Transcription of INSTALLATION INSTRUCTIONS R 410A Ductless …
1 421 01 9220 00 10/01/12 INSTALLATION INSTRUCTIONSR 410a Ductless Split SystemAir Conditioner and Heat PumpMODELS: DLC4(A/H) Outdoor, DLF4(A/H) IndoorSIZES: 9K, 12K, 18K, 24K, 30K, and 36 KNOTE: Read the entire instruction manual before starting the OF CONTENTSPAGEPARTS UNIT Mounting Hole in Wall for Connecting Piping,Drain&Wiring..9 OUTDOOR UNIT and Drainage and Power Wiring from Outdoor PURGING AND LEAKAGE FILTER following parts are included in your indoor unit. Pleasecontact your dealer if any parts are damaged or Plate1 Remote Control1 Remote Control Holder1 Mounting Hardware7 Battery ( )2 SAFETY CONSIDERATIONSI nstalling, starting up, and servicing air conditioningequipment can be hazardous due to system pressures,electrical components, and equipment location (roofs,elevated structures, etc.)
2 Only trained, qualified installers and service mechanicsshould install, start up, and service this personnel can perform basic maintenancefunctions such as cleaning coils. All other operations shouldbe performed by trained service working on the equipment, observe precautions in theliterature and on tags, stickers, and labels attached to all safety codes. Wear safety glasses and workgloves. Keep quenching cloth and fire extinguisher nearbywhen brazing. Use care in handling, rigging, and settingbulky these INSTRUCTIONS thoroughly and follow all warningsor cautions included in literature and attached to the local building codes and National Electrical Code(NEC) for special requirements.
3 In Canada, refer to currenteditions of the Canadian Electrical Code, CSA Recognize safety information. This is the safety alertsymbol !!. When you see this symbol on the unit and ininstructions or manuals, be alert to the potential for these signal words: DANGER,WARNING, and CAUTION. These words are used with thesafety alert symbol. DANGER identifies the most serioushazards which will result in severe personal injury or signifies hazards which could result in personalinjury or death.
4 CAUTION is used to identify unsafepractices which may result in minor personal injury orproduct and property damage. NOTE is used to highlightsuggestions which will result in enhanced INSTALLATION ,reliability, or operation.!WARNINGELECTRICAL SHOCK HAZARDF ailure to follow this warning could result in personalinjury or installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFFposition. There may be more than 1 disconnect out and tag switch with a suitable warning !
5 EQUIPMENT DAMAGE HAZARDF ailure to follow this caution may result in equipmentdamage or improper not bury more than 36 in. (914 mm) of refrigerantpipe in the ground. If any section of pipe is buried, theremust be a 6 in. (152 mm) vertical rise to the valveconnections on the outdoor units. If more than therecommended length is buried, refrigerant may migrateto the cooler buried section during extended periods ofsystem shutdown. This causes refrigerant slugging andcould possibly damage the compressor at start INSTRUCTIONS R 410a Ductless Split System.
6 DLF4(A/H), DLC4(A/H)2 421 02 9220 00 GENERALT hese INSTRUCTIONS cover the INSTALLATION , start up and servicingof DLC4(A/H) outdoor and DLF4(A/H) indoor units REQUIREMENTSA llow sufficient space for airflow and servicing unit. See Figure. 1for minimum required distances between unit and walls : Both refrigerant lines must be Minimum refrigerant line length between the indoor and outdoorunits is 10 ft.
7 (3 m).S The following maximum lengths are allowed:REFRIGERANT LINE LENGTHS ft. (m)Unit SizeMax LineLengthMax Elevation(ID over OD)Max Elevation(OD over ID)9K50 (15)33 (10)33 (10)12K66 (20)33 (10)33 (10)18, 24K82 (25)33 (10)33 (10)30, 36K98 (30)33 (10)33 (10)S The following are the piping SIZESUnit SizeMix PhaseVapor9, 12K1/4 3/8 18K1/4 1/2 24, 30, 36K1/4 5/8 R 410a Refrigerant Charge TableUnit SizeCharge Amount *LBS (kg)Additional Charge Amount **oz/ft (g/m)Metering Device **Cool OnlyHeat PumpCool OnlyHeat ( ) ( ) (15) (20) ( ) ( ) (15) (20) ( ) ( ) (15) (20) ( ) ( )
8 (15) (50)EXV30K ( ) (50) ( ) ( ) (50) (50)EXV* Charge is for piping that runs up to 25 ft. ( m)** For piping runs greater than 25 ft. ( m), add this amount of charge per foot of extra piping, up to the allowable length, specified in the above table.** EXV Electronic Expansion DeviceConnecting (Power and Control Cable)S The main power is supplied to the outdoor unit. The fieldsupplied connecting cable from the outdoor unit to indoor unitconsists of four wires and provides the power for the indoor unitas well as the communication signal and ground between theoutdoor and indoor unit.
9 Two wires are high voltage AC power, one is low voltage DCsignal and one is a ground Consult local building codes, NEC (National Electrical Code) orCEC (Canadian Electrical Code) for special !EQUIPMENT DAMAGE HAZARDF ailure to follow this caution may result in equipmentdamage or improper Based on the MCA s in the electrical table, only 14 AWGwire should be Use copper conductors only with a minimum 300 voltrating and 2/64 inch thick !EQUIPMENT DAMAGE HAZARDF ailure to follow this caution may result in equipmentdamage or improper Be sure to comply with local codes while running wire fromindoor unit to outdoor Every wire must be connected firmly.
10 Loose wiring maycause terminal to overheat or result in unit malfunction. Afire hazard may also exist. Therefore, be sure all wiring istightly No wire should be allowed to touch refrigerant tubing,compressor or any moving Disconnecting means must be provided and shall belocated within sight and readily accessible from the Connecting cable with conduit shall be routed throughhole in the conduit Data TableUnitSizeSystem VoltageVolts Ph. FanIndoor FanMCAMax Fuse/CB Amps(MOCP)RLALRAFLAO utputWattsVoltsFLAHPO utputWatts(Min/Max)9K115 1 60103 V 1 60103 V 1 60187 V 1 60187 V 1 60187 375 V 1 60187 V 1 60187 V INSTRUCTIONS R 410a Ductless Split System.