Example: quiz answers

FX07 Field Controller Technical Bulletin

Technical Bulletin FX07 Terminal Unit Controller Issue Date June 9, 2014 2014 Johnson Controls, Inc. 1 Code No. LIT-12011269 FX07 Field Controller Introduction to FX07 Field Controller .. 4 Features ..5 Installation .. 6 North American Emissions Compliance ..8 Installation Procedures .. 8 Mounting the FX07 Controller ..8 Electronic Circuit Isolation Diagram ..11 Powering the FX07 Controller - 24 VAC Models ..12 Powering the FX07 Controller - 90 to 240 VAC Models (Models Unavailable in North America) ..13 Connection Details for FX07 Controller ..14 Jumper Settings for FX07 Controller .

Figure 1: FX07 Field Controller Models . The FX07 is a field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating,

Tags:

  Controller

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FX07 Field Controller Technical Bulletin

1 Technical Bulletin FX07 Terminal Unit Controller Issue Date June 9, 2014 2014 Johnson Controls, Inc. 1 Code No. LIT-12011269 FX07 Field Controller Introduction to FX07 Field Controller .. 4 Features ..5 Installation .. 6 North American Emissions Compliance ..8 Installation Procedures .. 8 Mounting the FX07 Controller ..8 Electronic Circuit Isolation Diagram ..11 Powering the FX07 Controller - 24 VAC Models ..12 Powering the FX07 Controller - 90 to 240 VAC Models (Models Unavailable in North America) ..13 Connection Details for FX07 Controller ..14 Jumper Settings for FX07 Controller .

2 17 N2 Open Communication Card ..18 LONWORKS Communication Card ..21 RS-232C Communication Card ..23 Connecting the Modem ..25 BACnet Communication Card ..30 Room Command Modules ..34 Remote User Interfaces ..40 FX Programming Inputs and Outputs .. 44 Introduction .. 44 Inputs and Outputs Concepts .. 44 Detailed Inputs and Outputs Procedures .. 45 Analog Inputs ..45 Digital Inputs ..47 Analog Outputs ..48 Digital Outputs ..50 2 FX07 Field Controller Technical Bulletin Operation .. 54 Operation Concepts .. 54 Communication Services ..54 Event Management ..54 Trend Logging ..54 Time Scheduling.

3 54 User Interfaces ..54 Supervisory Option ..55 Application Configuration and Commissioning ..55 Security ..56 Application Upload/Download ..56 Detailed Operation Procedures .. 56 Communication Services ..56 Event Management ..57 Trend Logging ..58 Time Scheduling ..60 User Interfaces ..62 Integral Display Operation ..64 Supervisory Option ..76 Application Configuration and Commissioning ..79 Security ..87 Application Download ..90 Troubleshooting .. 96 Reading 9999 or Invalid from the Analog Inputs ..96 Specifications and Technical Data .. 97 Ordering Codes .. 97 Technical Specifications.

4 104 I/O Technical Details ..104 FX07 Controller ..106 N2 Open BACnet MS/TP LONWORKS Communication ..108 FX07 Field Controller Technical Bulletin 3 FX Programming GSM Connection ..109 4 FX07 Field Controller Technical Bulletin Introduction to FX07 Field Controller Figure 1: FX07 Field Controller Models The FX07 is a Field Controller in the Facility Explorer range of products. The Controller is designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications, such as small refrigeration compressors, close control units, rooftop air handlers, fan coil units, unit ventilators, and chilling or heating ceiling beam installations.

5 The Controller has 17 physical inputs and outputs and supports a wide range of temperature sensors and actuating devices. Active sensors for the measurement of humidity, pressure, and other variables are also supported. The FX07 also includes an onboard real-time clock to support the start-stop scheduling of equipment and real-time based control sequences. The FX07 has an optional attractive Liquid Crystal Display (LCD) with a set of graphic status icons used in the most common HVACR applications. The Controller also supports a remote panel or wall mounted Medium User Interface (MUI).

6 Communication cards enable the Controller to integrate into an N2 Open, LONWORKS , or BACnet network of a building automation system. FX07 Field Controller Technical Bulletin 5 For stand-alone applications, the FX07 also features communications services to transmit event notification messages via Short Messaging Service (SMS) using an RS-232C Serial communication card and Global System for Mobile Communications (GSM) modem. Using the FX Tools software package, you can fully configure and program the FX07 for a wide range of commercial HVACR applications. Features The features of the FX07 include.

7 Fully programmable Controller using FX Tools software package RS-485 (N2 Open or BACnet Master-Slave/Token-Passing [MS/TP]) or LON TP/FT-10 (twisted pair/free topology) plug-in communication card for connection to a supervisory system as an alternative, an RS-232C communications port for a modem (or null modem) connection in stand-alone applications compatible with Global System for Mobile Communications (GSM) modems DIN rail mounting removable screw connectors for servicing operations 17 physical inputs and outputs including relays and triacs wide range of analog sensor inputs: passive temperature: A99, PT1000 Standard, PT1000 Extended Range, NTC 10k, and Ni1000 (Johnson Controls) active voltage: ratiometric and 0 - 10 VDC optional user interfaces.

8 Integral or remote real-time clock for time-based control sequences events displayed on user interface (up to 20 events) FX CommPro online software tool for commissioning and service operations FX Programming Key for easy application loading 6 FX07 Field Controller Technical Bulletin Installation This section takes you through the process of installing a FX07 Field Controller . ! WARNING: Risk of Electric Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment.

9 Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. AVERTISSEMENT: Risque de d charge lectrique. D brancher ou isoler toute alimentation avant de r aliser un branchement lectrique. Plusieurs isolations et d branchements sont peut- tre n cessaires pour -couper enti rement l'alimentation de l' quipement. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entra ner une d charge lectrique et de provoquer des blessures graves, voire mortelles. IMPORTANT: Use this FX07 Controller only as an operating control.

10 Where fa ilure or malfunction of the FX07 could lead to personal injury or damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls that are intended to warn of, or protect against, failure or malfunction of the FX07 Controller . IMPORTANT: In North America, the Controller is intended for installation with Class 2 inputs and outputs only where no special electrical safety mounting precautions are generally necessary. These controllers are UL Listed as Open Energy Management Equipment per UL 916.