AABDCEEFGA ) Vertical Rack Ground Bar Kit (see page 4)B ) Horizontal Rack Ground Bar Kit (see page 5)C ) Telecommunications Main Grounding Bar (see page 7)D ) Telecommunications Grounding Bar (see page 8)E ) Ground Rod / Pipe Clamps (see page 9)F ) Compression Lugs (see page 10)G ) Unit Bonding Conductors (see page 11)Legend For Typical Grounding Application(layout on following page)GroundingSolutions for Data Center Applications2 Vertical Rack Ground Bar & Kits Provides a vertical ground path between equipment mounted on the rack Typically used on two post or four post racks Blank end and studded end can be attached together to splice bars Isolators may be used to separate bar from rack (or omitted depending on application Grounding scheme) Kit includes 1 - Vertical rack ground bar 3 - Insulators 1 - #2 compression lug 8 - 1/4"-20 x 1/2" SS4 hex bolts & lock washers

A A B D C E E F G A ) Vertical Rack Ground Bar Kit (see page 4) B ) Horizontal Rack Ground Bar Kit (see page 5) C ) Telecommunications Main Grounding Bar (see page 7) D ) Telecommunications Grounding Bar (see page 8) E ) Ground Rod / Pipe Clamps (see page 9) F ) Compression Lugs (see page 10) G ) Unit Bonding Conductors (see page 11) Legend For Typical Grounding Application

Tags:

  Industreis, Pages, Cooper industries, Cooper, Grounding

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Grounding - Cooper Industries

1 AABDCEEFGA ) Vertical Rack Ground Bar Kit (see page 4)B ) Horizontal Rack Ground Bar Kit (see page 5)C ) Telecommunications Main Grounding Bar (see page 7)D ) Telecommunications Grounding Bar (see page 8)E ) Ground Rod / Pipe Clamps (see page 9)F ) Compression Lugs (see page 10)G ) Unit Bonding Conductors (see page 11)Legend For Typical Grounding Application(layout on following page)GroundingSolutions for Data Center Applications2 Vertical Rack Ground Bar & Kits Provides a vertical ground path between equipment mounted on the rack Typically used on two post or four post racks Blank end and studded end can be attached together to splice bars Isolators may be used to separate bar from rack (or omitted depending on application Grounding scheme)

2 Kit includes 1 - Vertical rack ground bar 3 - Insulators 1 - #2 compression lug 8 - 1/4"-20 x 1/2" SS4 hex bolts & lock washers 4 - 5/16"-18 SS4 hex nut & lock washers 3 - #12-24 x 5/8" yellow zinc hex washer bolts Material: 1/4" x 5/8" copper barHardwareKit LULISTEDGROUNDING EQUIPMENTCOOPER B-Line UL LabelLength1/4" ( ) x 1/2" ( ) Slots (3 on SBVB36 - 4 on SBVB72)(2) 5/16"-18 Clinch Studs On One End of SBVB36(4) 5/16"-18 Clinch Studs Two On Each End of SBVB72 See photo insert above1/4"-20 Tapped Holes (16) On SBVB361/4"-20 Tapped Holes (26) On SBVB72 SBVB36shown Part Bar Only36" & Hardware Kit36" 0 0 SBVB72 Ground Bar Only72" & Hardware Kit72" Rack Ground Bar Kit Used to consolidate grounds on the equipment rack Typically used on two post or four post racks Isolators may be used to separate bar from rack (or omitted depending on application Grounding scheme) Kit includes 1 - Horizontal rack ground bar 2 - White insulators 4 - #12-24 x 5/8" ( ) zinc plated screws & flat washers 20 - #12-24 x 1/2" ( ) zinc plated screws 2 - Ground labels Material.

3 3/16" ( ) x 1" ( ) copper barLULISTEDGROUNDING EQUIPMENTCOOPER B-Line UL LabelLength9/32" ( ) (3)3/4"( )5/8" ( ) " ( )#12-24 Tap (35)9/32" ( ) x 1/2" ( ) Slots (3)Part "482 Bar & Hardware Kit19 3/8" Plate11/2"(38mm) "(16mm)5/8"(16mm)3/4"(19mm)3/4"(19mm)11/ 2"(38mm) BarHoles17/64" (7mm)LengthMCLU niversal Grounding Bar Used as a rack mounted equipment Grounding bus Kit includes 1 - Ground bar 1 - Splice plate 2 - #12-24 x 3/4" ( ) yellow zinc plated screws 2 - #12 yellow zinc plated lock washers 2 - 1/4" yellow zinc plated flat washers Material: 3/16" ( ) x 3/4" ( ) copper barPart "48219 5/16"49018 5/16" "58423 5/16"59222 5/16" (overall)MC (mtg.)

4 Centers)HolesRack 4 Telecommunications Main Grounding Bar Used as a central consolidation point for telecommunications and other low voltage systems within the room Typically located on wall or entry room where exterior ground enters building Kit includes 1 - Grounding bar assembly 6 - #6 compression lugs 1 each - #2, 1/0, 2/0, 3/0 compression lugs 12 each - 1/4"-20 x 3/4" ( ) SS4 hex bolts, hex nuts & lock washers 6 each - 3/8"-16 x 1" ( ) SS4 hex bolts, hex nuts & lock washersSBTMGB12shown SBTMGB12 Kshown LULISTEDGROUNDING EQUIPMENTCOOPER EQUIPMENTCOOPER (2) SS4 Wall Brackets(2) 2000V RatedInsulatorsCopper Bar65/8" ( )53/4" ( )1" ( )17/8" ( )1/4" ( )(4) 3/8"-16 SS4 Button Head ScrewsDimensional DataA = 4" ( )B = 5/8" ( )C = 11/4" ( )D = 1" ( )H1 = 5/16" ( )H2 = 7/16" ( )H3 = 3/8" ( )LULISTEDGROUNDING EQUIPMENTCOOPER EQUIPMENTCOOPER UL Label12" ( )9" ( )SBTMBG12 A B B C Typ.

5 D H3(4)H1(24)H2 (14)LULISTEDGROUNDING EQUIPMENTCOOPER EQUIPMENTCOOPER UL Label9" ( )SBTMBG20 A B B C Typ. D 20" ( )H1(48)H2 (14)H3(4)Part Bar Assy12" Assy & Hardware Kit12" Bar Assy20" Assy & Hardware Kit20" Grounding Bar Kit Provides a common Grounding point within the telecommunications room Typically is located on wall of data room Kit includes 1 - Grounding bar assembly 6 - #6 compression lugs 1 each - #2, 1/0, 2/0, 3/0 compression lugs 12 each - 1/4"-20 x 3/4" ( ) SS4 hex bolts, hex nuts & lock washers 6 each - 3/8"-16 x 1" ( ) SS4 hex bolts, hex nuts & lock washers Material.

6 Copper bar & SS4 wall bracketsSBTGBK shown LULISTEDGROUNDING EQUIPMENTCOOPER EQUIPMENTCOOPER (2) SS4 Wall Brackets(2) 2000V RatedInsulatorsCopper Bar65/8" ( )53/4" ( )1" ( )17/8" ( )1/4" ( )(4) 3/8"-16 SS4 Button Head ScrewsDimensional DataA = 2" ( )B = 5/8" ( )C = 11/4" ( )D = 1" ( )H1 = 5/16" ( )H2 = 7/16" ( )H3 = 3/8" ( )LULISTEDGROUNDING EQUIPMENTCOOPER UL LabelLength9" ( )SBTGB A B C Typ. D H3(4)H1 (12)H2 (8)Part Bar Assy12" Assy & Hardware Kit12" 6 Ground Rod / Pipe Clamps Used to attach ground wire to raised floor pedestals Ground wire system inside floor can be used to ground Flextray System trays Sized for ground wires 6 AWG stranded through 250 MCM 5/16" hardware included Material.

7 SS4 U-bolt and hardware - tinned bronze castingSBPC050075closed SBPC050075open 50H2 HLPLU A Part " - 3/4"15 - " " - 11/4"25 - " " - 2"40 - " " - 3"65 - " " - 4"90 - " " - 6"125 - " Size (nominal)7 Two-Hole Mechanical Lug Use for connection of electric wire to Grounding bus Setscrew may be either allen head or hex head Includes: silicon bronze hardware Additional sizes available Sold individually Material: Copper alloy C W Compression Lugs (Long Barrel) Use for connection of electric Grounding wire to Grounding bus Sold in package of 10 pcs. Material: Tinned Copper L W C Hole #14 to #85/8"161/2"13# #8 to #45/8"161/2"131/4 #4 to #13/4"195/8"161/4 #1 to 2/01"2513/16"203/8 C W BoltSizeWireSizePart NumberLug Size & # of 12/0 - 2 Hole13/32" " 21/32" " 22/0 - 2 Hole17/32" " 7/8" 3/4" 33/0 - 2 Hole9/16" " 3/4" " 44/0 - 2 Hole9/16" " 29/32" " Dia.

8 W L C Lug Used to attach ground wires to racks or cabinets Sold in package of 10 pcs. Setscrews (2): 3/8"-24 Hex Head Oval Point Material: Aluminum - tin platedUnit Bonding Conductor Used to bond electronic equipment to vertical or horizontal rack mount busbars Sold in packages of 5 with aluminum joint compound Material: Copper wireSBUBC614 Kshown 9/32" ( ) (2 Holes)LI2 " ( ).330" ( ).630" ( )11/4" ( )11/2" ( )Part Number 12/0 - # SizePart Number " " " #6 MTW Copper Wire with Green Insulation and Yellow StripeHoles for 1/4" Both Ends#6 Compression Ring Terminal - Both EndsGrounding Strap Use to provide Grounding path SB6693/4x101/2 and SB6691x73/4 includes: (1) cable with crimped lugs and 1/4"-20 hardware SB6693/8x63/4 includes: (1) cable with crimped lugs and 3/8"-16 hardware Material.

9 #6 flexible tin plated copper wire A B A SB6693/8x63/4SB6693/4x101/2&SB6691x73/4 Part Number 1/2"2673/4" 3/4"1971" 3/4"171N/ B A 9 Crimp Tool Used to attach ground lugs to electrical wire Sold per piece 101/2" (266mm) in lengthDieless Compression Tool Used to attach ground lugs to electrical wire Sold per piece 24" (609mm) in lengthPart Number Number Compound Improves electrical continuity at a Grounding or bonding connection Sold in packages of 12 1/2 ounce per packageCross ReferencePart Number NumberCPIP anduitSBCL140162-959 LCC2/0-38DW-XSBCL240162-960 LCCX2/0-12-XSBCL440162-961 LCCX4/0-38D-XSBJCA40166-812 CMP-300-1 SBJCC40168-812 CMP-200-1 SBPC05007540170-001 GPL seriesSBPC10012540170-002 GPL seriesSBPC15020040170-003 GPL seriesSBPC25030040170-004 GPL seriesSBPC35040040170-005 GPL seriesSBPC50060040170-006 GPL seriesSBTCO40165-001CT-930 SBTCR40165-002CT-1700 SBTGB40156-012- -SBTMGB1240153-012GB2B0306 TPI-1

10 SBTMGB12K40158-012- -SBTMGB2040153-020GB4B0624 TPI-1 SBTMGB20K40158-020- -SBVB3640160-036- -SBVB36K40161-036- -SBVB7240160-072- -SBVB72K40161-072 RGS134-1Y11 Follow us on social media to get the latest product and support Division509 West Monroe StreetHighland, IL 62249 United StatesPhone: is a registered other trademarks are property of their respective Eaton BoulevardCleveland, OH 44122 United 2016 EatonAll Rights ReservedPrinted in USAP ublication No. BR303005 ENMarch 2017 CDGRD-16 RFor more information.