FTA1000 - Fire Sprinklers

E-Mail Print Close Product Description Full Voltage Starting Electric FTA1000 . Fire Pump Controllers Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED. PUMP RUN LED. PHASE FAILURE LED. PHASE REVERSAL LED. LOW PRESSURE LED. DELUGE OPEN LED. INTERLOCK ON LED. TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch). TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch). EMERGENCY ISOLATING SWITCH OFF LED. (If unit ordered with Automatic Power Transfer Description Firetrol FTA1000 Full Voltage Fire Switch). Pump Controllers are intended for use with electric Minimum Run Timer / Off Delay Timer motor driven fire pumps where the capacity of the Daylight Savings Time Option power source permits full voltage starting.

Description—Firetrol® FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven re pumps where the capacity of …

Tags:

  Fta1000

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FTA1000 - Fire Sprinklers

1 E-Mail Print Close Product Description Full Voltage Starting Electric FTA1000 . Fire Pump Controllers Built-in Start and Stop push-buttons to bypass automatic start circuits Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators Single handle Isolating Disconnect Switch/Circuit Breaker mechanism POWER ON LED. PUMP RUN LED. PHASE FAILURE LED. PHASE REVERSAL LED. LOW PRESSURE LED. DELUGE OPEN LED. INTERLOCK ON LED. TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch). TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch). EMERGENCY ISOLATING SWITCH OFF LED. (If unit ordered with Automatic Power Transfer Description Firetrol FTA1000 Full Voltage Fire Switch). Pump Controllers are intended for use with electric Minimum Run Timer / Off Delay Timer motor driven fire pumps where the capacity of the Daylight Savings Time Option power source permits full voltage starting.

2 Full volt- Weekly Test Timer age is applied to the motor as soon as the controller Elapsed Time Meter is actuated. The controller monitors, displays and Digital Pressure Display records fire pump system information. USB Host Controller and Port Full voltage starting is simple and low cost and is Solid State Pressure Transducer preferred whenever the utility or emergency genera- Data Log tor set will permit this type of starting. Event Log (3000 Events). True RMS Metering with simultaneous 3 phase Approvals Firetrol fire pump controllers are listed display of amps and volts by Underwriters' Laboratories, Inc., in accordance Disk Error message with UL218, Standard for Fire Pump Controllers, Disk Near Full message CSA, Standard for Industrial Control Equipment, Pressure Error message and approved by Factory Mutual. They are built to Motor Over 320% message meet or exceed the requirements of the approving Local Start message authorities as well as NEMA and the latest editions Remote Start message of NFPA 20, Installation of Centrifugal Fire Pumps, Emergency Start message and NFPA 70, National Electrical Code.

3 Fail To Start message Undervoltage message Standard Features The following are included as Overvoltage message standard with each controller: High Speed Open Serial Communications Port Voltage surge protector NEMA Type 2 enclosure Main Disconnect Switch sized for connected mo- Suitable for use as Service Equipment tor horsepower and voltage Fire pump Circuit Breaker Motor contactor Emergency Manual Run Mechanism to mechani- cally close motor contactor contacts in an emer- gency condition Specifications FTA1000 . Electric Fire Pump Controllers -1900. Main Fire Pump Controller position without affecting the tripping characteristics The main fire pump controller shall be a factory of the circuit breaker. The controller door shall have assembled, wired and tested unit and shall conform a locking type handle and three point cam and roller to all the requirements of the latest edition of NFPA vault type hardware. The circuit breaker trip curve 20, Standard for the Installation of Stationary Pumps adjustment shall be factory set, tested and sealed for for Fire Protection and NFPA 70, National Electrical the full load amps of the connected motor.

4 The circuit Code. breaker shall be capable of being field tested to verify The controller shall be listed by Underwriters Labo- actual pick up, locked rotor, and instantaneous trip ratories, Inc., in accordance with UL218, Standard for points after field installation without disturbing incom- Fire Pump Controllers, CSA, and Canadian Standards ing line and load conductors. Association , Standard for Industrial Con- trol Equipment (cULus), approved by Factory Mutual Operator Interface and approved by the City of New York for fire pump The fire pump controller shall feature an operator service. interface with user keypad. The interface shall moni- tor and display motor operating conditions, including Starting Method all alarms, events, and pressure conditions. All alarms, The controller shall be of the combined manual events, and pressure conditions shall be displayed and automatic type designed for: with a time and date stamp.

5 The display shall be a 2- Full Voltage Starting line, 20-character, vacuum fluorescent, dot matrix type Solid State Soft Starting designed to allow easy viewing from all angles and in Wye (Star)-Delta Open Transition Starting all light conditions. The display and interface shall be Wye (Star)-Delta Closed Transition Starting NEMA rated for Type 2, 3R, 4, 4X, and 12 protection Part Winding Starting and shall be fully accessible without opening the con- Primary Resistance Reduced Voltage Starting troller door. The display and user interface shall uti- Autotransformer Reduced Voltage Starting lize multiple levels of password protection for system security. A minimum of 3 password levels shall be of the fire pump motor having the horsepower, volt- provided. The display shall be capable of being pro- age, phase and frequency rating shown on the plans grammed for any language. and drawings. The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall Ammeter/Voltmeter mounted enclosure.

6 The fire pump controller operator interface shall be capable of displaying true RMS digital motor Withstand Ratings (Short Circuit Current Ratings) voltage and current measurements for all three All controller components shall be front mounted, phases simultaneously. Displays requiring push- wired and front accessible for maintenance. The mini- button and selector switches to toggle between mum withstand rating of the controllers shall not be phases or current and voltage shall not be ac- less than 100,000 Amps RMS Symmetrical at 200- cepted. 600 Volts*. If the available system fault current ex- ceeds these ratings, the controllers shall be supplied Voltage and current shall be measured by True with a withstand rating of 150,000 or 200,000 Amps RMS technology to provide the most accurate RMS Symmetrical, as required. measurement for all sine waves, including non- *Note: 100,000 Amp withstand rating not available in sinusoidal waveforms.

7 Average responding meters some larger horsepowers. Consult factory for will not be accepted. details. Isolation Switch and Circuit Breaker Digital Status/Alarm Messages The controller shall include a motor rated combi- The digital display shall indicate text messages nation isolating disconnect switch/circuit breaker, for the status and alarm conditions of: mechanically interlocked and operated with a single, Motor On Sequential Start Time externally mounted handle. When moving the handle Minimum Run Time Local Start from OFF to ON, the interlocking mechanism shall / Off Delay Time Remote Start sequence the isolating disconnect switch ON first, and Fail to Start System Battery Low then the circuit breaker. When the handle is moved Under Voltage Over Voltage from ON to OFF, the interlocking mechanism shall Locked Rotor Trip Over Frequency sequence the circuit breaker OFF first, and then the Emergency Start Motor Over 320%.

8 Isolating disconnect switch. Drive Not Installed Motor Overload The isolating disconnect switch/circuit breaker Disk Error Printer Error shall be mechanically interlocked so that the enclo- Disk Near Full Pressure Error sure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater The Sequential Start Timer and Minimum Run Timer/. mechanism. The isolating disconnect switch/circuit Off Delay Timer shall be displayed as numeric values breaker shall be capable of being padlocked in the reflecting the value of the remaining time. OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON. LED Visual Indicators The START, STOP and SYSTEM PRESSURE shall LED indicators, visible with the door closed, shall be digitally displayed and adjustable through the user indicate: interface. The pressure transducer shall be mounted Power On Emerg.

9 Isolating Switch Open inside the controller to prevent accidental damage. Pump Running Low System Pressure The pressure transducer shall be directly pipe mounted Alarm Transfer Switch Normal to a bulkhead pipe coupling without any other support- Deluge Open Transfer Switch Emergency ing members. Field connections shall be made exter- Phase Failure Phase Reversal nally at the controller coupling to prevent distortion of Interlock On the pressure switch element and mechanism. Data Logging Operation The digital display shall monitor the system and A digitally set On Delay (Sequential Start) timer log the following data: shall be provided as standard. Upon a call to start, the Motor Calls/Starts Elapsed Motor Run Time user interface shall display a message indicating the Last Trip Currents Elapsed Power On Time remaining time value of the On Delay timer. Last Breaker Trip Maximum Run Currents The controller shall be field programmable for Minimum Voltages Minimum Run Currents manual stop automatic stop.

10 If set for automatic stop- Maximum Voltages Last Motor Run Time ping, the controller shall allow the user to select either Last Phase Failure Last Start Currents a Minimum Run Timer or an Off Delay Timer. Both Last Phase Reversal Min/Max Frequency timers shall be programmable through the user inter- Min/Max Pressure face. Event Recording Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index num- ber. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. USB Host Controller - The controller shall have a built-in USB Host Controller. A USB port capable of accepting a USB Flash Memory Disk (aka: flash drive, thumb drive, memory stick, ) shall be provided.