outputs Galvanic separation, supply - input - output DC supply or AC supply voltages up to 400 VAC. Made in accordance with the and EMC regulations PCV10 is a multirange converter / isolation amplifier All parameters in the converter are Programmable within the with current, voltage and pulse inputs and current, volt- specified limitations (min. and max. input and output levels), age, pulse or relay outputs. giving the following possibilities: The unit is supplied with 3 current and 3 voltage input mA Output connections, which makes it possible to program any in- 20. put range between 15 A and 10 A or 15 mV and Basic converter , (0 to 16. 1000 VAC/1500 VDC. With DC-inputs it is possible to defined input range and 12.)
2 Monitor both positive and negative signals. standard output range, 0-20 mA, 4-20 mA or 8. With AC inputs the converter monitors the RMS value of the signal, which means the signals are converted 0-10 V). 4. Input without any errors, no matter which shape they have. 0. 0 20 40 60 80 100%. The unit can also be programmed with frequency input, mA Output where the same input connections are used. The fre- 20. quency of the input signal is then monitored instead of converter with input 16. the analogue level. and/or output offset, 12. You can select between 2 different output configura- 12 to 50 VDC input 8. tions: and 8 to 15 mA output. 4. Type A is supplied with analogue current output, pro- 0. Input grammable between 0 and 20 mA and analogue volt- 0 20 40 60 80 100%. age output, Programmable between -10 and +10 V. mA Output 20. Type B has the same outputs as type A, but in addition Bidirectional input 16.
3 It is also supplied with pulse output, Programmable to range (only DC inputs), a maximum frequency of 10 kHz. -50 to +300 mA. 12. The unit is supplied with 2 trimming potentiometers, 8. which can be used to fine-adjust the metering range, if 4. the unit is used with analogue outputs. In either case the 0. Input potentiometers can be disabled and fixed values se- -40 -20 0 20 40 60%. lected, if adjustment is not required. V Output 10. If you want, you can order the unit with specified meter- Bidirectional output 6. ing ranges, or you can program it yourself, by means of range (only voltage the C-mac programming software for PC and a small in- output), -10 to +10. 2. 0. terface to connect between the PC and the module. -2. V. -6. Input -10. 0 20 40 60 80 100%. mA Output Inverted function with 20. or without offset, 16. 150 to 20 VAC input 12. and 4 to 20 mA output.
4 8. 4. Input 0. 0 20 40 60 80 100%. 1-1 Comadan Produktion a/s PCV10 connections: Supply voltage. Outputs, type PCV10 -A and PCV10 -B. terminal 15 and 16 9: output common 1 2 3 4 5 6 7 8. Inputs. 10: current output 11: voltage output C-mac 1: input common 12: pulse output ( type PCV10 -B only) Supply 2: 10 AAC/DC Relay 1. 3: 207 mAAC/292 mADC Relay 2. 4: 5,8 mAAC/8,2 mADC Programmable converter 5: 0,8 VAC/1,1 VDC. 6: 27 VAC/39 VDC 9 10 11 12 13 15 16. 8: 1000 VAC/1500 VDC. Connection drawings: Supply voltage, AC Supply voltage, DC Pulse outputs type PCV10 -B only): 9 10 11 12 13 15 16 9 10 11 12 13 15 16 9 10 11 12 13 15 16. - GND. IN NPN output. + Eksternal load: Current inputs: Voltage inputs: max. 30 V / 30 mA. High, max. High, max. 10 A AC/DC. 1000 VAC / 1500 VDC. + + 9 10 11 12 13 15 16. - - IN. + PNP output. 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Eksternal load: max.
5 30 V / 30 mA. Medium, max. 207 mA AC Medium, max. 292 mA DC 27 VAC / 39 VDC. + +. - - 9 10 11 12 13 15 16. - 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 + Pulse output. V = 10 V. Low, max. 5,8 mA AC Low, max. out R = 2 kW. 8,2 mA DC 0,8 VAC / 1,1 VDC out + +. - - 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8. Analog current output: Analog voltage output: Programmable ranges Programmable ranges between 0 and 20 mA between -10 and +10 V. 9 10 11 12 13 15 16 9 10 11 12 13 15 16. Com Com + +/- Comadan 1-2. Produktion a/s Mechanical dimensions: Materials: Housing base: CYCOLOY C2100, 1 2 3 4 5 6 7 8 grey C-mac Frontplate: CYCOLOY C2100, grey 70,0. Supply Terminal cover: CYCOLOY C2100, Programmable converter black Terminals: nickel plated brass 9 10 11 12 13 15 16. Screws: nickel plated iron 45,0 117,0. Weight: 350 g Programming connections and adjustments: Programming connector CON. Potentiometers P1 and P2.
6 Connects to the PC via C-mac interface cable. The interface unit is internally battery powered, PCV10 -A and PCV10 -B: C-mac which means it is not necessary to connect any P1 = Offset fine adjust +/- 5%. external supply voltage to the PCV unit during P2 = Span fine adjust +/- 5%. programming. Function selector switch DS. 1 OFF: Normal mode 1 ON: Programming mode 2 OFF: Disable P1 adjustment 2 ON : Enable P1 adjustment 3 OFF: Disable P2 adjustment 3 ON : Enable P2 adjustment PCV10 programming. Please notice, that it is only possible to adjust on one of It is possible to program and reprogram the unit at any the potentiometers at a time, you cannot set both time, no matter if the supply voltage is connected or not. switch 2 and 3 ON simultaneously. If the program is modified while the unit is installed and Reset to the programmed settings. in operation, all input signal conversions are disabled If you have fine-adjusted the programmed ranges, and and the output will not update as long as DS 1 is ON.
7 You want to reset to the original settings, you use the Programming of the unit is made by following the in- following procedure:Set switch 2 or 3 ON, depending structions in the C-mac programming unit on which of the ranges you want to for the starts with the modified program as soon as DS 1 is supply LED to switch 1 ON, and reset switched back to OFF position. switch 2 or 3 to OFF switch 1 OFF again. Fine adjustments with potentiometer 1 and 2. Now the selected range has been reset, and you can re- In order to avoid unwanted modifications of the pro- peat the procedure on the other range, if you want. grammed ranges and to ensure a good temperature sta- bility it is only possible to fine-adjust the programmed metering ranges if you use the following procedure: When you have a known and stable input signal, you set switch 2 or 3 ON, for P1 or P2 adjustment, respec- the switch has been activated for minimum 2 seconds, the supply LED extinguishes and the output signal changes to the value, which corresponds to the ac- tual position of the potentiometer.
8 Now you adjust the output signal to the wanted value, and then you set the switch back in OFF position. The modified range is now programmed, and the power LED is ON again. If you want to adjust the ranges again, you set the switch back in ON position, wait for the LED to extinguish, adjust on the potentiometer, and set the switch back in OFF posi- tion. 1-3 Comadan Produktion a/s Technical data: Supply voltage AC: 24, 115, 230 and 400 VAC +/- 10% Current inputs: Supply frequency: 40-70 Hz Terminals 1-2: Metering ranges (DC) 290 mA to 10A. Rin = 10 mW. Supply voltage DC: 12-50 VDC. Max. inrush current (10 sec): 20 A. Isolation voltages: Supply - internal electronics: 3,75 kV. Input - output: kV Terminals 1-3: Metering ranges (DC) 8 mA to 290 mA. Rin = W. Power consumption: 6 VA Max. inrush current (10 sec): 1A. Operation temp.: -20 C to +60 C Terminals 1-4: Metering ranges (DC) 15 A to 8 mA.
9 Humidity: 0-90% RH, non condensing Rin = 55 W. Temp. coefficient: < / C Max. inrush current (10 sec): 130 mA. EMC data. Voltage inputs: Terminals 1-5: Metering ranges (DC) 15 mV to V. Emission: EN 50 081 - 1. Rin = kW. Immunity: EN 50 082 - 2 Max. voltage (10 sec): 60 V. Safety: EN 60 730 - 1 Terminals 1-6: Metering ranges (DC) V to 38 V. Approvals. The module is produced in accordance Rin = 270 kW. with CE and high voltage regulations. Max. voltage (10 sec): 220 V. Speed and accuracy. Terminals 1-8: Metering ranges (DC) 38 V to 1500 V. Conversion speed: Rin = 10 MW. AC input (50 Hz): in - out delay: 150 msec Max. continuous voltage: 1800 V. DC input in - out delay: 20 msec. Max. voltage (10 sec): 2000 V. Accuracy: better than 0,2%, except at 10 A range AC input, current or voltage: at I > 5 A: in accuracy better than 1% Input frequency: 5 - 420 Hz Linearity: better than Frequency inputs: If the unit is programmed to monitor the frequency of the Resolution: Between 0,037% and 0,1%, dependent input signal, the normal current or voltage inputs are used.
10 On the programmed metering range. Because the pulses are detected at a level very close to zero, If the unit is programmed with input it is only recommended to use the frequency option, if the and/or output offset, the resolution will input signal comes from an AC source. be reduced proportionally. In either case During programming you select the input which corresponds the actual resolution is informed, to the actual current- or voltage level. when the unit is programmed. Panel mounting. Indications: Green LED: Steady light = supply ON If several modules are placed beside each other in a control Flashing = programming mode panel, there must be a minimum distance of 5 mm between each module. Outputs. Current output: Terminals 9-10, Programmable from Ordering guide. 0 to 20 mA. 1. Basic units without range programming. Max. external load: 500 W PCV10 -x-yyy Voltage output: Terminals 9-11, Programmable from x = Output configuration.