NBG-12LR and NBG-12LRA

DN-6840:B 3/5/2014 Page 1 of 2 NBG-12LR and NBG-12 LRADual-Action Agent Release StationsReleasing PanelsDN-6840:B F-710 Dual Action NBG-12 LRDual Action NBG-12 LRAG eneralThe NBG-12LR and NBG-12 LRA are Agent Release Stationsdesigned for use with NOTIFIER Fire Alarm Control Panelswith releasing Non-coded, dual-action operation. Made with durable polycarbonate. Optional surface Abort switch. Power-on indication. Released indication. Manual release (dual-action). NBG-12LR Dual-action release NBG-12 LRA and NBG-12LR are ideal for areas such asclean rooms and computer rooms where a chemical agent isused to extinguish a Temperature Range: 32 F to 120 F (0 C to 49 C). Relative Humidity: 10% to 93% (noncondensing). For use indoors in a dry Line InformationNBG-12 LRA: Agent release station with abort switch, ReleaseLED, and Normal : Dual-action agent release : Surface backbox for NBG-12 LRA, metal.

DN-6840:B • 3/5/2014 — Page 1 of 2 NBG-12LR and NBG-12LRA Dual-Action Agent Release Stations Releasing Panels DN-6840:B † F-710 Dual Action NBG-12LR

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of NBG-12LR and NBG-12LRA

1 DN-6840:B 3/5/2014 Page 1 of 2 NBG-12LR and NBG-12 LRADual-Action Agent Release StationsReleasing PanelsDN-6840:B F-710 Dual Action NBG-12 LRDual Action NBG-12 LRAG eneralThe NBG-12LR and NBG-12 LRA are Agent Release Stationsdesigned for use with NOTIFIER Fire Alarm Control Panelswith releasing Non-coded, dual-action operation. Made with durable polycarbonate. Optional surface Abort switch. Power-on indication. Released indication. Manual release (dual-action). NBG-12LR Dual-action release NBG-12 LRA and NBG-12LR are ideal for areas such asclean rooms and computer rooms where a chemical agent isused to extinguish a Temperature Range: 32 F to 120 F (0 C to 49 C). Relative Humidity: 10% to 93% (noncondensing). For use indoors in a dry Line InformationNBG-12 LRA: Agent release station with abort switch, ReleaseLED, and Normal : Dual-action agent release : Surface backbox for NBG-12 LRA, metal.

2 ( cm) W x ( cm) L x ( cm) : Surface backbox for NBG-12LR , metal. ( cm) W x ( cm) L x ( cm) : Surface backbox for NBG-12LR , : Optional trim ring for semi-flush Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in progress. Consult fac-tory for latest listing status. UL/ULC Listed: S692. MEA Listed: 67-20-E. FM Approved. CSFM: 7150-0028:0199. FDNY: COA#6114 (NFS2-3030), COA#6121 (NFS2-640,NFS-320). Coast Guard, Lloyd s Register, American Bureau ofShipping (ABS): For information on marine applications,see 2 of 2 DN-6840:B 3/5/2014 NOTIFIER and FlashScan are registered trademarks of HoneywellInternational Inc. 2014 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes.

3 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) :D 4/13/2012 Page 1 of 2 NBG-12 LXAddressable Manual Pull StationIntelligent/Addressable DevicesDN-6726:D H-240 The NBG-12 LXAddressable Manual Pull GeneralThe Notifier NBG-12LX is a state-of-the-art, dual-action ( ,requires two motions to activate the station) pull station thatincludes an addressable interface for any Notifier intelligentcontrol panel except FireWarden series panels, and the NSP-25 panel. Because the NBG-12LX is addressable, the controlpanel can display the exact location of the activated manualstation. This leads fire personnel quickly to the location of Maintenance personnel can open station for inspection andaddress setting without causing an alarm condition.

4 Built-in bicolor LED, which is visible through the handle ofthe station, flashes in normal operation and latches steadyred when in alarm. Handle latches in down position and the word ACTIVATED appears to clearly indicate the station has been operated. Captive screw terminals wire-ready for easy connection toSLC loop (accepts up to 12 mm wire). Can be surface mounted (with SB-10 or SB-I/O) or semi-flush mounted. Semi-flush mount to a standard single-gang, double-gang, or 4" ( cm) square electrical box. Smooth dual-action design. Meets ADAAG controls and operating mechanisms guide-lines (Section [13]); meets ADA requirement for 5 activation force. Highly visible. Attractive shape and textured finish. Key reset. Includes Braille text on station handle. Optional trim ring (BG12TR). Meets UL 38, Standard for Manually Actuated SignalingBoxes.

5 Up to 99 NBG-12LX stations per loop on CLIP protocolloops. Up to 159 NBG-12LX stations per loop on FlashScan pro-tocol loops. Dual-color LED blinks green to indicate normal onFlashScan , door, and handle are molded of durable polycarbonatematerial with a textured Shipping Weight: oz. ( g) Normal operating voltage: 24 VDC. Maximum SLC loop voltage: VDC. Maximum SLC standby current: 375 A. Maximum SLC alarm current: 5 mA. Temperature Range: 32 F to 120 F (0 C to 49 C) Relative Humidity: 10% to 93% (noncondensing) For use indoors in a dry locationInstallationThe NBG-12LX will mount semi-flush into a single-gang, dou-ble-gang, or standard 4" ( cm) square electrical outletbox, or will surface mount to the model SB-10 or SB-I/O sur-face backbox. If the NBG-12LX is being semi-flush mounted,then the optional trim ring (BG12TR) may be used.

6 TheBG12TR is usually needed for semi-flush mounting with 4"( cm) or double-gang boxes (not with single-gang boxes).OperationPushing in, then pulling down on the handle causes it to latchin the down/activated position. Once latched, the word ACTI-VATED (in bright yellow) appears at the top of the handle,while a portion of the handle protrudes from the bottom of thestation. To reset the station, simply unlock the station with thekey and pull the door open. This action resets the handle; clos-ing the door automatically resets the manual station, on command from the control panel,sends data to the panel representing the state of the manualswitch. Two rotary decimal switches allow address settings (1 159 on FlashScan systems, 1 99 on CLIP systems).Architectural/Engineering SpecificationsManual Fire Alarm Stations shall be non-coded, with a key-operated reset lock in order that they may be tested, and sodesigned that after actual Emergency Operation, they cannotbe restored to normal except by use of a key.

7 An operated sta-tion shall automatically condition itself so as to be visuallydetected as activated. Manual stations shall be constructed ofred-colored polycarbonate material with clearly visible operat-ing instructions provided on the cover. The word FIRE shallappear on the front of the stations in white letters, inches( cm) or larger. Stations shall be suitable for surfacemounting on matching backbox SB-10 or SB-I/O; or semi-flushmounting on a standard single-gang, double-gang, orPage 2 of 2 DN-6726:D 4/13/2012 NOTIFIER and FlashScan are registered trademarks of HoneywellInternational Inc. 2012 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements.

8 All specifications are subject to change without more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) in the " ( cm) square electrical box, and shall be installedwithin the limits defined by the Americans with Disabilities Act(ADA) or per national/local requirements. Manual Stationsshall be Underwriters Laboratories stations shall connect with two wires to one of the con-trol panel SLC loops. The manual station shall, on commandfrom the control panel, send data to the panel representing thestate of the manual switch. Manual stations shall provideaddress setting by use of rotary decimal loop poll LED shall be clearly visible through the front ofthe station. The LED shall flash while in the normal condition,and stay steadily illuminated when in Line InformationNBG-12LX: Dual-action addressable pull station. Includes keylocking feature. (Listed for Canadian and non-Canadian appli-cations.)

9 NBG-12 LXSP: Spanish/English labelled version. NBG-12 LXP: Portuguese labelled : Surface backbox; : Surface backbox; : Optional trim : Keys, set of : New York City trim Listings and ApprovalsIn some cases, certain modules or applications may not belisted by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status. UL/ULC Listed: S692 (listed for Canadian and non-Cana-dian applications). MEA: 67-02-E. CSFM: 7150-0028:0199. FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030). BSMI: CI313066760047. Coast Guard. Lloyd s Register. FM : Patent No. D428,351; 6,380,846; 6,314,772;6,632,108. DN-6643:A1 04/22/08 Page 1 of 2 NBG-12 SeriesNon-Coded Conventional Manual Fire Alarm Pull StationsConventional Initiating DevicesDN-6643:A1 I-410 GeneralThe NOTIFIER NBG-12 Series is a cost-effective, feature-packed series of non-coded manual fire alarm pull stations.

10 Itwas designed to meet multiple applications with the installer andend-user in mind. The NBG-12 Series features a variety of mod-els including single- and dual-action NBG-12 Series provides an alarm initiating input signal toconventional fire alarm control panels (FACPs) such as theSFP Series, and to XP Transponders. Its innovative design,durable construction, and multiple mounting options make theNBG-12 Series simple to install, maintain, and Aesthetically pleasing, highly visible design and color. Attractive contoured shape and light textured finish. Meets ADA 5 lb. maximum pull-force. Meets UL 38, Standard for Manually Actuated Signaling Boxes. Easily operated (single- or dual-action, model dependent),yet designed to prevent false alarms when bumped, shaken,or jarred. PUSH IN/PULL DOWN handle latches in the down position toclearly indicate the station has been operated.