Data Sheet DS/266XRH-EN Rev. A Model 266DRH Differential ...

Model 266 DRH Differential Model 266 PRH and 266 HRH Gauge Model 266 VRH and 266 NRH AbsoluteData Sheet DS/266 XRH-EN Rev. ABase accuracy from % of calibrated spanReliable sensing system coupled with very latest digital technologies provides large turn down ratio up to 60:1 Comprehensive sensor choice optimize in-use total performance and stabilityFlexible configuration facilities provided locally via local LCD keypad 2600T Series Pressure TransmittersEngineered solutions for allapplicationsNew TTG (Through-The-Glass) keypad technology allows quick and easy local configuration without opening the cover, even in explosion proof environmentsIEC 61508 certification for SIL2 (1oo1) and SIL3 (1oo2) applicationsPED compliance to sound engineering practice (SEP)2 DS/266 XRH-EN Rev.

reference at armospheric or vacuum pressure respectively for gauge or absolute measure. The following table list the types of standard seal which can be combined with 266xR transmitters. Refer to seal data sheet for all data and details relevant to seal element.

Tags:

  Transmitter, Vacuum

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Data Sheet DS/266XRH-EN Rev. A Model 266DRH Differential ...

1 Model 266 DRH Differential Model 266 PRH and 266 HRH Gauge Model 266 VRH and 266 NRH AbsoluteData Sheet DS/266 XRH-EN Rev. ABase accuracy from % of calibrated spanReliable sensing system coupled with very latest digital technologies provides large turn down ratio up to 60:1 Comprehensive sensor choice optimize in-use total performance and stabilityFlexible configuration facilities provided locally via local LCD keypad 2600T Series Pressure TransmittersEngineered solutions for allapplicationsNew TTG (Through-The-Glass) keypad technology allows quick and easy local configuration without opening the cover, even in explosion proof environmentsIEC 61508 certification for SIL2 (1oo1) and SIL3 (1oo2) applicationsPED compliance to sound engineering practice (SEP)2 DS/266 XRH-EN Rev.

2 A | 2600T Series Pressure transmitters 266 DRH, 266 PRH, 266 HRH, 266 VRH, 266 NRHM odel 266 DRH Differential Model 266 PRH and 266 HRH Gauge Model 266 VRH and 266 NRH AbsoluteSeal modelSeal typeSeal diaphragm size (thickness)MnemonicS26 WAS26 WEWafer (ASME and EN standards) in. /DN in. / DN 50P23 in. / DN in. /DN 40 (low) in. / DN 50 (low)F23 in. / DN 80 (low)F3S26 FAS26 FES26 RAS26 REFlanged flush diaphragm (ASME and EN standards; fixed and rotating flange)2 in. / DN 50P23 in. / DN 80P34 in. / DN 100P32 in. / DN 50 (low)F23 in. / DN 80 (low)F34 in. / DN 100 (low)F3 Flanged extended diaphragm (ASME and EN standards; only rotating flange S26RA and S26RE)2 in. / DN 50E23 in. / DN 80E34 in. / DN 100P3S26 RJFlanged flush diaphragm (JIS standards; only rotating flange)A 50P2A 80P3A 100P3S26 RRFlanged flush diaphragm (Ring Joint ASME standards; rotating flange) Chemical Tee3 off-line flanged2 1/2 , S26 MEOff-line flanged (ASME and EN standards)2 1/2 nut, TriclampCherry BurrelSanitary, Aseptic2 in.

3 / F50S23 in. / F80S34 and Socket2 1/2 connection type1 1/2 type1 serviceflanged1 1/2 1/2 descriptionModels detailed in this data Sheet apply for those transmitters which include one or two remote seal(s) connected via a capillary to the transmitter sensor. Depending on the selected ordering code the following models are available:a) Model 266 DRH which allows a Differential measurement using either two remote seals of same type and size or one remote seal (on positive or negative side) and a standard threaded connection direct 1/4 18 NPT on flange or 1/2 14 NPT through adapter, for the wet or dry leg on the side opposite to ) models 266 PRH or 266 VRH allowing gauge or absolute measurement respetively with the reference side at atmosphere or at vacuum .

4 The other side which can be the positive or negative (high or low pressure side) features the required remote 266HR or 266NR have the remote seal on the positive side and the user can select the suitable code for having the reference at armospheric or vacuum pressure respectively for gauge or absolute measure. The following table list the types of standard seal which can be combined with 266xR transmitters. Refer to seal data Sheet for all data and details relevant to seal element. All following data apply for identical characteristics of the two sides when the transmitter is Differential with two Series Pressure transmitters 266 DRH, 266 PRH, 266 HRH, 266 VRH, 266 NRH | DS/266 XRH-EN Rev. A 3( ) Lower Range Limit is kPa abs, mbar abs, 1 mmHg for inert Galden or kPa abs, 4 mbar abs, 3 mmHg for inert limitsMaximum span = URL (can be further adjusted up to URL (TD = ) for Differential models, within the range limits)IT IS RECOMMENDED TO SELECT THE transmitter SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE suppression and elevationZero and span can be adjusted to any value within the range limits detailed in the table as long as.

5 Calibrated span minimum spanFunctional SpecificationsRange and span limitsSensorCodeUpper RangeLimit (URL)Lower Range Limit (LRL)Minimum span266 DRHdifferential266 PRHgauge266 VRHabsolute266 HRH gauge266 NRH absoluteB4 kPa-4 kPa40 mbar-40 mbar2 mbar16 inH2O-16 inH2OE16 kPa-16 kPa-16 kPa abs ( ) kPa160 mbar-160 mbar-160 mbar abs ( )8 mbar64 inH2O-64 inH2O-64 mmHg ( ) inH2OF40 kPa-40 kPa-40 kPa abs ( ) kPa400 mbar-400 mbar-400 mbar abs ( ) mbar160 inH2O-160 inH2O-160 mmHg ( ) inH2OG65 kPa-65 kPa-65 kPa abs ( )-65 kPa abs ( ) mbar-650 mbar-650 mbar abs ( )-650 mbar abs ( )11 mbar260 inH2O-260 inH2O-260 mmHg ( )-260 mmHg ( ) inH2OH160 kPa-160 kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa1600 mbar-1600 mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar642 inH2O-642 mmHg ( ) mmHg ( ) mmHg ( ) mmHg ( ) inH2OM600 kPa-600 kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa abs ( )10kPa6 bar-6 mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar abs ( ) bar87 psi-87 mmHg ( ) mmHg ( ) mmHg ( ) mmHg ( ) psiP2400 kPa-2400 kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa abs ( )40 kPa24 bar-24 mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar abs ( ) bar348 psi-348 mmHg ( ) mmHg ( ) mmHg ( ) mmHg ( ) psiQ8000 kPa-8000 kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa abs ( )134 kPa80 bar-80 mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar abs ( ) bar1160 psi-1160 mmHg ( ) mmHg ( ) mmHg ( ) mmHg ( )

6 PsiS16000 kPa-16000 kPa abs ( ) kPa abs ( ) kPa abs ( ) kPa abs ( )267 kPa160 bar-160 mbar abs ( ) mbar abs ( ) mbar abs ( ) mbar abs ( ) bar2320 psi-2320 mmHg ( ) mmHg ( ) mmHg ( ) mmHg ( ) psiV60000 kPa abs ( )1000 kPa600 mbar abs ( )10 bar8700 mmHg ( )145 psiDampingSelectable time constant : between 0 and 60 sThis is in addition to sensor response on timeOperation within specification in less than 10 s with minimum resistance > 100 M at 500 V DC (terminals to earth)4 DS/266 XRH-EN Rev. A | 2600T Series Pressure transmitters 266 DRH, 266 PRH, 266 HRH, 266 VRH, 266 NRHM odel 266 DRH Differential Model 266 PRH and 266 HRH Gauge Model 266 VRH and 266 NRH AbsoluteOperative limitsREFER ALSO TO S26X DATA Sheet FOR POSSIBLE FURTHER LIMITATION DUE TO SEAL VARIANTS Pressure limits.

7 Overpressure limitsWithout damage to the transmitterModels 266 DRH, 266 PRH, 266 VRHFill fluidOverpressure limitsSensor F to SSilicone kPa abs, mbar abs, mmHgand 21 MPa, 210 bar, 3045 psi (1)Sensor ESilicone kPa abs, mbar abs, mmHgand 16 MPa, 160 bar, 2320 psi Sensor BSilicone kPa abs, mbar abs, mmHgand 7 MPa, 70 bar, 1015 psi Sensor F to SInert (Galden) kPa abs, mbar abs, 1 mmHgand 21 MPa, 210 bar, 3045 psi (1) Sensor EInert (Galden) kPa abs, mbar abs, 1 mmHgand 16 MPa, 160 bar, 2320 psi Sensor F to SInert (Halocarbon) kPa abs, 4 mbar abs, 3 mmHg and 21 MPa, 210 bar, 3045 psi (1) Sensor EInert (Halocarbon) kPa abs, 4 mbar abs, 3 mmHg and 16 MPa, 160 bar, 2320 psi (1) 16 MPa, 160 bar, 2320 psi for AISI 316 ss NACE boltingModels 266 HRHand 266 NRHFill fluidOverpressure limitsSensor P, Q, SSilicone kPa abs, mbar abs, mmHg and 21 MPa, 210 bar, 3045 psiSensor G, H, MSilicone kPa abs, mbar abs, mmHg and 14 MPa, 140 bar, 2030 psi Sensor P, Q, SInert (Galden) kPa abs, mbar abs, 1 mmHg and 21 MPa, 210 bar, 3045 psi Sensor G, H, MInert (Galden) kPa abs, mbar abs, 1 mmHg and 14 MPa, 140 bar, 2030 psi Sensor P, Q, SInert (Halocarbon) kPa abs, 4 mbar abs, 3 mmHg and 21 MPa, 210 bar, 3045 psi Sensor G, H, MInert (Halocarbon)

8 KPa abs, 4 mbar abs, 3 mmHg and 14 MPa, 140 bar, 2030 psi Sensor VSilicone kPa abs, mbar abs, mmHg and 90 MPa, 900 bar, 13050 psiStatic pressure limitsTransmitters for Differential pressure Model 266 DRH operates within specifications between the following limits:SensorsStatic pressure limitsSensor F to Swith 2 kPa abs, mbar abs, mmHg and 21 MPa, 210 bar, 3045 psi (1)Sensor F to Swith 1 kPa abs, 13 mbar abs, psiaand 21 MPa, 210 bar, 3045 psi (1)Sensor Ewith 2 kPa abs, mbar abs, mmHg and 16 MPa, 160 bar, 2320 psiSensor Ewith 1 kPa abs, 13 mbar abs, psia and 16 MPa, 160 bar, 2320 psiSensor Bwith 2 kPa abs, mbar abs, mmHg and 7 MPa, 70 bar, 1015 psi Sensor Bwith 1 kPa abs, 13 mbar abs, psia and 7 MPa, 70 bar, 1015 psi (1) 16 MPa, 160 bar, 2320 psi for AISI 316 ss NACE bolting Overpressure and static upper limit can be derated by the flange rating of seal.

9 Refer to relevant S26 data sheetProof pressureThe transmitter can be exposed without leaking to line pressure of up to ModelSensorProof pressure266 DRHS ensor F to MPa, bar, 5836 psiSensor MPa, 315 bar, 4567 psiSensor B14 MPa, 140 bar, 2030 psi266 PRH266 VRHS ensor F to MPa, bar, 5836 psiSensor MPa, 315 bar, 4567 psi266 HRH266 NRHS ensor G, H, M28 MPa, 280 bar, 4060 psiSensor P, Q, MPa, bar, 5836 psi266 HRHS ensor V90 MPa, 900 bar, 13050 psior two times the flange rating of seal, whichever is ANSI/ISA S hydrostatic test Series Pressure transmitters 266 DRH, 266 PRH, 266 HRH, 266 VRH, 266 NRH | DS/266 XRH-EN Rev. A 5 Temperature limits C ( F) :Ambientis the operating temperatureModels 266 DRH, 266 PRH, 266 VRHA mbient temperature limitsSilicone oil for sensor F to S-40 and 85 C (-40 and 185 F)Silicone oil for sensor B andE-25 and 85 C (-13 and 185 F)Inert (Galden) for sensor F to S-20 and 85 C (-4 and 185 F)Inert (Galden) for sensor E-10 and 85 C (14 and 185 F)Inert (Halocarbon) for sensor F to S-20 and 85 C (-4 and 185 F)Inert (Halocarbon) for sensor E-10 and 85 C (14 and 185 F) Model 266 HRH - 266 NRHA mbient temperature limitsSilicone oil for sensor G to V-40 and 85 C (-40 and 185 F)Inert (Galden) for sensor G to S-20 and 85 C (-4 and 185 F)Inert (Halocarbon) for sensor G to S-20 and 85 C (-4 and 185 F)

10 Models 266 XRH Ambient temperature limitsLCD integral display-40 and 85 C (-40 and 185 F)LCD display may not be clearly readable below 20 C ( 4 F) or above +70 C (+158 F)IMPORTANTFor Hazardous Atmosphere applications see the temperature range specified on the certificate/approval relevant to the aimed type of protectionProcessModel 266 DRH (side without seal)Process temperature limitsSilicone oil for sensor F to S-40 and 121 C (-40 and 250 F) (1)Silicone oil for sensor B and E-25 and 121 C (-13 and 250 F) (1)Inert (Galden) for sensor F to S-20 and 100 C (-4 and 212 F) (2)Inert (Galden) for sensor E-10 and 100 C (14 and 212 F) (2)Inert (Halocarbon) for sensor F to S-20 and 100 C (-4 and 212 F) (2)Inert (Halocarbon) for sensor E-10 and 100 C (14 and 212 F) (2)Viton gasket-20 and 121 C (-4 and 250 F)(1) 100 C (212 F) for application below atmospheric pressure(2) 65 C (150 F) for application below atmospheric pressureThe following table show characteristics of fill fluids when used in transmitters with remote seal(s).