DN-6724:B3 2/17/2011 Page 1 of 2 FCM-1(A) & FRM-1(A) SeriesControl and Relay ModulesIntelligent / addressable DevicesDN-6724:B3 GeneralFCM-1(A) Control Module: The FCM-1(A) addressable Con-trol Module provides Notifier intelligent fire alarm Control pan-els a circuit for Notification Appliances (horns, strobes,speakers, etc.). Addressability allows the FCM-1(A) to be acti-vated, either manually or through panel programming, on aselect (zone or area of coverage) (A) Relay Module: The FRM-1(A) addressable RelayModule provides the system with a dry-contact output for acti-vating a variety of auxiliary devices, such as fans, dampers, Control equipment, etc. Addressability allows the dry contact tobe activated, either manually or through panel programming,on a select ( Patent 5,539,389) is a communication pro-tocol developed by NOTIFIER Engineering that greatlyenhances the speed of communication between analog intelli-gent devices.

Intelligent / Addressable Devices DN-6724:B3 General FCM-1(A) Control Module: The FCM-1(A) Addressable Con-trol Module provides Notifier intelligent fire alarm control pan-els a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be acti-vated, either manually or through panel programming ...

Tags:

  Fire, Addressable

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FCM-1(A) & FRM-1(A) Series - Control Fire Systems

1 DN-6724:B3 2/17/2011 Page 1 of 2 FCM-1(A) & FRM-1(A) SeriesControl and Relay ModulesIntelligent / addressable DevicesDN-6724:B3 GeneralFCM-1(A) Control Module: The FCM-1(A) addressable Con-trol Module provides Notifier intelligent fire alarm Control pan-els a circuit for Notification Appliances (horns, strobes,speakers, etc.). Addressability allows the FCM-1(A) to be acti-vated, either manually or through panel programming, on aselect (zone or area of coverage) (A) Relay Module: The FRM-1(A) addressable RelayModule provides the system with a dry-contact output for acti-vating a variety of auxiliary devices, such as fans, dampers, Control equipment, etc. Addressability allows the dry contact tobe activated, either manually or through panel programming,on a select ( Patent 5,539,389) is a communication pro-tocol developed by NOTIFIER Engineering that greatlyenhances the speed of communication between analog intelli-gent devices.

2 Intelligent devices communicate in a groupedfashion. If one of the devices within the group has new infor-mation, the panel CPU stops the group poll and concentrateson single points. The net effect is response speed greater thanfive times that of other Built-in type identification automatically identifies thesedevices to the Control panel. Internal circuitry and relay powered directly by two-wireSLC loop. The FCM-1(A) module requires power (for horns,strobes, etc.), or audio (for speakers). Integral LED blinks green each time a communication isreceived from the Control panel and turns on in steady redwhen activated. LED blink may be deselected globally (affects all devices). High noise immunity (EMF/RFI). The FCM-1(A) may be used to switch 24-volt NAC power,audio (up to Vrms). Wide viewing angle of LED. SEMS screws with clamping plates for wiring ease.

3 Direct-dial entry of address 01 159 for FlashScan loops,01 99 for CLIP mode loops. Speaker, and audible/visual applications may be wired forClass B or A (Style Y or Z).ApplicationsThe FCM-1(A) is used to switch 24 VDC audible/visual power,high-level audio (speakers). The FRM-1(A) may be pro-grammed to operate dry contacts for applications such as doorholders or Air Handling Unit shutdown, and to reset four-wiresmoke detector : Refer to the SLC Manual (PN 51253) for details regardingreleasing applications with the FCM-1(A). Refer to the FCM-1-RELdatasheet (DN-60390) for new FlashScan releasing applications. Construction The face plate is made of off-white heat-resistant plastic. Controls include two rotary switches for direct-dial entry ofaddress (01-159). The FCM-1(A) is configured for a single Class B (Style Y) orClass A (Style Z) Notification Appliance Circuit.

4 The FRM-1(A) provides two Form-C dry contacts thatswitch FCM-1(A) or FRM-1(A) uses one of 159 possible moduleaddresses on a SLC loop (99 on CLIP loops). It responds toregular polls from the Control panel and reports its type andstatus, including the open/normal/short status of its Notifica-tion Appliance Circuit (NAC). The LED blinks with each pollreceived. On command, it activates its internal relay. TheFCM-1(A) supervises Class B (Style Y) or Class A (Style Z)notification or Control code command from the panel, the FCM-1(A) will dis-connect the supervision and connect the external power sup-ply in the proper polarity across the load device. Thedisconnection of the supervision provides a positive indicationto the panel that the Control relay actually turned ON. Theexternal power supply is always relay isolated from the com-munication loop so that a trouble condition on the externalpower supply will never interfere with the rest of the switches set a unique address for each module.

5 Theaddress may be set before or after mounting. The built-inTYPE CODE (not settable) will identify the module to the con-trol panel, so as to differentiate between a module and a sen-sor for FCM-1(A) Normal operating voltage: 15 to 32 current draw: mA (LED on).Average operating current: 350 A direct poll, 375 A grouppoll with LED flashing, 485 A Max. (LED flashing, NACshorted.)FCM-1(A) 2 of 2 DN-6724:B3 2/17/2011 Notifier and FlashScan are registered trademarks of HoneywellInternational Inc. 2011 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without more information, contact Notifier.

6 Phone: (203) 484-7161, FAX: (203) in the NAC Line Loss: 4 supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum(Speakers): V RMS, on external supply: mA maximum using 24 VDCsupply; mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, thecurrent rating is 3A; For class A wiring system, the current rat-ing is range: 32 F to 120 F (0 C to 49 C).Humidity range: 10% to 93% : " ( mm) high x 4" ( mm) wide " ( mm) deep. Mounts to a 4" ( mm) square " ( mm) deep : SMB500 Electrical Box; CB500 BarrierSpecifications for FRM-1(A) Normal operating voltage: 15 to 32 current draw: mA (LED on).Average operating current: 230 A direct poll; 255 A resistance: not range: 32 F to 120 F (0 C to 49 C).Humidity range: 10% to 93% : " ( mm) high x 4" ( mm) wide " ( mm) deep.

7 Mounts to a 4" ( mm) square " ( mm) deep : SMB500 Electrical Box; CB500 BarrierAgency Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac-tory for latest listing status. UL: S635 ULC: S3705 (A version only) FM Approved CSFM: 7300-0028:0219 MEA: 14-00-E FDNY: COA #6067, #6065 Contact Ratings for FRM-1(A) NOTE: Maximum (Speakers): V RMS, 50 WProduct Line InformationNOTE: A suffix indicates ULC Listed (A): Intelligent addressable Control (A): Intelligent addressable Relay : Capacitor, required for Class A (Style Z) operationof : Optional Surface-Mount : Control Module Barrier required by UL for separat-ing power-limited and non-power limited wiring in the samejunction box as FCM-1(A). NOTE: For installation instructions, see the following documents: FCM-1(A) Installation document I56-1169.

8 FRM-1(A) Installation document I56-3502. Notifier SLC Wiring Manual, document RatingMaximum VoltageLoad DescriptionApplication3 A30 VDCR esistiveNon-Coded2 A30 A110 A125 A30 VDCI nductive(L/R=5ms)Coded1 A30 VDCI nductive(L/R=2ms) A125 VACI nductive(PF= ) A25 VACI nductive(PF= ) VACI nductive(PF= )Non-Coded2 A25 VACI nductive(PF= )Non-CodedDN-60390:B 05/20/2009 Page 1 of 2 FCM-1-REL(A)Releasing Control ModuleIntelligent/ addressable DevicesDN-60390:B H-235 GeneralThe FCM-1-REL Releasing Control Module is specificallydesigned for fire suppression releasing applications in Flash-Scan Systems . Power to the release agent solenoid(s) runsthrough the module for full-time monitoring and FCM-1-REL Releasing Control Module uses a redun-dant protocol; the module must be armed with a pair of sig-nals in order to activate. It will then enter a 3-second windowawaiting a pair of confirmation signals.

9 If no confirmation isreceived, the module will automatically reset. It also super-vises the wiring to the connected load and reports the statusto the panel as NORMAL, OPEN, or SHORT CIRCUIT. Themodule has two pairs of output termination points availablefor fault-tolerant wiring and a panel-controlled LED module may be connected to either one 24 VDC solenoidor up to two 12 VDC solenoids (in Series ). To ensure properoperation, this module shall be connected to a compatibleNotifier system Control panel only (list available from Notifier).In addition, please refer to Notifier Device Compatibility Doc-ument PN 15378 for the list of compatible solenoids. NOTE: FCM-1-REL is required for all new FlashScan-modereleasing applications with NFS2-3030 (version or higher),NFS2-640 (version or higher) and NFS-320(E)(C) ( or higher) panels. Use FCM-1 for releasing applications onNFS-640, NFS-3030, and all CLIP mode panels.

10 Features Redundant protocol for added protection Configurable for Class A or Class B operation External supply voltage monitoring Can power one 24V or two 12V solenoids SEMS screws for easing wiring Panel controlled status LED Analog communications Rotary address switches Low standby current Mounts in standard 4" ( cm) junction box FlashScan operationSpecificationsGENERAL SPECIFICATIONS Operating Voltage: 15 to 32 VDC Communication Line Loop Impedance: 40 Ohm max. Temperature Range: 14 F to 140 F (-10 to 60 C) Relative Humidity: 10% to 95% noncondensing Shipping Weight: oz (156 g) Dimensions: " W " H " D( cm W cm H cm D)SLC Average Operating Current: 700 A max @ 24 VDC(one communication every 5 sec. with LED enabled) Maximum Activation Current: mA (LED on)EXTERNAL SUPPLY Normal Operating Voltage: 24 VDC Nominal Maximum Line Loss: VDC (total allowable loss frompower supply to module and from module to solenoid) Minimum Operating Voltage to Activate Solenoid:18 VDC (at solenoid) Standby Current: mA Activation Current: 10 mASOLENOID Supervisory Loop Voltage: V Supervisory Loop Current (Normal): 30 mA Maximum Activation Current: 2 AProduct Line Information NOTE: A suffix indicates ULC Listed (A): Releasing Control : Optional Surface-Mount : Control Module Barrier required by UL for sepa-rating power-limited and non-power limited wiring in thesame junction box as 2 of 2 DN-60390:B 05/20/2009 Notifier and FlashScan are registered trademarks of HoneywellInternational Inc.