Transcription of DESCRIPTION WARRANTY TECHNICAL GUIDE
1 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALETECHNICAL GUIDEMODELS: GY9F*DHGAS-FIREDCONDENSING / HIGH EFFICIENCYDOWNFLOW/HORIZONTAL FURNACES95% AFUENATURAL GAS64 - 80 MBH INPUTDue to continuous product improvement, specifications are subject to change without us on the web at for the most up-to-date TECHNICAL rating information can be found at 9001 Certified QualityManagement System339033-YTG-A-0607 DESCRIPTIONT hese Category IV, highly efficient, compact, condensingtype furnaces are designed for residential and commercialinstallations in a basement, closet, alcove, recreation room orgarage where the ambient temperature is above 32 F, orhigher. They may be either side wall or thru-roof vented usingapproved plastic type combustion air and vent piping.
2 Allunits are factory assembled, wired and tested to assuredependable and economical installation and limited WARRANTY on both heat exchangers to the orig-inal purchaser; a 20-year limited WARRANTY from original instal-lation date to subsequent WARRANTY on the heat exchanger in commercial limited parts Compact, easy to install, ideal height 40" cabinet Blower-off delay for cooling SEER improvement. Easy to connect power/control wiring. Built-in, high level self diagnostics with fault code display. Low unit amp requirement for easy replacement applica-tion. Integrated control module for reliable, economical opera-tion. May be installed as either two-pipe (sealed combustion) or single pipe vent (using indoor combustion air) Top intake & vent connection allows downflow installa-tion in narrow locations.
3 Electronic Hot Surface Ignition saves fuel cost with increased dependability and reliability. Induced combustion system with inshot main burners for quiet, efficient operation. No special vent termination kit required. 100% shut off main gas valve for extra safety. PSC four speed, direct drive motor with large, quiet blower. 24V, 40 VA control transformer and blower relay supplied for add-on cooling. Hi-tech tubular aluminized steel primary heat exchanger. Secondary (condensing) heat exchanger of 29-4C high-grade stainless steel. Timed on, adjustable off blower capability for maximum comfort. Easy access from front of unit for cleaning, maintenance or service. Protection from intake, exhaust or condensate Products Group339033-YTG-A-0607 Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local furnace shall be installed so that the electrical components are protected from size and overcurrent protection must comply with the National Electric : 1.
4 For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea Wire size based on copper conductors, 60 C, 3% voltage Continuous return air temperature must not be below 55 All filters must be high velocity cleanable IMAGESUPPLY ENDTOP IMAGERETURN ENDLEFT SIDERIGHT SIDEHORIZONTAL CONDENSATEDRAIN OPENING 2 JUNCTION BOXHOLE 7/8 GAS PIPE ENTRY 1-1/2 CONDENSATE DRAINHOLE 7/8 SIDE PIPING HOLE 3-3/8 T-STAT WIRING 7/8 CONDENSATEDRAIN OPENING 1-3/4 28-1/2T-STAT WIRING 7/8 CONDENSATEDRAIN OPENING 1-3/4 HORIZONTALCONDENSATEDRAIN OPENING 1-3/4 JUNCTION BOXHOLE 7/8 GAS PIPEENTRY 1-1/2 CONDENSATE DRAINHOLE 7/8 40 AFRONTCABINET AND DUCT DIMENSIONSM odelsCFMC abinetSizeCabinet DimensionA (in.)B (in.)C (in.)D (in.)GY9F064C16DH111600C2119-3/418-1/22- 1/8GY9F080C16DH111600C2119-3/418-1/22-1/ 8 ELECTRICAL AND PERFORMANCE DATAM odelsInput/CabinetOutputNominal AirflowCabinet WidthTotal Unit AFUEAir Temp.
5 FGY9F064C16DH1164/C61160021129525 - 55GY9F080C16DH1180/C76160021129525 - 55 ModelsInput/CabinetMax. Outlet Air SizeMax. Over-current ProtectMin. Wire Size(awg) @ 75 ft. One WayOperation WeightMBH x 102014155GY9F080C16DH1180/C1653 x 102014170 Unitary Products Group3339033-YTG-A-0607 NOTES:1. Airflow expressed in standard cubic feet per minute (CFM).2. Motor voltage at 115 NR = Operation at this static pressure is not PERFORMANCEThe airflow capacity data published in the Blower Perfor-mance table listed above represents blower performanceWITHOUT filters. To determine the approximate blower per-formance of the system, apply the filter drop value for the fil-ter being used or select an appropriate value from the FilterPerformance table : The filter pressure drop values in the Filter Perfor-mance table shown are typical values for the type of filterlisted and should only be used as a guideline.
6 Actual pres-sure drop ratings for each filter type vary between filter : 1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity PERFORMANCE CFMAIRFLOW WITH TOP RETURN - WITHOUT FILTERS (CFM)ModelsSpeedTapExternal Static Pressure, Inches High158315901569155415321502145714091327 1221 Medium Low1256127512751288127512651232118711261 023 Low937939936945942936912874810726GY9F080 C16DH11 High199619611938189618361779170716251531 1399 Medium High144914801495148814881449141713681299 1208 Medium Low1167119211921187120211921182114010971 018 Low932900871840805761710663641623 RECOMMENDED FILTER SIZESCFM Cabinet SizeTop Return Filter in1600C(2) 14 x 20 FILTER PERFORMANCE - PRESSURE DROP INCHES AND (KPA)
7 Airflow RangeMinimum Opening SizeFilter TypeDisposableWashable FiberPleatedCFM in2 In - - - - - - & CLEARANCES TO COMBUSTIBLESA pplicationTopFrontRearLeftSideRightSideF lueFloor/BottomClosetAlcoveAtticLine ContactDownflow1300001"*Ye sYe sYe sN oHorizontal030110 CombustibleNoYesYesYe s *Special floor base or air conditioning coil required for use on combustible floor. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or Products Group339033-YTG-A-0607 For additional connection diagrams for all UPG equipment refer to Low Voltage System Wiring document available online in the Product Catalogue ChartAC1 Single Stage A/C w/Single Stage Furnace, 1 Stage Cooling Ready - (G,L)*8/9S, G(Y,M)
8 9 FHM1 HumidistatThermostat Installer Setup Number 1 - System Type - must be set to 0 Selection of GAS/ELEC switch on thermostat not necessaryThermostat Installer Setup Number 15 - Compressor Protection - must be set to 524V HUMIDIFIERGFanGFanGFanGFanWFirst Stage HeatWFirst Stage HeatWFirst Stage HeatWSingle Stage HeatRC24-Volt Hot (Cool XFMR)RC24-Volt Hot (Cool XFMR)RC24-Volt Hot (Cool XFMR)R24-Volt Hot (Heat XFMR)RH24-Volt Hot (Heat XFMR)RH24-Volt Hot (Heat XFMR)R24-Volt HotC24-Volt CommonC24-Volt CommonYFirst Stage CoolYFirst Stage CoolYFirst Stage CoolY/Y2 Single/Second Stage CoolYSingle Stage Cool*DN11C00124C24-Volt CommonC24-Volt CommonOptional w/Batteries*BN11C01124*DP11C40124 PSCFURNACE CONTROLSINGLE STAGEAIR CONDITIONING*BN11C00124*BP11C50124*PP11C 70224 THERMOSTATTHERMOSTATTHERMOSTATHP1W/031-0 1975- Series Demand ControlSingle Stage H/P - E*RD, E*BD, ERHS, HPX13 - w/Single Stage Furnace, 1 Stage Cooling Ready - (G,L)*8/9S, G(Y,M)
9 9 FSINGLE STAGEHEAT PUMP*DN22U00124* bp21h50124 *PP32H70124 THERMOSTATTHERMOSTATTHERMOSTATPSCFURNACE CONTROL*BN21H00124*DP21H40124*DN21H00124 N/AN/AC24-Volt CommonR24-Volt HotEEmergency HeatOReversing Valve Energized in CoolC24-Volt CommonC24-Volt CommonYFirst Stage Heat/CoolY/Y2 Single/Second Stage CoolYSingle Stage Heat/CoolR24-Volt HotR24-Volt HotW1 Second Stage HeatWSingle Stage HeatW1/66 First Stage Heat OutGFanGFanWFirst Stage HeatStep 1 of Thermostat User Configuration Menu must be set to Heat Pump 1 Step 9 of Thermostat User Configuration Menu must be set to Pump OFFOR eversing Valve Energized in CoolLMalfunction LightX/LMalfunction LightUnitary Products Group5339033-YTG-A-0607 APPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOWTo determine the approximate airflow of the unit with a filter inplace, follow the steps the filter the External System Static Pressure (ESP) without the a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system total system static matches a ESP value in the airflow table ( , , etc,) the system airflow corre-sponds to the intersection of the ESP column and Model/Blower Speed the total system static falls between ESP values in the table ( , , etc.)
10 , the static pressure may be rounded to the nearest value in the table determining the airflow using Step 5 or calculate the airflow by using the following : For a 120,000 Btuh furnace operating on highspeed blower, it is found that total system static is " determine the system airflow, complete the the airflow values at " & " @ ": 2152 CFMA irflow @ ": 2042 the airflow @ " from the airflow @ " to obtain airflow - 2152 = -110 the total system static from " and divide this difference by the difference in ESP values in the table, " - ", to obtain a percentage.( - ) / ( - ) = percentage by airflow difference to obtain airflow reduction.( ) x (-110) = airflow reduction value to airflow @ " to obtain actual airflow @ " - 88 = 2064 ACCESSORIESPROPANE (LP) CONVERSION KIT - 1NP0357 - All ModelsThis accessory conversion kit may be used to convert naturalgas (N) units for propane (LP) operation.