Transcription of Commercial Solar Sizing & Installation Guidelines
1 Technical Design Guide1 Commercial Solar Sizing & Installation GuidelinesConsiderations when installing a Solar thermal SystemRenewablesTechnical Design Guidance Document2 IMPORTANTThis document is for guidance only. All solarsystems should be fully designed by acompetent Group Plc or any of its companiesdo not take responsibility for any systemsdesigned using the following details. Forsystem design assistance, please contactour technical support team:+44 (0) 28 3836 4500 All descriptions and specifications of products and procedures in this guide are current atthe time of printing.
2 However, Kingspan Renewables is continually involved in product testingand improvement, and specifications and procedures are subject to change. We reserve theright to amend specifications and procedures without prior Choose Kingspan Solar ?With over 30 years of experience, theThermomax brand is firmly established asa world leader in Solar thermal Solar offer quality, market-leadingcomplete packages for all your solarrequirements. Each package is customdesigned for each specific application. Ourpremium quality Solar panels and hot waterstorage cylinders are sized and specifiedto meet the requirements of each individualproject.
3 A number of accessories are alsoavailable to enhance the this guide varioussuggestions have been made for systemdesign and Installation . You are stronglyadvised to follow these suggestions,however,final design of any Installation isleft to the discretion of the and StandardsThe Solar water heating system should beinstalled in compliance with current buildingregulations, all local standards and Health& Safety regulations. These regulations arestatutory documents and take priority over allrecommendations within this Installation and operating procedures,please refer to the Installation and Operatingmanuals provided with the ForumDesign Awardfor Excellence inProduct DesignThermomax products werethefirst to receive theEuropean quality mark forsolar collectors -The Solar .
4 0405081113 CollectorsinstallationThe Solar circuitFrost protectionStagnationpreventionPump Stationsand SafetyComponentsSolar LoadingModule and FreshWater ModulesControlsystemCommissioningAppendi x 1 -Steam ReachAppendix 2 -Pump Sizing4 Commercial Solar Sizing & Installation GuidelinesCollectors collector array size:150 Thermomax tubes (DF100, HP200, HP250, Varisol)8 no. Flat Plates(CLS1808, CLS2108, CLS2510)8 no. Flat Plates(FP200V, FP240V)5 no. Flat Plates(FP200H)4 no. Flat Plates(FP240H) wide variety of mounting kits is available to suit almost any collectors are arranged in banks or laid flat, sufficient space ofapproximately 500mm should be left between each bank to allow for to the wind turbulence around the edges of the roof.
5 We recommend thatapproximately 1 metre should be allowed between the collectors and the edgeof the should NOT be left exposed for long periods before exposure to the sun when fluid is not being circulated through the systemwill cause significant degradation of the fluid and possible damage to solarcollectors. Collectors should only be installed when the required plant,cylinders, pipework and controls etc have been installed and collectors need to be installed for more than a few days before thesystem is commissioned, collector covers are available to prevent is also possible to rotate the tubes in Thermomax panels (DF range only) toprevent the selective absorber coating (blue side)
6 Being exposed to the , although this will minimise the Solar irradiation falling on theabsorbers, it is only recommended for short and Varisol DF collector tubes cannot be rotated when there ispressure in the hydraulic system. Tubes must be correctly orientatedbefore the system is Solar Sizing & Installation GuidelinesThe Solar for the collector array should be sized based on the followingconditions:For Thermomax tube systems. Solar loop volume flow rate:60 l/hr/m2<12m2collector area &40 l/hr/m2 >12m2 collector flat panel systems. Solar loop volume flow rate: 60 l/hr/m2<12m2collector area & 40 l/hr/m2 >12m2 collector area.
7 For low flow systems: 25l/hr/m2 (flat panel only)Please note, Thermomax tube systems cannot be used with low flow maximum flow velocity in the pipework should not exceed pipework for the Solar circuit must be fully insulated. The thickness of theinsulation should be greater than or equal to the internal pipe collector arrays with multiple banks of panels it is important that the correctflow rate is achieved on each bank of collectors. Incorrect flow rates, inparticular low flow rates on individual banks can reduce the overall efficiency ofthe system. In extreme cases the individual bank may stagnate and this couldresult in damage to the collectors and other system two methods to best achieve the correct hydraulic balance are hightemperature balancing valves or a reverse-return (Tichelmann) Solar rated balancing valves (flowsetters) on each bank are thepreferred method of achieving the correct flow rates.
8 Where the collectorbanks contain varying numbers of panels or differently sized panels this isthe only method of achieving the correct flow each of the collector banks are identical in construction a reverse-return (Tichelmann) pipe arrangement may be must be taken to ensure the same fittings and components are usedon each bank connection. In this way the pressure loss across each branchwill be the pipe materials for Solar thermal systems are smooth bore copper,black mild steel or stainless steel. Under no circumstances should plastic orPEX pipe be used.
9 Corrugated stainless steel may be used however, the highpressure loss per length of pipe for this material means it will be unsuitable forall but the smallest pipe must not be used as it reacts with glycol based heattransfer fluids making them ineffective for frost Solar Sizing & Installation Guidelines6 thermal coefficient of linear expansion of copper is x 10-6 per C . In largesolar systems the pipe work connecting the collectors may be subject toextreme changes in temperature from subzero in winter to over 170 C in theevent of stagnation. Therefore a 10 metre length of copper tube, irrespective ofits size, wall thickness or temper, could change in length by up to mm (inthe temperature range of -25 C to 175 C).
10 Pipes installed on Solar thermal systems must be free to accommodate thisexpansion, otherwise stresses will build up in the pipework, which may lead tojoints being pulled apart and/or tubes fracturing. The magnitude and frequencyof such changes in length can result in the reduced life of the joint or failure ofthe pipe within a short loops, horseshoes or changes of direction in the pipework are commonlyemployed to compensate for thermal expansion. If bellows or gland type jointsare used they must be rated for the high temperatures experienced in solarthermal Solar Sizing & Installation GuidelinesFrost ProtectionAnti-Freeze Protection & areas prone to sub-zero temperatures for part of the year, care must betaken prevent the heat transfer fluid from freezing and causing damage insidethe collector, external pipework or heat exchanger.