Transcription of EST Fire Alarm Control Panel Operating Instructions
1 Frame these Instructions and mount on the wall next to the Control Panel . EST Fire Alarm Control Panel Operating Instructions For models: iO64G, iO64GD, iO64R, iO64RD, iO64G-2, iO64R-2, iO64GL, iO64GL-F. iO500G, iO500GD, iO500R, iO500RD, iO500G-2, iO500R-2, iO500GL-F. For additional information, refer to the EST io64 and iO500 TO SILENCE THE Panel BUZZER. Technical Reference Manual (P/N 3101112-EN). 1. Press Panel Silence. RESPONDING TO Alarm SIGNALS The buzzer turns off. Any new events turn the buzzer back on. 1. Evacuate the area. Trouble conditions not cleared resound the buzzer after a predetermined time. 2. Notify the proper authorities immediately and state the nature and location of the emergency. WARNING! Trouble conditions may affect the Panel 's ability to 3. Be prepared to provide directions to firefighters when they provide early detection and indication of a fire. Clear trouble arrive. conditions immediately.
2 TO SILENCE Alarm NOTIFICATION SIGNALS RESPONDING TO SUPERVISORY SIGNALS. 1. Silence the Panel buzzer. WARNING! Alarm notification signals should not be silenced until after all occupants have been evacuated. 2. Investigate the cause of the supervisory signal and notify the authorized service personnel immediately. 1. Press Signal Silence. The Signal Silenced LED turns on and all audible notification RESPONDING TO MONITOR SIGNALS. circuits turn off. New Alarm events turn the notification circuits 1. Silence the Panel buzzer. back on. 2. Investigate the cause of the monitor signal and notify the Note: Panel programming may delay Alarm silence for up to one authorized service personnel immediately. minute, may prevent Alarm silencing when water flows through the sprinkler system, and may not turn off visible notification PERIODIC TEST RECOMMENDATIONS. circuits. See Maintenance and Testing, in the EST io64 and iO500. TO RETURN THE SYSTEM TO NORMAL AFTER AN Alarm Technical Reference Manual for test Instructions and OR SUPERVISORY EVENT references.
3 1. Make sure all smoke detectors are free from smoke and all Installed by manual pull stations are reset. Name: 2. Press Reset. Company: Note: Panel programming may delay Panel reset for up to one minute after Alarm notification circuits turn on. Address: TO INITIATE A FIRE DRILL Phone: 1. Press Drill. Per NFPA 72. All audible notification circuits turn on. This function does not automatically notify the fire department. Protected Premises Fire Alarm System, Local TO PERFORM A LAMP TEST ( Panel and remote annunciators) Auxiliary Fire Alarm System 1. Press the Menu button. Remote Supervising Station Fire Alarm System 2. Choose Test. Central Station 3. Choose Lamp Test. Releasing per NFPA 11, 12, 12A, 13, 15, 16, 17, 70, 72, and 4. Press Enter. 2001. TO PERFORM A REMOTE ANNUNCIATOR LAMP TEST Per NFPA 720. 1. Press and hold the Silence button on the LCRA for five Carbon monoxide signaling seconds. Date: 2. LEDs on remote annunciators will remain on until silence button is released.
4 For service contact RESPONDING TO TROUBLE SIGNALS Company: 1. Silence the Panel buzzer. Address: 2. Investigate the cause of the trouble and notify the Phone: authorized service personnel immediately. Acceptance Inspection by Date: 2013 UTC Fire & Security Americas Corporation, Inc. 1/1 P/N 3101105-EN REV 04 ISS 02 MAY13.