Cavity fire barriers Cavity fire barriers fire separation within concealed spaces Floors and ceilings C06. Cavity fire barriers Cavity fire barriers Regulatory requirements demand that cavities 30 60. and concealed spaces, in the structure or fabric mins of a building, are sub-divided or sealed by means of Cavity barriers or fire -stopping to restrict the hidden spread of smoke and flames. This is of prime importance since many buildings are honeycombed with concealed cavities and voids within the roofs, floors, and walls. Key benefits Cavity barrier performance options to match partition performances up to 60 minutes fire resistance fire separation is maintained throughout Floors and ceilings the life of the building due to the board lining being mechanically fixed High level of component commonality with GypWall partition systems C06.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C06. S09. P447 C06 Cavity fire barriers Floors and ceilings mins 30 60 Cavity fire barriers

Tags:

  Barriers, Fire, Saint, Gabion, Cavity, Cavity fire barriers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Cavity fire barriers - Gyproc Ireland

1 Cavity fire barriers Cavity fire barriers fire separation within concealed spaces Floors and ceilings C06. Cavity fire barriers Cavity fire barriers Regulatory requirements demand that cavities 30 60. and concealed spaces, in the structure or fabric mins of a building, are sub-divided or sealed by means of Cavity barriers or fire -stopping to restrict the hidden spread of smoke and flames. This is of prime importance since many buildings are honeycombed with concealed cavities and voids within the roofs, floors, and walls. Key benefits Cavity barrier performance options to match partition performances up to 60 minutes fire resistance fire separation is maintained throughout Floors and ceilings the life of the building due to the board lining being mechanically fixed High level of component commonality with GypWall partition systems C06.

2 ROI: 1800 744480 NI: 0845 3990159 C06. S09. P447. Cavity fire barriers performance Cavity fire barriers For details of when to specify fire Cavity fire barriers typical applications resistance using EN. Refer to C02. S01. P18. Table 1a Solutions to satisfy the requirements of BS EN 1364-1: 1999. 1 2. Gypframe 48 S 50 C' Stud framework 63mm x 38mm timber stud framework with studs at 600mm centres. with studs at 600mm centres. Linings each side, as in table, fixed using Linings each side, as in table, fixed using Gyproc Drywall Screws at 300mm Gyproc Drywall Screws at 300mm centres. fire -stopping material, centres. 25mm Isover Acoustic Roll in stone mine al wool to the perimeter the Cavity . fire -stopping material, as stone mineral wool to the perimeter as Detail Board type Lining thickness fire resistance System mm Integrity minutes Insulation minutes reference 1 Gyproc WallBoard 1 x 15 30 30 A206002.

3 2 Gyproc WallBoard 1 x 15 30 30 A026010. 1 Glasroc F multiboard 1 x 60 60 G106010. Floors and ceilings 1. Refer to construction details 1 and 2. For details of when to specify fire resistance using BS. Refer to C02. S01. P18. Table 1b Solutions to satisfy the requirements of BS 476: Part 8: 1972 or BS 476 Part 22:1987. C06. 1 2 3. Gypframe 48 S 50 C' Stud framework 75mm x 50mm timber stud framework Gypframe 48 S 50 metal C' Stud with studs at 600mm centres. Linings, with studs at 600mm centres. Linings, framework with studs at 600mm as in table, fixed using Gyproc Drywall as in table, fixed using Gyproc Drywall centres. Linings each side, as in table, Screws at 300mm centres. fire -stopping Screws at 300mm centres. fire -stopping fixed using Gyproc Drywall Screws at material, stone mineral wool to the material, stone mineral wool to the 300mm centres.

4 fire -stopping material, perimeter as perimeter as stone mineral wool to the perimeter as Detail Board type Lining thickness fire resistance System mm Integrity minutes Insulation minutes reference 1 Glasroc F multiboard 1 x 10 30 15 G110001. 2 Glasroc F multiboard 1 x 10 30 15 G110002. 2 Gyproc FireLine 1 x 30 15 E106002. 3 Glasroc F multiboard 1 x 6 (both sides) 30 15 G110003. 1. Refer to construction details 1 and 2. The fire resistance and sound insulation performances are for imperforate partitions, with all joints taped and filled, or skimmed according to Gyproc 's recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and the Company's fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc .

5 C06. S09. P448 Cavity fire barriers design Cavity fire barriers Planning key factors The maximum distance between barriers must be appropriate to the location of each Cavity . Also, due consideration must be given to Important information the class of surface exposed within the Cavity . Fixings through the Cavity barrier framework into the structural soffit must It is also important that smoke and flames are restricted from be capable of supporting the weight of passing from any Cavity in a building element directly into a room or the entire Cavity barrier construction. another Cavity . Therefore, a Cavity must be closed by a Cavity barrier at every junction with another Cavity . Any Cavity contained within Gyproc ceiling solutions are not intended an element is also required to be closed by a Cavity barrier around to provide any support to the Cavity the perimeter of any opening through the element.

6 The closure barrier. of cavities may already be provided by the construction itself, where a Gyproc partition system prevents the continuation of cavities at a T' junction. fire stopping Smoke and flames must also be restricted from by-passing any A Cavity barrier must be tightly fitted to a rigid construction, building elements that are required to have fire resistance. Any or, if it abuts against slates, tiles, corrugated sheeting, or other Cavity crossing the edges or ends of a fire resistant element should construction to which it cannot be so fitted, then it must be suitably have a Cavity barrier provided in the same plane as the element, fire -stopped at the junction. Refer to construction details 1 - 2, refer to construction details 3 and 4. There are certain exceptions which show fire -stopping solutions using stone mineral wool.

7 To this requirement, such as cavities in floors and roofs where the ceilings provide a minimum of 30 minutes fire resistance in addition Any services running through a fire Cavity barrier should be Floors and ceilings to satisfying other stipulated requirements. fire -stopped using suitable materials, shown by test to maintain the fire resistance within that construction. Cavity barriers must maintain their performance during the life of a building, taking account of any possible building movement due to subsidence, shrinkage, or thermal change. In addition, the possible failure of its fixings or adjacent construction in the event of a fire , and the collapse in a fire of any permitted services penetrating the C06. Cavity barrier, should be considered. ROI: 1800 744480 NI: 0845 3990159 C06.

8 S09. P449. Cavity fire barriers construction details Cavity fire barriers 1 2. 11. 10 10. 11 3. 4. 1. 1. 2. 5 5. 9 9. 6 6. 7 7. Sub-division of ceiling void using Sub-division of ceiling void using timber framed Cavity barrier Gypframe metal framed Cavity barrier 3 4. 2. Floors and ceilings 1. 1 12. 2. 7. 7. C06. Sub-division or partition Cavity Cavity barrier at T' junction of partitions 1 Gyproc plasterboard or Glasroc F specialist board forming Cavity fire barrier 8 Isover insulation 2 Gypframe C' Stud 9 Gypframe FEA1 Steel Angle 3 Gypframe Folded Edge Standard Floor & Ceiling Channel 10 Concrete soffit 4 Timber framing 11 Fixing to soffit (by others) suitable for weight of Cavity barrier construction 5 Stone mineral wool fire -stopping 12 Gyproc Sealant 6 Suspended grid ceiling 7 Gyproc plasterboard C06.

9 S09. P450 Cavity fire barriers system components Cavity fire barriers Gypframe metal components Gypframe C' Studs (48 S 50, 60 S 50, 70 S 50, Gypframe Folded Edge Standard Floor & Ceiling 70 S 60, 92 S 50, 92 S 60, 92 S 10, 146 S 50) Channels (50 FEC 50, 62 FEC 50, 72 FEC 50, 94 FEC 50, Vertical stud designed to receive fixing of board. 148 FEC 50). Standard floor and ceiling channels for retaining Gypframe studs at floor and ceiling junctions. Gypframe FEA1 Steel Angle Timber Framing (by others). Steel angle providing framing stability and To suit. board support. Board products Gyproc WallBoard Gyproc FireLine1. Standard gypsum plasterboard. Gypsum plasterboard with fire resistant additives. Gyproc Moisture Resistant Glasroc F multiboard Gypsum plasterboard with moisture resistant Non-combustible glass-reinforced gypsum board.

10 Floors and ceilings additives in the core and special green lining paper for easy recognition. 1. Also available in Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas. Fixing products C06. Gyproc Drywall Screws Gyproc Jack-Point Screws Corrosion resistant self-tapping steel screws for Corrosion resistant self-tapping steel screws fixing board-to-timber and board-to-metal framing for fixing board to metal framing thick and less than thick. greater ( I' stud thick and greater). Gyproc Collated Drywall Screws Gyproc Wafer Head Drywall Screws Corrosion resistant self-tapping steel screws for Corrosion resistant self-tapping steel screws fixing board-to-timber and board-to-metal framing for fixing metal to metal framing less than less than thick. thick.