Transcription of HID Ballast Testing
1 HID Ballast Testing2. HID Short-Circuit Lamp CurrentTo assure the Ballast is delivering the proper current under lampstarting conditions, a measurement may be taken by connecting anammeter between the lamp socket center pin and the socket shellwith rated input voltage applied to the Ballast . If available, a socketadapter may be Energize Ballast with proper rated input Measure current with ammeter at A1 and A2 as shown Readings must be within test limits shown on using a clamp-on ammeter for this measurement, becertain the meter is not near the magnetic field of the Ballast orany steel member which might distort the magnetic short-circuit lamp current test results in high, low or noreading, further checks should be made to determine whethercause is attributable to improper supply voltage, shorted or opencapacitor or inoperative Ballast .
2 Checks may be made as follows: Supply Voltage CheckMeasure Line Voltage. If Ballast is multi-voltage unit, makecertain input voltage connection is made to proper input voltageterminal or lead. Capacitor CheckVerify capacitor rating is as required and shown on Ballast label. Ballast CheckPerform Open-Circuit Voltage test to ensure operation within theRMS range shown in the table to the HID Open-Circuit and Short-Circuit Test LimitsLOWPRESSURESODIUMBALLASTSHIGH PRESSURESODIUM BALLASTS*MERCURYBALLASTSMETAL HALIDEBALLASTSLAMPANSIW attageNumberSecondaryShortCircuitCurrent Amps* CAUTION: Always disconnect the ignitor before measuring the output voltage of High Pressure Sodium ballastsand Pulse Start metal halide ballasts.
3 High voltage starting pulses can damage commonly used H46225 H43225 255 225 255 2 400 (ILO) 2 H33225 400 (Series)2 H33475 525 H35405 455 405 455 Reactance Autotransformer(HX)70M98 230 280 240 Wattage Autotransformer(CWA)175 M57 285 320 M59285 400 (ILO)2 M59285 400 (Series)2 M59600 (LLRPSL) (SCWA) S54110 S55110 325 455 505 505 455 L73 645 715 L74645 715 Constant Wattage Autotransformer Pulse StartLow Loss Linear Reactor Pulse StartOpenCircuitVoltageRMSS hort-Circuit Current TestA1V1A2 OUTPUTCOMMONCAPLAMPSOCKETBALLASTINPUTLIN EO utdoorSheet#: TD-110 TD - 110 Continuity of Primary Coil 1.
4 Disconnect Ballast from power supply and discharge thecapacitor. 2. Check for continuity of Ballast primary coil between input of Secondary Coil1. Disconnect Ballast from power supply and discharge Check for continuity of Ballast secondary coil between lampand common HID Ballast ContinuityNOTE: Information compiled by Advance Transformer Co. and reprinted with VCOMCOMLAMPCAPB etween Common and Line VCOMCOMLAMPCAPB etween Common and Capacitor VCOMCOMLAMPCAPB etween Line and Lamp VCOMCOMLAMPB etween Common and Lamp VCOMLAMPB etween Common and Capacitor VCOMCOMLAMPB etween Common and Lamp Ballast Testing 2002 Acuity Lighting Group, Inc. 3/02 Sheet #: TD-110 Lithonia LightingAcuity Lighting Group, LightingOne Lithonia Way, Conyers, GA 30012-3957 Phone: 770-922-9000 Fax: 770-918-1209In Canada: 1100 50th Ave.
5 , Lachine, Quebec H8T