GUIDE SPECIFICATION FOR CARFLEX LIQUIDTIGHT FLEXIBLE nonmetallic LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall have a smooth inner surface withintegral reinforcement within the conduit wall and be designated as a TypeLFNC-B (for FNMC-B). LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be listedto UL standard UL1660. LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall beflame resistant and when used with listed fittings, is approved for theinstallation of electrical LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be installed in accordance withArticle 351, Part B of the National Electrical Code (NEC) and other applicablesections of the NEC and/or local electrical LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be marked OUTDOOR foroutdoor applications exposed to sunlight and weathering FLEXIBLE nonmetallic conduit shall be marked for DIRECTBURIAL for direct burial LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be evaluated by the NationalEvaluation Service, Inc.

GUIDE SPECIFICATION FOR CARFLEX LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT www.carlonsales.com 1.1 Liquidtight flexible Nonmetallic Conduit shall have a smooth inner surface with integral reinforcement within the conduit wall and be designated as a Type

Tags:

  Flexible, Nonmetallic, Conduit, Liquidtight, Liquidtight flexible nonmetallic conduit

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of GUIDE SPECIFICATION FOR CARFLEX LIQUIDTIGHT FLEXIBLE ...

1 GUIDE SPECIFICATION FOR CARFLEX LIQUIDTIGHT FLEXIBLE nonmetallic LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall have a smooth inner surface withintegral reinforcement within the conduit wall and be designated as a TypeLFNC-B (for FNMC-B). LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be listedto UL standard UL1660. LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall beflame resistant and when used with listed fittings, is approved for theinstallation of electrical LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be installed in accordance withArticle 351, Part B of the National Electrical Code (NEC) and other applicablesections of the NEC and/or local electrical LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be marked OUTDOOR foroutdoor applications exposed to sunlight and weathering FLEXIBLE nonmetallic conduit shall be marked for DIRECTBURIAL for direct burial LIQUIDTIGHT FLEXIBLE nonmetallic conduit shall be evaluated by the NationalEvaluation Service, Inc.

2 For the installation within a three hour or less fire-resistive floor/ceiling and two hour fire-resistive wall LIQUIDTIGHT Fittings shall be listed for the use with LIQUIDTIGHT FlexibleNonmetallic conduit and shall be marked LFNC-B (FNMC-B). LiquidtightFittings uses for direct burial applications shall be listed for Wet Locations .Gross Automation (877) 268-3700