VariSTAR Storm Trapper Secondary class MOV surge arresterGeneralEaton's Cooper Power series VariSTAR Storm Trapper Secondary class MOV surge arrester is de signed to provide overvoltage pro tec tion for low voltage equipment and dis tri bu tion circuits. Storm Trapper ar rest ers are Canadian Standards Association, CSA listed for safety and comply with IEEE Std -1993 standard "IEEE Standard for Metal Oxide surge arrester for AC Power Circuits."Applications* Storm Trapper surge arresters are avail able in three volt age ratings: 175-Volt ArrestersThe 175-volt arrester is de signed for single-phase 120-volt ap pli ca tions. It is available as single-, double-, or triple-pole for two-, three-, or four-wire ArrestersThe 350-volt single-pole arrester is de signed for in di vid u al application at sin gle voltage source in stal la tions with line-to-ground voltages greater than 175 volts and less than 350 350-volt two-pole device is designed for com-mon three-wire 480

VariSTAR® Storm Trapper® secondary class MOV surge arrester General Eaton's Cooper Power™ series VariSTAR® Storm Trapper® secondary class MOV surge arrester is designed to provide overvoltage protec tion for

Tags:

  Class, Secondary, Storm, Surge, Surge arrester, Arrester, Varistar, Ca235020en varistar storm trapper secondary, Ca235020en, Trapper, 174 storm trapper, 174 secondary class

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CA235020EN VariSTAR Storm Trapper Secondary …

1 VariSTAR Storm Trapper Secondary class MOV surge arresterGeneralEaton's Cooper Power series VariSTAR Storm Trapper Secondary class MOV surge arrester is de signed to provide overvoltage pro tec tion for low voltage equipment and dis tri bu tion circuits. Storm Trapper ar rest ers are Canadian Standards Association, CSA listed for safety and comply with IEEE Std -1993 standard "IEEE Standard for Metal Oxide surge arrester for AC Power Circuits."Applications* Storm Trapper surge arresters are avail able in three volt age ratings: 175-Volt ArrestersThe 175-volt arrester is de signed for single-phase 120-volt ap pli ca tions. It is available as single-, double-, or triple-pole for two-, three-, or four-wire ArrestersThe 350-volt single-pole arrester is de signed for in di vid u al application at sin gle voltage source in stal la tions with line-to-ground voltages greater than 175 volts and less than 350 350-volt two-pole device is designed for com-mon three-wire 480/240 volt applications.

2 The 350-volt three-pole unit pro tects motors and other equipment on three-phase systems which can have a number of sys tem voltages be tween 175 and 350 ArrestersThe 650-volt arrester is designed for com mer cial/industrial ap pli ca tions where the line-to-ground system voltage is great er than 350 volts, but not more than 650 Storm Trapper arrester is mois ture proof. Refer to Service Instructions S235-15-1, MOV Storm Trapper Secondary class surge arrester Installation Instructions for details.* For service entrance applications, a higher energy device is recommended. Refer to Catalog Data CA235015EN Storm Trapper High Energy Lov-Voltage Distribution- class MOV surge arrester CA235015EN.

3 surge ArrestersCatalog Data CA235020 ENEffective August 2015 Supersedes TD235003EN September 2014 COOPER POWERSERIESEach Storm Trapper arrester must pass the following production tests: 100% Physical Inspection 100% Reference Voltage (Vref) 100% Vacuum over Fluid Seal Test 100% Radio Interference Voltage Test (RIV)Production testsA complete production test program assures a quality product. Each VariSTAR metal oxide varistor receives a series of 100% electrical tests. Quality is further ensured by a series of destructive tests performed on every batch of varistors. Listed are the tests that are performed on the varistors: 100% Physical In spec tion 100% Discharge Voltage Test 100% V1mA/cm2 100% Leakage Current at 80% of V1mA/cm2 Voltage Batch High Current Short-Duration Test Batch Thermal Stability Test(a) " Leads.

4 (b) 18" 1. Protective CharacteristicsArrester RatingMCOVM aximum Discharge Voltage 8/20 s Current Wave(kV crest)(V rms)(V rms) kA(a)3 kA(a)5 kA(a)10 kA(a)10 kA(b) Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge 2. Performance Test Characteristics*DescriptionCharacteristi csDuty Cycle20 current surges of kA crest 8/20 s waveshape followed by 2 current surges of kA crest 8/20 s waveshapeHigh Current, Short Duration Discharge2 current surges of 10 kA crest 4/10 s waveshapeFeatures and detailed descriptionTable 3. Insulation CharacteristicsArrester Rating (V rms) s Impulse (kV crest)1 min. Dry (kV rms)10 sec.

5 Wet (kV rms)175106635010666501066 Figure 1. Cutaway Illustration of Storm Trapper Arresterotee:NDimensions are given for reference "(73 mm) "(25 mm) "(57 mm)LEAD WIRESNo. 14 Awg, 19 strand, tinnedcopper, 18 inches long,600 volt insulationEPOXY POTTING Provides a weather-proof seal of the leads from the "(51 mm).19" (5 mm) "(93 mm)BUILT-IN SLOTSA ccommodates two mounting screws for horizontal or vertical DISKSH ighly non-linear, metal oxidevaristors provide exceptionalsurge VIEWFRONT "(37 mm).25" (6 mm) "(102 mm)WEATHERPROOF HOUSINGA ssures a lifetime of moistureresistance with a moisture-proof ultrasonic " (6 mm)1/2 -14 THREADEDMOUNTING SHAFTFor attaching to a standard fuse/breaker box knockout -14 THREAD LOCKNUT* Per IEEE Std -1993 Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge 5.

6 Commonly Applied Voltage Ratings of the Storm Trapper ArresterSystem ConfigurationVoltage(Volts rms) Storm Trapper ArresterPhase/WiringMCOV*(Volts rms)Number of Pole(s)See Wiring Diagram(Figure 3)Catalog**NumberSingle-Phase/Two-Wire12 017511 ASZ175B124035011 ASZ350B148065011 ASZ650B160065011 ASZ650B1 Single-Phase/Three-Wire240/12017522 ASZ175B2480/24035022 ASZ350B2 Three-Phase (ungrounded)/Three-Wire24035033 ASZ350B348065033 ASZ650B3 Three-Phase (one-phase grounded)/Three-Wire24035024 ASZ350B248065024 ASZ650B2 Three-Phase (one-phase center-tap grounded)/ Four-Wire240/12035035 ASZ350B3480/24065035 ASZ650B3 Three-Phase/Four-Wire208Y/12017536 ASZ175B3480Y/27735036 ASZ350B3 Table 4.

7 Storm Trapper Catalog NumbersArrester Rating(V rms)Number of PolesCatalog Number without Mounting BracketCatalog Number with Mounting Bracket1751 ASZ175B1 ASZ175B111752 ASZ175B2 ASZ175B211753 ASZ175B3 ASZ175B313501 ASZ350B1 ASZ350B113502 ASZ350B2 ASZ350B213503 ASZ350B3 ASZ350B316501 ASZ650B1 ASZ650B116502 ASZ650B2 ASZ650B216503 ASZ650B3 ASZ650B31 Figure 2. Side View of Storm Trapper arrester with Mounting "(38 mm) "(44 mm)LEAD WIRESARRESTERHOUSINGO rdering informationTo order a VariSTAR Storm Trapper Secondary class MOV surge arrester , determine the voltage rating for the intended application using Table 5 and the ap pli ca ble wiring diagram per Figure 3. Specify the appropriate catalog number from Table 4.

8 Contact your Eaton representative for ap plications not listed..18( mm) .50( mm) .82( mm) .68( mm) .37 DIA( mm) .18 DIA( mm)2- HOLES .18( mm)MOUNTINGBRACKETLOCKNUT .18( mm) .28( mm) .28( mm) .09 R( mm) * Maximum continuous operating voltage (MCOV) is the maximum designated rms value of power frequency voltage that may be applied continuously between the terminals of the arrester .** Mounting bracket option available. Add suffix 1 to change catalog number (Example: A5Z175B11).4 Catalog Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge Diagram 3: Three-phase (ungrounded)/three-wire Diagram 1: Single-phase/two-wire Diagram 2: Single-phase/three-wire Diagram 4: Three-phase (one-phase grounded)/three-wire Diagram 5: Three-phase (one-phase center-tap grounded)/four-wire Diagram 6: Three-phase/four-wire 3.

9 Wiring :NBlack leads to line: white leads to ground. Voltage between a white lead and any black lead should not exceed the arrester NEGROUND OR NEUTRALWHTBLKVOLTAGELI NELI NEGROUND OR NEUTRALWHTBLK240 V(480 V)120 V(240 V)LI NELI NELI NEGROUNDWHTBLK240 V(480 V)240 V(480 V)240 V(480 V)LI NELI NELI NEGROUNDWHTBLK240 V(480 V)240 V(480 V)240 V(480 V)120 V (240 V)120 V (240 V)LI NELI NELI NEGROUNDWHTBLK120 V (277 V)120 V (277 V)208 V (480 V)120 V (277 V)208 V (480 V)208 V (480 V)LI NELI NEGROUND OR NEUTRALWHTBLK240 V(480 V)240 V(480 V)240 V(480 V)5 Catalog Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge Data CA235020 ENEffective August 2015 VariSTAR Storm Trapper Secondary class MOV surge VariSTAR Storm Trapper Secondary class MOV surge arresterEaton1000 Eaton BoulevardCleveland, OH 44122 United s Cooper Power Systems Division2300 Badger DriveWaukesha, WI 53188 United 2015 EatonAll Rights ReservedPrinted in USAP ublication No.

10 CA235020 ENCatalog Data CA235020 ENEffective August 2015 For Eaton s Cooper Power series VariSTAR Storm Trapper surge arrester product information call 1-877-277-4636 or visit: is a registered other trademarks are property of their respective owners.