GOBI Manual DE - REFCO

GOBII nstallation and operating guideInstallations- und BedienungsanleitungGuide d installation et d utilisationIstruzioni per l'installazione e l'usoGu a de instalaci n y funcionamiento Installatiehandleiding en gebruiksaanwijzingINSTRUCTIONSBox Contents1. gobi Pump2. Filter3. Backplate4. Front cover5. Condensate collection x 25mm (1 ) screws (x3)Rawl plugs (x3)GOBIC ondensate removal pumpInstallation and operating guideThe gobi is a self-containedcondensate removal system foruse outside but directly adjacent toair conditioning air handlers, asshown INSTRUCTIONS AND WARNINGU nder normal use this equipment requires no user intervention. Installation, both fixingand electrical, and maintenance work shall be carried out only by the manufacturer orby its service center or in any case by a person having similar skills, so as to preventany risk.

GOBI Installation and operating guide Installations- und Bedienungsanleitung Guide d’installation et d’utilisation Istruzioni per l'installazione e l'uso

Tags:

  Manual, Gobi, Gobi manual

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of GOBI Manual DE - REFCO

1 GOBII nstallation and operating guideInstallations- und BedienungsanleitungGuide d installation et d utilisationIstruzioni per l'installazione e l'usoGu a de instalaci n y funcionamiento Installatiehandleiding en gebruiksaanwijzingINSTRUCTIONSBox Contents1. gobi Pump2. Filter3. Backplate4. Front cover5. Condensate collection x 25mm (1 ) screws (x3)Rawl plugs (x3)GOBIC ondensate removal pumpInstallation and operating guideThe gobi is a self-containedcondensate removal system foruse outside but directly adjacent toair conditioning air handlers, asshown INSTRUCTIONS AND WARNINGU nder normal use this equipment requires no user intervention. Installation, both fixingand electrical, and maintenance work shall be carried out only by the manufacturer orby its service center or in any case by a person having similar skills, so as to preventany risk.

2 Electrical installation of equipment shall be in compliance with theseinstallation instructions and with all National and Local Regulations for Electrical reduce the risk of fire, electrical shock and injury to persons, the following safetyinstructions shall be used: This pump is intended for indoor use with water only (max 25 C).This pump is NOT ALL power supplies before starting installation, connection ormaintenance pump is provided with a grounding conductor. To reduce the risk of electricshock, be certain that it is connected only to a properly grounded, grounding electrical installation, make sure this condensate pump is connected to acircuit having a switch with contact separation in all poles that provide fulldisconnection from the power supply under over-voltage categories electrical installation, a fuse non-time delay (rated 250V 1A), shall be fittedinto the line, supply side, see electrical installation power cord is not replaceable.

3 If the power cord is damaged then the entirepump must be should be supervised to ensure that they are not left unattended in thearea where the pump is in or persons with reduced physical, sensory or mental capabilities whichlimits their ability to use the appliance should have a responsible person to instructthem in its not allow any chemicals to come into contact with this pump. Remove the pumpfrom the system before using cleaning fluid or any other chemicals. Flush the systemwith clean water before re-connecting the any installations where property damage and/or personal injury might result from aninoperative or leaking pump, it is strongly recommended that the alarm relay should beused to operate an alarm and/or switch off the air conditioning unit.

4 All interconnecting tubes and cables should be confined within the air conditioningunit, or enclosed in any way. All fittings on this pump are designed to be finger-tight. The use of tools to attachpipework may result in damage to the HandedLeft Screw the backplate to the wallbelow the air handler and justoverlapping the outlet hole. Enlarge theoutlet hole if Cut the drain hose level with thebottom of the Place the gobi pump on themounting posts, feed the power cablethrough the air handler outlet hole andconnect the discharge Slide the filter over the pump inlettube and fit the condensate collectiontray onto the Slide on the cover and snap gobi can be installed on the left or right hand side of the air following installation instructions refer to a right handed installation.

5 For left handedinstallations swap the positions of the pump and condensate collection tray as ConnectionsConnect the ground, live and neutral wire from the supply cable of the gobi pump tothe supply terminals (see )This product must be connected using a switch with contact separation in all poles thatprovide full disconnection from the power supply under over-voltage categories III. Afuse non time delay (rated 250V 1A), shall be fitted into the line, supply side (see). ContactsVolt Free Break On Fault connection is rated 5amps 1250VA. It may be necessary to use acontactor if the air handler supply is to be Connections1 GREEN/ YELLOWEARTHE2 BLACKLIVEL3 WHITENEUTRALN4 VIOLETA larm contact5 VIOLETA larm contactWire ColourConnectSymbolELNPOWER & the pump is live during testing2.

6 Remove the gobi Half fill the condensate collection tray withclean tap water - The pump will start on lowpower. It may be noisy whilst air is purgedfrom the Continue to add water until the sensor is fullysubmerged - The pump will switch to fullpower and the alarm contacts will Allow the gobi to remove the water fromthe collection tray - The pump will stop andthe alarm contacts will Re-fit the gobi CleaningDo not allow the pump to collect oroperate with cleaning chemicals in ALL power Remove air-handler cover, gobi coverand condensate collection Follow manufacturers instructions butcollect chemicals in a separate Flush the system with clean Re-fit condensate collection tray.

7 gobi cover and air-handler 11 12 13 14816 17 18 19 201511234567891011121233040501060200000 Vertical lift(m)(ft)Flow rate(l/h)(US gal/h))0m Horiz50m Horiz100m HorizCapacitySpecificationsPower supply:120/240 Vac, 50/60Hz Auto sensingPower consumption:16W max., when idleAlarm relay:5A, 30 Vdc, 250 Vac Break on faultCapacity:12 litres/hour max. ( US gal/h)Maximum head:Vertical >20m (65 ft), Horizontal >100 m(328 ft) Suction 1 m max. ( ft)Ambient temp:0 - 40 CWater temp:25 C :Flame retardant ABS UL94 5 VADischarge tube:6mm (1/4 ) IDDimensions:286 x 61 x 53mm ( x x 2 )IP:44 Trouble ShootingPump does not run:Pump is pumping air:Check fuse and electrical that water is reaching the that the collection tray is that the sensor is clean that the outlet tube is is noisy:Pump continues to run with no water:Check that the mains cable and outlet tubeare not vibrating against the sides of sensor may be contaminated by dirt,mould or certain cleaning chemicals.

8 Gentlywipe the sensor with a damp cloth. If theproblem persists, repeat with methylatedspirit and then rinse with product is guaranteed for two years to be free from manufacturing defects or faultymaterials. If it should fail for either of these reasons within two years from the date ofmanufacture it will be repaired or replaced free of charge, at the option of REFCOM anufacturing Manufacturing Ltd. can accept no liability whatsoever for any loss or damagearising from the use of this product, however caused. Before using this product the usershould satisfy himself that it is suitable for use in the intended application and for themanner in which it is intended that it be product is subject to continuous development and improvement and REFCOM anufacturing Ltd.