INSTALLATION MANUAL - Daikin Comfort

INSTALLATIONMANUALR410A SPLIT SERIESMODELSFTXB09A RXB09 AFTXB12 ARXB12 AFTXB18 ARXB18 AFTXB24 ARXB24 AFTKB09 ARKB09 AFTKB12 ARKB12 AFTKB18 ARKB18 AFTKB24 ARKB24 AInstallation ManualR410A Split SeriesManuel d installationS rie split R410 AManual de instalaci nSerie Split R410 AEnglishFran aisEspa olIM-5 WMYJ(R)-0617(3)- Daikin USAPart Number.: R08019046594 CCVR IM-5 WMYJ(R)-0617(3)- Daikin U1 1 CVR IM-5 WMYJ(R)-0617(3)- Daikin U1 112/19/19 11:32:33 AM12/19/19 11:32:33 AMCVR IM-5 WMYJ(R)-0617(3)- Daikin U2 2 CVR IM-5 WMYJ(R)-0617(3)- Daikin U2 212/19/19 11:32:34 AM12/19/19 11:32:34 AMEnglish1-1 Indoor Unit [FTXB/FTKB]NBFRONT VIEWTOP VIEWCSIDE VIEWBTHE MARK SHOWS PIPING DIRECTIONREARREARRIGHTLEFTBOTTOMBOTTOMFR ONT GRILLE FIXED SCREWS (INSIDE)LOUVERSIGNAL RECEIVERINDOOR UNIT ON/OFF SWITCHROOM TEMPERATURE THERMISTOR (INSIDE)NAME PLATETERMINAL BLOCK WITH EARTH TERMINALOUTLINE AND DIMENSIONSO riginal InstructionA1 IM-5 WMYJ(R)-0617(3)- Daikin USA1 11 IM-5 WMYJ(R)-0617(3)- Daikin USA1 112/19/19 11

This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirement. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.

Tags:

  Manual, Conditioners, Daikin, Air conditioners

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of INSTALLATION MANUAL - Daikin Comfort

1 INSTALLATIONMANUALR410A SPLIT SERIESMODELSFTXB09A RXB09 AFTXB12 ARXB12 AFTXB18 ARXB18 AFTXB24 ARXB24 AFTKB09 ARKB09 AFTKB12 ARKB12 AFTKB18 ARKB18 AFTKB24 ARKB24 AInstallation ManualR410A Split SeriesManuel d installationS rie split R410 AManual de instalaci nSerie Split R410 AEnglishFran aisEspa olIM-5 WMYJ(R)-0617(3)- Daikin USAPart Number.: R08019046594 CCVR IM-5 WMYJ(R)-0617(3)- Daikin U1 1 CVR IM-5 WMYJ(R)-0617(3)- Daikin U1 112/19/19 11:32:33 AM12/19/19 11:32:33 AMCVR IM-5 WMYJ(R)-0617(3)- Daikin U2 2 CVR IM-5 WMYJ(R)-0617(3)- Daikin U2 212/19/19 11:32:34 AM12/19/19 11:32:34 AMEnglish1-1 Indoor Unit [FTXB/FTKB]NBFRONT VIEWTOP VIEWCSIDE VIEWBTHE MARK SHOWS PIPING DIRECTIONREARREARRIGHTLEFTBOTTOMBOTTOMFR ONT GRILLE FIXED SCREWS (INSIDE)LOUVERSIGNAL RECEIVERINDOOR UNIT ON/OFF SWITCHROOM TEMPERATURE THERMISTOR (INSIDE)NAME PLATETERMINAL BLOCK WITH EARTH TERMINALOUTLINE AND DIMENSIONSO riginal InstructionA1 IM-5 WMYJ(R)-0617(3)- Daikin USA1 11 IM-5 WMYJ(R)-0617(3)- Daikin USA1 112/19/19 11:33.

2 50 AM12/19/19 11:33:50 AM1-2 Dimension ModelABCDEFGHIJKLMN09/1235-1/16 (890)11-11/16 (297)8-1/4 (210)5-7/8 (149)7-5/16 (186)1-3/8 (35)2(51)3-15/16(100)3-15/16(101)6 (153)7-1/8 (181)8-1/8 (207)2-1/16 (52)32-2/3 (830)All dimensions are in Inch (mm)DBGHJLMAKFIGFET hrough the wall hole 2-9/16" (65mm)Drain hose positionLiquid pipe endGas pipe endINSTALLATION PLATE 18/24 Recommended mounting plate retention spots (7 spots in all)All dimensions are in Inch (mm) Recommended mounting plate retention spots (5 spots in all)Through the wall hole 2-9/16" (65mm)Drain hose positionGas pipe endLiquid pipe endEFGIKMLJHGFBDAINSTALLATION PLATE 09/12 Indoor Unit [FTXB/FTKB]Dimension ModelABCDEFGHIJKLMN18/2446-1/8 (1172)12-5/8 (320)9-1/2 (242)9-5/8(244)12-7/8(327)2-9/16 (66)1-3/4(45)3-15/16(100)4(102)3-9/16(91 )8-5/8(219)25(634)1-3/4(45) 43-1/2(1106)1 IM-5 WMYJ(R)-0617(3)- Daikin USA2 21 IM-5 WMYJ(R)-0617(3)- Daikin USA2 212/19/19 11:33:51 AM12/19/19 11:33.

3 51 AMEnglish1-3 Outdoor Unit [RXB/RKB]Dimension ModelABCDEFGHIJKLMNO1833-11/16(855)24-3/ 4(628)12-15/16(328)20-1/2(520)7-1/16(179 )1-13/16(46)4(101)4-7/16(113)23-3/4(603) 4-15/16(126)6-7/16(164)9/16(15)1-5/16(34 )15/16(23)14-1/4(362)2433-11/16(855)28-3 /4(730)12-15/16(328)20-1/2(520)7-1/16(17 9)1-13/16(46)4(101)4-7/16(113)23-3/4(603 )4-15/16(126)6-7/16(164)9/16(15)1-5/16(3 4)15/16(23)14-1/4(362)Dimension ModelABCDEFGHIJKLMNOPQ09/1221-5/8(550)25 -15/16(658)2(51)7/16(11)10-3/4(273)5/8(1 6)9/16(14)18-1/2(470)3-3/4(96)3-11/16(93 )3-11/16(94)2-3/8(60)9/16(14)5-1/4(133)5 /16(8)3/8(10)11-3/4(299)Dimension ModelPQRST182-7/8(73)2-15/16(75)5/16(8)2 -5/8(67)1/4(7)242-7/8(73)2-15/16(75)5/16 (8)2-5/8(67)1/4(7)EFBHINQKLGAMCDJ5/64 (2)OPBAONPQDMIJJKLFECGHLSRTAll dimensions are in Inch (mm)All dimensions are in Inch (mm)1/8 (3)1 IM-5 WMYJ(R)-0617(3)- Daikin USA3 31 IM-5 WMYJ(R)-0617(3)- Daikin USA3 312/19/19 11:33:51 AM12/19/19 11:33:51 AM1-4!

4 WARNING! CAUTIONOnly qualified personnel must carry out the INSTALLATION work. INSTALLATION must be done in accordance with this INSTALLATION MANUAL . Improper INSTALLATION may result in water leakage, electric shock, or installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed ambient space, can lead to oxygen only specified accessories and parts for INSTALLATION work. Failure to use specified parts may result in water leakage, electric shock, fire, or the unit the air conditioner or heat pump on a foundation strong enough to withstand the weight of the unit.

5 A foundation of insufficient strength may result in the unit falling and causing into account strong winds, typhoons, or earthquakes when installing. Improper INSTALLATION may result in the unit falling and causing sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local, state, and national regulations. An insufficient power supply capacity or improper electrical construction may lead to electric shock or sure that all wiring is secured, that specified wires are used, and that no external forces act on the terminal connections or wires. Improper connections or INSTALLATION may result in wiring, position the wires so that the electrical wiring box cover can be securely fastened.

6 Improper positioning of the electrical wiring box cover may result in electric shock, fire, or the terminals touching electrical parts, turn off the unit. It is recommended to install a ground fault circuit interrupter if one is not already available. This helps prevent electric shock or fasten the outdoor unit terminal cover (panel). If the terminal cover/panel is not installed properly, dust or water may enter the outdoor unit causing fire or electric installing or relocating the system, keep the refrigerant circuit free from substances other than the specified refrigerant (R410A) such as air. Any presence of air or other foreign substance in the refrigerant circuit can cause an abnormal pressure rise or rupture, resulting in not change the setting of the protection devices.

7 If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur. Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric not allow children to play on or around the unit to prevent heat exchanger fins are sharp enough to cut. To avoid injury wear gloves or cover the fins while working around not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts.

8 Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper drain piping to proper drainage. Improper drain piping may result in water leakage and property piping to prevent careful when transporting the not turn off the power immediately after stopping operation. Always wait for at least 5 minutes before turning off the power. Otherwise, water leakage may not use a charging cylinder. Using a charging cylinder may cause the refrigerant to R410A in the system must be kept clean, dry, and tight.(a) Clean and Dry -- Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting into the system(b) Tight -- R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth s protection again harmful ultraviolet radiation.

9 R410A can contribute to the greenhouse effect if it is released. Therefore, take proper measures to check for the tightness of the refrigerant piping INSTALLATION . Read the chapter Refrigerant Piping and follow the R410A is a blend, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in a state of gas, its composition can change and the system will not work indoor unit is for R410A. See the catalog for indoor models that can be connected. Normal operation is not possible when connected to other units. SAFETY PRECAUTIONSINSTALLATION MANUALThis MANUAL provides the procedures of INSTALLATION to ensure a safe and good standard of operation for the air conditioner adjustment may be necessary to suit local using your air conditioner, please read this instruction MANUAL carefully and keep it for future appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge.

10 Unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their should be supervised to ensure that they do not play with the IM-5 WMYJ(R)-0617(3)- Daikin USA4 41 IM-5 WMYJ(R)-0617(3)- Daikin USA4 412/19/19 11:33:52 AM12/19/19 11:33:52 AMEnglish1-5 Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). Install the indoor unit far away from fluorescent lamps as much as units are for indoor INSTALLATION only. Outdoor units can be installed either outdoors or indoors. This unit is for indoor not install the air conditioner or heat pump in the following locations:(a) Where a mineral oil mist or oil spray or vapor is produced, for example, in a kitchen.