Example: bankruptcy

DRYWALL GRID SYSTEMS

DRYWALL grid SYSTEMSHANGING & FRAMING FLAT CEILINGSP erformanceWORK SMARTERE liminate the labor-intensive cutting, tying, and spacing of track and channel framing. Our SYSTEMS are engineered with rout locations and cross tees to maintain precise module spacing. Main beams have 51 rout locations and cross tee lengths of 50", 26", and 14" to accommodate type F fixtures without field modifications or accessories. Pre-notched main beams simplify curved DRYWALL installations. Our DRYWALL SYSTEMS are manufactured to meet or exceed ASTM standards and code requirements, and are engineered to provide economical alternatives to stud and track vertical load carrying capacity for main beam and cross tee members is determined in accordance with ASTM test method E3090.

Flat Drywall Grid Installation TABLE OF CONTENTS 2 Code Compliance 2-3 Performance 4 Components 5 Moldings 6 Corrosion Prevention ®7-8 Axiom Trim 9-10 AxiomBuilding Perimeter System 11-12 Rout Locations 12-13 Accessories 14 System Framing 15 Type F Fixtures 16-19 Suspended Drywall Grid System 20 Hanging and Framing 21 Yoke Wire Hung Ceilings

Tags:

  Grid

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of DRYWALL GRID SYSTEMS

1 DRYWALL grid SYSTEMSHANGING & FRAMING FLAT CEILINGSP erformanceWORK SMARTERE liminate the labor-intensive cutting, tying, and spacing of track and channel framing. Our SYSTEMS are engineered with rout locations and cross tees to maintain precise module spacing. Main beams have 51 rout locations and cross tee lengths of 50", 26", and 14" to accommodate type F fixtures without field modifications or accessories. Pre-notched main beams simplify curved DRYWALL installations. Our DRYWALL SYSTEMS are manufactured to meet or exceed ASTM standards and code requirements, and are engineered to provide economical alternatives to stud and track vertical load carrying capacity for main beam and cross tee members is determined in accordance with ASTM test method E3090.

2 Suspended ceiling SYSTEMS constructed of screw-attached gypsum board panels may be installed in accordance with ASTM C1858 and are exempt from code prescribed requirements of acoustical or lay-in panel ceilings. This standard practice is limited to framing that supports a single level ceiling and is surrounded by and attached to laterally braced walls or grid SystemsCode Compliance You Can Trust Meets: ASTM C1858 ASTM C635 ASTM C645 ASTM C754 ASTM C840 ASTM E3090 ICC Evaluation Service Report ESR-1289 City of LA RR 25348 IBC categories D, E, and F single layer DRYWALL ceilings are exempt from lateral force bracing requirements, regardless of room size Miami-Dade County, Florida wind uplift NOA No.

3 03/17/2021 Miami-Dade County, Florida impact testing NOA No. 10/07/2020 Consult local codes for specific requirements Locking Angle Mechanism creates repeatable accurate spacing for corrections to molding PeakForm patented profile increases strength and stability for improved performance during installation SuperLock main beam clip is engineered for a strong secure connection and fast accurate alignment confirmed with an audible click; easy to remove and relocate ScrewStop reverse hem prevents screw spinoff on 1-1/2" wide face2 For more information, call 877 276-78763 For more information.

4 Call 877 276-7876 Flat DRYWALL grid Installation TABLE OF CONTENTS 2 Code Compliance 2-3 Performance 4 Components 5 Moldings 6 Corrosion Prevention 7-8 Axiom Trim 9-10 Axiom Building Perimeter System 11-12 Rout Locations 12-13 Accessories 14 System Framing 15 Type F Fixtures 16-19 Suspended DRYWALL grid System 20 Hanging and Framing 21 Yoke Wire Hung Ceilings 22 Trapeze Supported Loads 23 Double Hung Ceilings 24 Triple Hung Ceilings 25 Exterior Wind Load Data 26-27 UL Fire Resistive 28 Seismic Installation Instructions 29 Load Data 30 Basic Products 31 Sound Control 32 Estimating Rotary-stitched Greater torsional strength and stability 1-1/2" wide face main beams and cross tees Easy installation of screw-applied gypsum wallboard G40, G90 hot dipped galvanized coating Corrosion resistance G90 hot dipped galvanized coating Superior corrosion resistance for exterior applications Heavy-duty load rating Minimum 16 Lbs/LF on main beams Fire rated Applicable to 25 UL Fire Resistant designs (D501, D502, G523, G524, G527, G528, G529, G553, J502, L502, L508, L513, L515, L525, L526, L529, L564, P501, P506.)

5 P507, P508, P509, P510, P513, P514, P516). Item XL7936G90 and XL8965 are not fire rated. Wind uplift and impact testing construction available, including Miami Dade/Broward County, Florida Cross tee spacing: 24" for 5/8" DRYWALL 16" for 1/2" drywallDRYWALL grid SYSTEMS4 For more information, call 877 276-7876 MAIN BEAMSCOMPONENTSLoad Test Data (Lbs/LF)Item NumberLengthFace DimensionProfileHeightFireRatedRoutsL/24 0 Simple SpanL/360 Simple SpanPerspective72"72"XL8965XL8965 HRC72"1-1/2" 1-1/2" Yes6 routs starting 24" from each end "50"XL8947P XL8947PG9050"1-1/2" 1-1/2" Yes8 routs starting 10" from each end '3'4'2'3'4'XL8945P XL8945PG90 XL8945 HRC48"1-1/2" 1-1/2" Yes9 routs center rout and starting 10" from each end "1-1/2"1-1/2"No XL8926 XL8926G9024"1-1/2" 1-1/2" Yes3 routs center rout and 10" from each end Load Test Data (Lbs/LF)

6 Item NumberLengthFace DimensionProfileHeightDutyLoadFireRatedR outsL/240 Simple Span L/360 Simple SpanPerspective2'3'4'2'3'4'HD8906HD8906G 90HD8906 HRC144"1-1/2" 1-11/16" Heavy DutyYes51 routs starting 2-1/4" from each end "1-1/2" 1-11/16" Heavy DutyYes51 routs starting 2-1/4" from each end "1-1/2" 1-11/16" Heavy DutyYes51 routs starting 2-1/4" from each end Spacing (KG/LM)Item NumberLengthFace DimensionProfileHeightDutyLoadFireRatedR outs600mm 900mm 1200mm 600mm 900mm 1200mmHD79403600mm30mm38mmYes200mm starting 75mm from each end Type F fixture compatible1/4"9/16"1-11/16"1-1/2"1/4"9/1 6"1-11/16"1-1/2"CROSS TEES1/4"3/8"1-1/2"1-1/2"MetricLoad Total Data (KG/LM)Item NumberLengthFace DimensionProfileHeightFireRatedRoutsL/24 0L/360L/240L/360 XL79611600mm 30mm38mmYes800mm center of @ 6' @ 6' @ @ 1600mmXL793038mm30mm38mmYes450mm, 600mm, 750mm @ 4' @ 4' @ @ @ 3' @ 3' @ @ 900mmNOTE.

7 All items available in High Recycled Content (HRC) as special order. Type F fixture compatibleMOLDINGS5 For more information, call 877 276-7876 MOLDINGSItem NumberLengthDescriptionProfilePerspectiv e7858144"Reverse Angle Molding nominal1-9/16" x 15/16"KAM10120"Knurled Angle Molding nominal1-1/4" x 1-1/4"KAM12 KAM12G90 KAM12 HRC144"Knurled Angle Molding nominal1-1/4" x 1-1/4"KAM1510 KAM1512 KAM151020 KAM151020EQ120" 144" Knurled Angle Molding nominal 1-1/2" x 1-1/2" (KAM1510 & KAM1512 - 25 ga.; KAM151020 - 20 ga.; KAM151020EQ - 22 ga.)KAM21020 KAM21025 KAM21020EQ120" 144"Knurled Angle Molding nominal 2" x 2" (20 ga.)

8 (KAM21020 - 20 ga.; KAM21025 - 25 ga.; KAM21020EQ 22 ga.) LAM12 LAM12G90 LAM12 HRCLAM151220E144"Locking Angle Molding nominal 1-1/4" x 1-1/4"1-1/2" x 1-1/2"SC151220EQ SC151225 SC21220EQ SC21225148"148"148"148"SimpleCurve Knurled Angle Molding(SC151220EQ 12' x " & SC21220EQ 12' x 2" 20 ga.; SC151225 12' x " & SC21225 12' x 2" 25 ga.)NOTE: All items available in High Recycled Content (HRC) as special 12/14/981/28/9915/16"1-9/16"1-1/4"1-1/4" 1-1/4"1-1/2"or 2"1-1/4"1-1/2"or 2"1-1/2"1-1/2"2"2"SimpleCurve Knurled Angle Molding5/8" Gypsum Board6 For more information, call 877 276-7876 CORROSION PREVENTIONC orrosion prevention is an essential factor in the economical utilization of galvanized sheet metal for ceiling suspension SYSTEMS .

9 Armstrong Ceilings provides G40 for standard construction per ASTM C645. When conditions include exposure to extreme moisture and salt water, G90 is available per ASTM : Commercial-quality cold rolled hot dipped galvanized steelItem NumberLength/Item DescriptionFace DimensionFlangeProfile Height7901120" Shadow Reveal Molding3/8" shadow reveal9/16"1-1/4"7902120" Shadow Reveal Molding3/8" shadow reveal15/16"1-1/4"7903120" Inverted T Molding1" inverted T 1-1/2"7904 7904PF*120" Flush Transition Molding15/16" horizontal15/16"1-1/4" 7905 7905PF*120" Flush Transition Molding9/16" horizontal9/16"1-1/4" 7906120" F Molding120" vertical transition1/2"1-7/16" 7907120" Tegular Transition Molding9/16" horizontal9/16"1-1/4"7908120" Tegular Transition

10 Molding15/16" horizontal15/16"1-1/4"790915/16" 1" Step Transition Molding15/16" horizontal15/16"1-7/8"79109/16" 1" Step Transition Molding9/16" horizontal9/16"1-7/8"79119/16" Shadow Reveal Transition Molding3/8" x 1/4" shadow reveal9/16"1-1/8"791215/16" Shadow Reveal Transition Molding3/8" x 1/4" shadow reveal15/16"1-1/4"* 7904PF and 7905PF feature protective film on the acoustical wall angle flange for faster, easier TRANSITION MOLDING7 For more information, call 877 276-7876 AXIOM TRIMAXIOM DRYWALL TRANSITIONSM aterial: Extruded aluminum, alloy 6063 Item NumberLength/Item Description DimensionsAXTRVESTRS traight Transition for Vector Ceiling120 x 2-9/16 x 1-11/16"AXTRTECURC urved Transition for Tegular120 x 2-9/16 x 1-11/16"AXTR2 STR2" Straight Transition120 x 2 x 1-1/2"AXTR2 CUR2" Curved Transition120 x 2 x 1-1/2"AXTR4 STR4" Straight Transition120 x 4 x 1-1/2"AXTR4 CUR4" Curved Transition120 x 4 x 1-1/2"AXTR6 STR6" Straight Transition120 x 6 x 1-1/2"AXTR6 CUR6" Curved Transition120 x 6 x 1-1/2"AXTR8 STR8" Straight Transition120 x 8 x 1-1/2"AXBTSTRD rywall Bottom Trim120 x 1-1/8 x 27/32"ACCESSORIESAX4 SPLICEBS