FP600S - FP cables

FP600S FIRE RESISTANT CABLESM echanical Impact Very GoodTemperature Range -25 to +90 CFire ResistanceBS 7846 120 minBS 8491 120 minLow Smoke EmissionsBS EN 61034-2 Halogen Free BS EN 50267-2-1 Flexibility RigidFire Performance BS EN 60332-1-2BS EN 50266-2-4 Bending Radius FixedCircular conductor r= 6 DShaped conductor r= 8 DFIRE RESISTANT CABLESC ertificate No 077nCertificate No 517c/01FP 600 SBS 7846-F120 CABLE CHARACTERISTICSP rysmian FP600S is our highest performance fire resistant power cable, designed for the onerous fire survival requirements in BS8519 and now requested by regulators and specifiers for the increasing number of fire fighting and life safety applications.>BS8519:2010 Selection and Installation of fire-resistant power and control cable systems for life safety and fire fighting applications which has replaced Components for smoke and heat control systems.

KEY APPLICATIONS Electrical supplies for fire fighting, life safety and property protection systems. Active fire safety systems which, as part of a Fire Safety

Tags:

  Safety, Life, Fp600s, Life safety

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FP600S - FP cables

1 FP600S FIRE RESISTANT CABLESM echanical Impact Very GoodTemperature Range -25 to +90 CFire ResistanceBS 7846 120 minBS 8491 120 minLow Smoke EmissionsBS EN 61034-2 Halogen Free BS EN 50267-2-1 Flexibility RigidFire Performance BS EN 60332-1-2BS EN 50266-2-4 Bending Radius FixedCircular conductor r= 6 DShaped conductor r= 8 DFIRE RESISTANT CABLESC ertificate No 077nCertificate No 517c/01FP 600 SBS 7846-F120 CABLE CHARACTERISTICSP rysmian FP600S is our highest performance fire resistant power cable, designed for the onerous fire survival requirements in BS8519 and now requested by regulators and specifiers for the increasing number of fire fighting and life safety applications.>BS8519:2010 Selection and Installation of fire-resistant power and control cable systems for life safety and fire fighting applications which has replaced Components for smoke and heat control systems.

2 Specifications for cable systems is tested to Method for assessment for the fire integrity of large diameter power involves direct mechanical impact and water jet application under fire conditions and Armoured fire resistant cables having thermosetting insulation and low emission of smoke and corrosive gas when affected by fire FP600S is approved by BASEC and LPCB to achieve the highest performance in the test standards BS8491 and BS7846 FP600S is easy to install and handles like a standard armoured cable. No special tools are needed so it can be terminated, glanded and cleated just as easily which ensures substantial installation savings compared with accordance with BS8519 cable should be supported by fixings that do not compromise its fire performance and withstand at least the same fire conditions so management systems, supports, joints and terminations should be selected is recommended that joints are avoided in order to maintain the highest integrity of the use of BICON cable glands and cleats is :2005 >BS8491:2008 >BS7846.

3 2000> cross sectional areamm2 Approximateoveralldiameter mmApproximatediameterunderarmourmm Nominaldiameterof armourwiresmmApproximatecable weightkg/kmMaximum conductor resistance at 20 C ohms/kmShort circuit rating (1sec) of conductorkACurrent rating Three phase AC clipped directAmpsClaw CleatRef accessoriesCurrent rating Three phase AC Free air AmpsVolt drop Three phase AC mV/A/mBrass GlandRef No. Three Core Four CoreCircular conductor conductor 50mm2 and aboveInstallation methods for current rating in accordance with BS7671/IEE Wiring tabulated ratings are based upon a 30 C ambient temperature and 90 C operating other ambient temperatures or where cables are grouped together.

4 The following rating factors should be RESISTANT CABLESFP600S cross sectional areamm2 Approximateoveralldiameter mmApproximatediameterunderarmourmm Nominaldiameterof armourwiresmmApproximatecable weightkg/kmMaximum conductor resistance at 20 C ohms/kmCurrent Rating DC or single phase AC Free Air AmpsCurrent rating DC or single phase AC clipped directAmpsClaw CleatRef accessoriesVoltage drop DC mV/A/mVolt drop single phase AC mV/A/mBrass GlandRef No. Two CoreFP600 SLOW VOLTAGE 600/1000V KEY APPLICATIONSE lectrical supplies for fire fighting, life safety and property protection systems. Active fire safety systems which, as part of a Fire safety Engineering solution, rely on an effective electrical supply remaining operational during a emphasis is now being given to the integrity of electrical circuits which maintain the functional safe working conditions of such equipment and systems.

5 FP600S is a new generation fire resistant cable designed to meet the much more onerous fire survival requirement now considered appropriate for such of circuits which are required to remain operational under such conditions include:The new requirements and test method for cables for use in such applications, which involves an integrated fire test with the application of radiation by flame, direct impact and water jet to a single sample of cable are given in BS7346-6 Components for smoke and heat control systems - Part 6 Specification for Cable has been extensively tested against these requirements and achieved the maximum 120 minute DESCRIPTIONCONDUCTORP lain annelaed copper stranded circular (4-35 mm ) or shaped (50-400 mm ) conductor complying with BS EN 60228 Class Insulation:Mineral ceramic (Mica/Glass) fire resistant tapeSecondary Insulation.

6 90 C cross - linked insulationAmbient Temperature C2530354045505560 Correction MethodNumber of circuits or multi-core cables23456789 Single layer clipped to a non-metallic * layer multicore on a perforated metal cable tray, vertical or * factors for Ambient temperaturesAtrium, basement, underground car park and shopping mall smoke venting systemsElectrically operated fire shutters and smoke curtains Fire fighting liftsPressurisation and depressurisation fansSmoke dampers motor drivenSmoke relief dampers motor driven openSprinkler and wet-riser pumps>>>>>>>Correction factors for grouping of cables *Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be applied.

7 Note: Standard conditions of grouping as stated in BS791 (IEE Wiring Regs) RESISTANT CABLESCORE IDENTIFICATIONoo brown-blueooo brown-black-greyoooo blue-brown-black-greyBEDDINGT hermoplastic LSOH bedding compoundARMOURS ingle layer of galvanised steel wiresSHEATHR obust thermoplastic LSOH sheath. Colour - colours to speical orderINSTALLATIONM inimum recommended installation temperature 0 for indoor and outdoor installations. For externalexposure the use of a Black sheath is be installed in accordance with BS7671/IEE WiringRegulations or any other appropriate national for direct burial, trough, tray, ladder orother installations requiring a robust armoured RADIUSA minimum internal radius of bend of 6 x cable diameteris recommended during installations for cables havingcircular conductors and 8 x cable diameter for cableshaving shaped special accessories are required for the installationof brass armoured cable glands and cast iron cleatsmay be the cable is required to maintain circuit integrityin a fire.

8 It is important that any accessory used tosupport the cable can also withstand that fire. The use ofthe appropriate BICON gland or cleat is recommended. Sales enquiriesTel: 0845 767 8345 Fax: 023 8029 5465UK Technical helplineTel: 0845 767 8345 Fax: 023 8029 5002 Prysmian cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6 YUUnited KingdomFor further information please see our dedicated FP Sales enquiresTel: +44 23 5029 5481 Fax: +44 23 8029 5465 Overseas Technical helplineTel: +44 23 8029 5481 Fax: +44 23 8029 5002 Information hotlineTel: +44 (0) 23 8029 5029 Fax: +44 (0) 23 8029