Transcription of In this catalogue - tnb.ca
1 In this and High VoltageElastimold / Fisher Pierce cable Accessories ..Section AHomac / Blackburn Overhead Connectors ..Section BHomac Underground Distribution ..Section CBoreal Flexible DRussellstoll Electrical Interconnection EAlphanumerical FElastimold Fisher Pierce cable ..A2 Ratings ..A3 A4 Standard Interfaces ..A5200 A Loadbreak ..A6 A9200 A Deadbreak ..A10 A11600 Series Deadbreak ..A12 A15600 Series Deadbreak Cam-Op , Link-Op ..A16 A17600 Series Deadbreak Stick-Op , Window-Op ..A18 A19600 Series Deadbreak cable Joints ..A20 A21 Molded Multi-Point Junctions ..A22 A23 PCJ Power cable Joints ..A24 A25 cable Terminations ..A26 A29 Shield Adapters, Sealing and Grounding ..A30 A31 Equipment Bushings ..A32 How to Specify Size-Sensitive Products ..A33 A34 AEIC and ICEA cable Insulation Diameter ..A35 A38WX Size Tables ..A39 A41 Shrink-Fit cable Joints ..A42 A43 Ranger2 Terminations ..A44 A49 Faulted Circuit Indicators ..A50 A57 Underground Distribution Switchgear.
2 A58 A69 Molded Fuse Products ..A70 A79 Surge Arresters ..A80 A85 Molded Vacuum Recloser ..A86 A87 Table of ContentsA1 Elastimold cable Elbow Connectors and their related accessories are available in 200 A loadbreak, 200 A deadbreak and 600 A deadbreak styles. Rated for padmount,subsurface, vault, indoor, outdoor and other applications, units feature interchangeable interfaces which can be easily engaged or separated to provide a convenient method toconnect or disconnect cable and equipment in a distribution section provides an easy-to-use, comprehensive listing of Elastimold products for5 kV thru 35 kV underground power distribution systems. Included are separable elbowconnectors, cable joints, terminations and other cable accessory components. Thiscatalogue incorporates information relative to product application, ratings and Thomas & Betts Elastimold brand is recognized as the leading producer of premoldedcable accessory components worldwide. Utilizing specially formulated materials with 100%peroxide-cured insulation and shielding, Elastimold products represent the state-of-the-artin premolded process technology.
3 Durable, quality construction and non-degrading, high-reliability, maintenance-free performance is assured when specifying Elastimold s broad line of premolded products offers significant advantages over field-fabricated and other alternatives, including: 100% factory assurance testing prior todelivery and installation; simplified, single-piece construction with built-in insulating, shielding and sealing surfaces; ease of installation with no special skills or tools required;and compact, lightweight, durable designs for easy handling and Special Component Services Group provides custom products tailored to specific application requirements. Please contact the factory for further information regarding this service. For Surge Arresters see pages A80 to A85 and FusedElbows, see pages A70 to Joints are available in permanently crimped or bolted (separable) connectorstyles. Permanently crimped units are rated the same as the cable they are connecting and are available for all applications including direct Terminations are available in single-piece or modular designs.
4 Rated for indoor,outdoor or padmount applications, units allow connection and transition from shielded underground cables to bare overhead conductors and live-front cable Tests and PerformanceElastimold Separable Connectors, cable Joints, cable Terminators and other cable accessory products have been designed and tested per applicable portions of IEEE, ANSI and other industry standards including: IEEE 386 Standard For Separable Connectors IEEE 404 Standard For cable Joints and Splices IEEE 48 Standard For cable Terminations IEEE 592 Standard For Exposed Semiconducting Shields ANSI Standard For Copperand Aluminum Conductor Connectors AEIC CS8 Standards For XLPand EPR Insulated Cables ICEA S-94-649-2004 and S-97-682-2000 Standard for Cables Rated 5,000 46,000 VCable Joints and Terminations RatingsRefer to the pages listed below for rating information: PCJ cable Joints, page A24 cable Terminations, page A26 to A29 Separable Connector RatingsTable 1 shows voltage and current ratings which apply to all Separable Connectors including 200 A Loadbreak, 200 A Deadbreak and 600 Series Deadbreak products.
5 Table 2 shows switching and fault close ratings which only apply to 200 A Loadbreak cable 115 kV Class Ratings25 kV Class Ratings35 kV Class Ratings OPERATING VOLTAGEM aximum line-to-ground (See Application Info Note 1) kV BILI mpulse withstand x 50 microsecond wave95 kV125 kV150 kV WITHSTAND VOLTAGEAC One MinuteDC Fifteen Minute34 kV53 kV40 kV78 kV50 kV103 kV CORONA EXTINCTION LEVEL@ 3pC Sensitivity11 kV19 kV26 kV200 A ProductsContinuous Current:Symmetrical Momentary Current:600 Series ProductsContinuous Current:Symmetrical Momentary Current:200 A*10 kA sym, 10 cycle duration600 and 900 A*25 kA sym, 10 cycle durationTable 2 Loadmake/Loadbreak SwitchingFault Close15 kVClass Ratings 1 and 3 circuits kV line to ground, kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power fault close operation at kV or kV; 10,000 A, rms, sym. 10 cycles ( sec.) max. asym factor applies to new or used mating parts (up to maximum designated switching operations.)
6 25 kVClass Ratings 1 and 3 circuits kV line to ground, kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power fault close operation at kV or kV; 10,000 A, rms, sym. 10 cycles ( sec.) max. asym factor applies to new or used mating parts (up to maximum designated switching operations.)35 kVClass Ratings 1 and 3 circuits kV line to ground, kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power fault close operation at kV or kV; 10,000 A, rms, sym. 10 cycles ( sec.) max. asym factor applies to new or used mating parts (up to maximum designated switching operations.)Application Information: 1. Loadbreak connectors are designed and rated for use on grounded WYE systems. For application on ungrounded WYE or delta systems,the next higher voltage class product is recommended. Examples: 5 kV ungrounded: use 15 kV class products; 15 kV ungrounded: use 25 kV class products; 25 kV ungrounded: use 35 kV class Products are designed and constructed for all applications including padmount, subsurface, vault, indoor, outdoor, direct sunlight, direct buried and continuously submerged in Products are designed and rated for ambient temperatures of -40 C to +65 C.
7 It is recommended that loadbreak connectors be hotstick operated at -20 C to +65 C ambient temperature range and at altitudes not exceeding 6000 ft.* Designed for 90 C maximum continuous operating temperatureRatingsCertified Tests and Performance (cont d)Elastimold cable InterfacesStandard Interfaces for Separable Connectors,Components and Equipment BushingsANSI/IEEE Standard 386 defines the specific interface dimensions that 200 A and 600 Series elbows, inserts, junctions, equipment bushingsand any mating components must conform to insure interchangeability. The table below provides information concerning the types of interfacessupplied by Elastimold for various applications and is useful to assure proper matching of No200 A DEEPWELLEQUIPMENT BUSHING15 kV, 25 kVand 35 kV200 A BushingWell kV, kV, kVIEEE386-2001 Fig. 3200 A LOADBREAK INSERT15 kV 200 A kV kVIEEE386-2001 Fig. 5200 A LOADBREAK INSERT25 kV200 A kV kVIEEE386-2001 Fig. 7, Note 1200 A LOADBREAK INSERT35 kV200 A LoadbreakInterface No.
8 KV kVIEEE386-2001 Fig. 7, Note 1200 A DEADBREAK INSERT15 kV and 25 kV200 A kV and kVIEEE386-2001 Fig. 4600 SERIES EQUIPMENT BUSHING15 kV and 25 kV600 A DeadbreakInterface kV and kVIEEE386-2001 Fig. 11600 SERIES EQUIPMENT BUSHING35 kV600 A DeadbreakInterface kVIEEE386-2001 Fig. 131. Elastimold uses Fig. 7 interface for both 25 and 35 kV cable A Loadbreak200 A loadbreak connectors and accessories provide a convenientmethod to connect/disconnect cable and equipment on powerdistribution systems. Loadbreak elbows include provisions forenergized operation using standard hotstick tools, allowingloadmake/break operation and a visible disconnect. Components canbe isolated with insulated caps, plugs and parking accessories allow system grounding, testing,bypass, lightning surge protection and current limiting connecting points and taps can be provided by useof junctions or OverviewSee page A3 A4 for complete information including switchingand fault close Ratings200 A Continuous10 kA sym.
9 , 10 CyclesVoltage Ratings15 kV Class kV kV Phase-to-Phase95 kV BIL34 kV AC Withstand53 kV DC Withstand11 kV Corona Extinction25 kV kV kV Phase-to-Phase125 kV BIL40 kV AC Withstand78 kV DC Withstand19 kV Corona Extinction35 kV kV kV Phase-to-Phase150 kV BIL50 kV AC Withstand103 kV DC Withstand26 kV Corona Extinction200 A LOADBREAK SEPARABLE CONNECTOR COMPONENTSCABLE TO EQUIPMENTCONNECTIONSBUSHINGWELLLOADBREAK BUSHING INSERTEXTENDEDBUSHING INSERTBUSHING WELLPLUGLOADBREAKFEED-THRU INSERTBOLTEDELBOWW/TAPOPERATING ACCESSORIESINSULATED PARKINGBUSHINGFEED THRUPARKINGSTANDGROUNDINGPLUGLOADBREAK ELBOW CONNECTORWITH OR WITHOUT TEST POINTREPLACEMENTELBOWREPAIRELBOWGROUNDIN GELBOWFUSED ELBOWINSULATED CAPINSULATED CAPWITH GROUNDASSEMBLY TOOLSEE PAGESA80 TO A85 FORSURGE ARRESTERAPPLICATIONSE lastimold cable A LoadbreakIllustration(not to scale)DescriptionVoltageClassELASTIMOLDC at. kV165LR-W5 XUse Tables W1 and X1N2, 3, 4, 525 kV275LR-W5 XUse Tables W16 and X1N2, 3, 4, 535 kV375LR-W5 XUse Tables W3 and X2N2, 3, 5 ElbowConnectorw/ Test Point15 kV166LR-W5 XUse Tables W1 and X1N2, 3, 4, 5, 2425 kV276LR-W5 XUse Tables W16 and X1N2, 3, 4, 5, 2435 kV376LR-W5 XUse Tables W3 and X2N2, 3, 5, 24 Jacket SealElbowConnector15 kV165 LRJS-W5 XUse Tables W1 and X1N2, 1925 kV275 LRJS-W5 XUse Tables W16 and X1N2, 19 Jacket SealElbowConnectorw/ Test Point15 kV166 LRJS-W5 XUse Tables W1 and X1N2, 19, 2425 kV276 LRJS-W5 XUse Tables W16 and X1N2, 19, 24 Repair ElbowConnector15 kV167 ELR-W5 XUse Tables W5 and X1N5, 10, 1825 kV273 ELR-W5 XUse Tables W5 and X1N5, 10, 18 Repair ElbowConnectorw/ Test Point15 kV168 ELR-W5 XUse Tables W5 and X1N5, 10, 18, 2425 kV274 ELR-W5 XUse Tables W5 and X1N5, 10, 18, 24 ReplacementElbow15 kV167 RLR-W5 XUse Tables W4 and X1N5, 11, 1325 kV273 RLR-W5 XUse Tables W2 and X1N5, 11.
10 13 ReplacementElboww/ Test Point15 kV168 RLR-W5 XUse Tables W4 and X1N5, 11, 13, 2425 kV274 RLR-W5 XUse Tables W2 and X1N5, 11, 13, 24 Direct TestElbowConnector15 kV167 DLR-W5 XUse Tables W4 and X1N2, 5, 2225 kV273 DLR-W5 XUse Tables W2 and X1N2, 5, 22 Direct TestRepair ElbowConnector15 kV167 DELR-W5 XUse Tables W5 and X1N5, 10, 18, 2225 kV273 DELR-W5 XUse Tables W5 and X1N5, 10, 18, 22 Direct TestRepair ElbowConnectorw/ Test Point15 kV168 DELR-W5 XUse Tables W5 and X1N5, 10, 18, 22, 2425 kV274 DELR-W5 XUse Tables W5 and X1N5, 10, 18, 22, 24 Fused Elbow(Full RangeCurrent Limiting)15 kV25 kV168 FLR H-W0X274 FLR H-W0 XSee Product GuidePG-PC-H Bolted Elboww/ Tap15 kV167 LRT-W5 XUse Tables W4 and X1N17 Bushing Insert15 kV25 kV35 kV35 kV1601A42701A43701A43701A3N4, 8, 20N4, 8, 20N6, 21N8, 21 ExtendedBushing Insert15 kV25 kV1601EA42701EA4N8, 20N8, 20 Feed-ThruInsert15 kV25 kV35 kV1602A3R2702A13702A1N16N16N6, 16 Insulated Cap15 kV160 DRN9 Insulated Capw/ Ground15 kV15 kV25 kV35 kV160 DRG167 DRG273 DRG375 DRGN9N7, 9N7, 9N7, 9N1.