MELODYC assette-type fan coil units1 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BOPERATING PRINCIPLEThe fan(s) take the air from the room through a to be purified, dehumidified, heated or refrigeratedthrough a chilled or hot water exchanger coil, this air is thendischarged into the room to be air conditioned through 4directional louvers so as to obtain a maximum increase of theair stream and ensure the diffusion by Coanda melody cassette type fan coil units range consists of 5models covering a range of air flow from 290 to 1690 m3/hwhich meet the most stringent sound level models:- single cassette FCU type 61 62-63 - dimensions of 600 x 600 mmceiling tile- double cassette, type 122 - 123 - dimensions of 600 x 1200 mmceiling tileThe melody cassette type fan coil units 61, 62, 63, 122 and123 are available in 3 versions: 2 tube system, heating or cooling operation 2 tube + 2 wire system, cooling + heating/cooling + electricaloperation 4 tube system, cooling and heating MELODYfan coil units are fitted with a 5-speed motor,enabling all the requirements of acceptable sound levels in thevarious rooms to be air conditioned to be melody cassette is a non-independent terminal airconditioning unit installed in suspended c

MELODY Cassette-type fan coil units AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.505 B 1 OPERATING PRINCIPLE The fan(s) take the air from the room through a grille.

Tags:

  Melody

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Cassette-type fan coil units - EUROCONFORT

1 MELODYC assette-type fan coil units1 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BOPERATING PRINCIPLEThe fan(s) take the air from the room through a to be purified, dehumidified, heated or refrigeratedthrough a chilled or hot water exchanger coil, this air is thendischarged into the room to be air conditioned through 4directional louvers so as to obtain a maximum increase of theair stream and ensure the diffusion by Coanda melody cassette type fan coil units range consists of 5models covering a range of air flow from 290 to 1690 m3/hwhich meet the most stringent sound level models:- single cassette FCU type 61 62-63 - dimensions of 600 x 600 mmceiling tile- double cassette, type 122 - 123 - dimensions of 600 x 1200 mmceiling tileThe melody cassette type fan coil units 61, 62, 63, 122 and123 are available in 3 versions.

2 2 tube system, heating or cooling operation 2 tube + 2 wire system, cooling + heating/cooling + electricaloperation 4 tube system, cooling and heating MELODYfan coil units are fitted with a 5-speed motor,enabling all the requirements of acceptable sound levels in thevarious rooms to be air conditioned to be melody cassette is a non-independent terminal airconditioning unit installed in suspended ceilings whichcombines low cost installation and operating advantages ofcentral hot/chilled water production with individual temperaturecontrols in each integrationadapt to aesthetic,financialand material constraintsCIAT takes part in the EUROVENT fan coil unit certification programme, see performances in Eurovent mode, on last page of the list of products and certified characteristics is given in the EUROVENT directory and on the web site .AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BMELODY2 Cassette-type fan coil unitsTECHNICAL DESCRIPTIONACCESSORIES(DELIVERED SEPARATELY)- 100 mm diameter smooth sleeves for treated fresh air 200 mm diameter sleeves for air discharge in an adjacent Diameter 100 mm smooth sleeve with self-adjustable modulefor fresh air DEVICES(DELIVERED IN KIT)- Electromechanical wall-mounted thermostat V30electronic controller V200electronic controller V2000 communicating electronic controller V3000communicating electronic controller LONcontrol, consult grille- Fits perfectly within the suspended ceiling tile White RAL 9010 The manual deflectors are adjustable (3 positions) allowinghomogeneous air distribution throughout the Possibility of closing one or two discharge deflectors withthe coil (2-pipe or 4-pipe system)

3 - Galvanised sheet Copper tubes, aluminium Air vent and partial Nominal pressure: 16 Test pressure: 24 Maximum water temperature: 70 C (2 T).Electrical elements(2 tube + electrical)- Shrouded heating element, stainless tubes, galvanised 2 temperature limiter thermostats (1 auto + 1 manual).Condensates recovery tray- A condensate recovery drain pan in expanded polystyrene,covered with a waterproof Recovery is provided by a draining pump equipped with asafety float and mounted on anti-vibration The auxiliary pan is supplied as an accessory to recover thevalve motor assembly Motor- 5 speeds, 3 of which pre-wired in Closed type, with protected Permanent Automatic open thermal protection in Resilient Supply 230 v/1 ph/50 Hz or 60 Reduced consumption. Fan(s)- Balanced centrifugal impeller with profiled Polymer filter- Located on the detachable grille, easy to remove without Positioned on the fan motor assembly intake, in conformitywith E 36102 Filtering media in renewable polyester Class UL 94 V2, structure- Galvanised sheet Thermal and sound-proofing by foam insulation (3 mm thick)of external with electrical battery, melamine foam (10 mm).

4 Without electrical battery, isolene 100 mm and 200 mm diameter pre-cut holes on the sides forfresh air inlet, allowing the connection of an air discharge ductfor the treatment of adjacent connection box- Connection with pin Separate electrical fan coil units3 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BDIMENSIONSC assette-type fan coil unit only M8 M8 Cassette-type fan coil unit with grille/diffuserAIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BMELODY4 Cassette-type fan coil unitsDIMENSIONSC onnections: supply piping, fresh air and discharge ductsA: Electrical boxAN: Fresh air 100 mm(duct connection - optional)B: Air ventC: Partial drainageE: Cold water outletE1: Hot water coil inlet(4-tube system)EC: Condensates drain 32 mmS: Cold water outletS1: Hot water coil outlet(4-tube system)SG: Adjacent local discharge 200 mm(duct connection - optional)Cassette type fan coil with V200; V2000 ; V3000 controlsSeparate box supplied as an accessory, to be mounted on - Fit the box with 2 Parker screws2 - Fit the coverMELODYMass ADETAIL ADETAIL AMELODYC assette-type fan coil units5 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA B2-way valve kit assembly (option deliveredseparately)The kit includes:- 1 on/off 2-way valve - 1 male/female boss4-way valve kit assembly (option deliveredseparately)The kit includes:- 1 on/off 4-way valve - 1 male/female bossMELODYABC ooling coilValve inlet E/outlet SHeating coilValve inlet E1/outlet S161 - 6295105 1/2 1/2 6395105 3/4 1/2 122 - 123550560 3/4 1/2 184118157258B50S1SE1E70A95105184118157B5 0S1SE1E70A2589510518411815725870AS1SE1EB 5010512518411815725870AB50S1SE1E105125V2 000.

5 V3000 2-way valve kit assembly(option delivered separately)The kit includes:- 1 controller in a separate electrical box- 1 progressive 2-way valve (24V)- 1 user s terminalV2000 ; V3000 4-way valve kit assembly(option delivered separately)The kit includes:- 1 controller in a separate electrical box- 1 progressive 4-way valve (24V)- 1 user s terminalMELODYABC ooling coilValve inlet E/outlet SHeating coilValve inlet E1/outlet S161 - 6295105 1/2 1/2 6395105 3/4 1/2 122 - 123550560 3/4 1/2 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BMELODY6 Cassette-type fan coil unitsPre-selected factory water temp.: 90/70 C, winter air temp.: 19 C - Cold water temp.: 7/12 C, summer air temp.: 27 C 50% RHComfort level: attenuation level of room and installation: 12 dBA(1) The supply air temperature should not exceed 65 C (CIAT recommendation).Fresh air intake and air discharge into an adjacent roomOn one side of the cassette, pre-punched openings enable separate fresh air intake and air discharge duct connections into anadjacent room.

6 (1) The fresh air flow must not exceed 20% of the nominal flow.(2) Air flow given for a 5 m duct with a 90 elbow and one louvre closed on the duct outlet. Decompression with a return air grilleshould be provided in the adjacent flow (high speed)m3/h74086089016401690(1) Fresh air flowm3/h748689164169(2) Air flow into adjacent roomm3 flowm3/h2-pipe system4-pipe systemComfortlevelISO or NRAir temperature meanrise in electric heater230/1/50 HeatingcapacityWCooling capacityWHeatingcapacityWCooling capacityWTotaleSensibleTotaleSensible900 W1500 W3000 W61R17409 6102 8202 3502 4402 3002 1301 0601 8101 0801 5301 0004 7903 5505 0404 1603 7004 1403 0404 2703 6602 0003 6402 6603 6903 2602 1003 1002 1602 7602 8102 1502 5301 6802 2902 3601 0006 3904 2606 6005 5903 86044-5-R273015 9005 5003 5805 9804 7603 0004 6602 9805 1403 9802 1003 6902 3404 3403 1002 1603 0201 9203 7402 6701 70023-12-122R1164027 8009 5607 1109 5708 4906 1008 2606 1308 7107 3605 1007 2805 3007 9206 5404 1006 1104 2806 1505 6004 6005 0703 3304 8504 7003 00012 8008 54012 20011 2007 00011 0007 26011 1009 4806 8009 2805 9709 7507 9205 1007 3304 6708 2306 3404 3005 9603 8207 0805

7 3003 fan coil units7 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA BMELODY616263122123 Power input in W R1808993179185R2607074140147R34356591111 18R42940428184R52331326163 Absorbed current in 2-pipe system coil0,51,01,52,33,34-pipe system coilCooling-0,71,31,93,1 Heating-0,10,30,30,6 Supply pipe diameter (tapped connectors)MELODY61 - 6263 - 122 - 123 Standard 2-pipe system coilG 3/8G 1/24-pipe system coilCoolingG 3/8G 1/2 HeatingG 3/8G 3/8 Electrical characteristics (230 V - 1 ph - 50 Hz or 60 Hz) - FanMotorrefElectrical characteristics (230 V - 1 ph - 50 Hz or 60 Hz) - Electric heaterMELODY61 62 - 63122 - 123power 900 Wpower 1500 Wpower 3000 WNumber of elements112 IntensityA3,96,513 Automatic reset safety thermostat1 automatic + 1 manual1 automatic + 1 manual2 automatic + 2 manualSupply wiresmm23 G 1,53 G 1,53 G 1,5 Fuse (type GL)A6816 TECHNICAL AND ELECTRICAL CHARACTERISTICSCoil content (litres)TARIF HT(MAT RIEL EN STOCK)Cooling or heating 2-pipe cassette type fan coil unitCoil2-pipes cooling or heatingMELODY 612 TFC622 TFC632 TFC1222 TFC1232 TFCAir handling section + External auxiliary drain panCode391209239120953912098391210439121 07 Diffusion grilleCode39432923943294 TotalCodeC063754C063762C063800C063886C06 3894 DescriptionMO7 Smooth spigot 100 mm with air flow ratecontroller, with integrated gasket.

8 Packed with nutsand screws and a air flow rate controller is designed to supply adetermined flow** with air differential pressurebetween 50 and 100 Pa.** 3 flow rates are available by use of3 clips. The lower air flow is by **Code7013440 MO460 / 75 /90m3/h**Code7013544 MO1- Smooth sleeve alone (OD: 100 mm).Screws and bolts supplied M17 Smooth sheet metal circular discharge sleeve RA12 piece male/female connector 3/8" < 1/2"seals + 5200708 RA22 piece male/female connector 1/2" < 3/4"seals + 5202079 Cooling 2-pipe coil + electric heater cassette type fan coil unitCoil2-pipe cooling + electric heaterHeater900 W1500 W3000 WMELODY 612 TFC-E622 TFC-E632 TFC-E1222 TFC-E1232 TFC-EAir handling section + External auxiliary drain panCode719502339120973912100391210639121 09 Diffusion grilleCode39432923943294 TotalCodeC063843C063851C063878C063924C08 3932 Coil4-pipe cooling or heatingMELODY 624 TFC634 TFC1224 TFC1234 TFCAir handling section + External auxiliary drain panCode3912096391209939121053912108 Diffusion grilleCode39432923943294 TotalCodeC063827C063835C063908C063916 AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA

9 BMELODY8 Cassette-type fan coil unitsTARIF HT(MAT RIEL EN STOCK)Cooling or heating 4-pipe cassette type fan coil unitAccessories are in stock to meet your requirements at short (SUPPLIED SEPARATELY)This document is part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior office Avenue Jean Falconnier - 1401350 - Culoz - FranceTel.: +33 (0)4 79 42 42 42 - Fax: +33 (0)4 79 42 42 10e-mail: - IIndustrielle d AApplications TThermiques - with a registered capital of 26 000 000 - Belley B 545 620 114 CIAT ServiceTel.: +33 (0)4 79 42 42 90 - Fax: +33 (0)4 79 42 42 13