1 MTH SERIES installation , Operation, and Service Manual ! WARNING ONLY FACTORY AUTHORIZED BURNER Service PERSONNEL SHOULD START UP, ADJUST, OR Service THIS EQUIPMENT IC-SA-1714 8/2015 MTH SERIES installation , Operation, and Service Manual Manual Number: IC-SA-1714 Release Date: August 2015 Information to be filled out by owner Unit Serial Number: Date of installation : Distributor Information Name: Address: Phone Number: 750-00523-000 Copyright 2015 by Industrial Combustion All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted in any form or by any means without the prior written consent of Industrial Combustion.
2 Industrial Combustion 351 21st Street Monroe, WI 53566 608-325-3141 PREFACE It is the responsibility of the owner of this equipment to post and maintain a legible copy of this installation , Operation and Maintenance Manual while this equipment is in Service . Warning and caution references have been made in this Manual and should be adhered to for smooth operation of the burner. ! Warning This symbol precedes information which, if disregarded, may result in injury to the user of the burner or to others. ! Caution This symbol precedes information which, if disregarded, may result in damage to the burner.
3 NOTE: This symbol precedes information which is vital to the operation or maintenance of the burner. Model designations are based on the type of fuel(s) to be fired and the amount of furnace pressure to be overcome. Burner size is based on firing rate (rated input in Btu/hr). Model Standards Fuel-Air Atomization MTH Gas The equipment must be installed in accordance with applicable local, state, or Provincial installation Requirements including the National Electrical Code (NEC) and Associated Insurance Underwriters. Where applicable, the equipment shall be installed in accordance with the Provincial installation Requirements, or in their absence, the Canadian Gas Association (CGA) and and Canadian Standard Association (CSA) B140 and B139 (for oil burners) installation Codes shall prevail.
4 Authorities having jurisdiction should be consulted before installations are made. Oil and gas burning equipment shall be connected to flues having sufficient draft at all times to assure safe and proper operation of the burner. The MTH Series burners are designed to burn gas only as defined by ASTM D396-2010 specifications. Low NOx Emission Configuration Burner Model MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- 010 015 025 035 042 052 063 084 105 126 147 160 Number 2 2 3 4 Gas volume (MBTU/h) HHV 1000 1500 2500 3500 4200 5250 6300 8400 10500 12600 14700 16000 Turndown (max.)
5 3:1 3:1 4:1 4:1 5:1 5:1 5:1 6:1 6:1 6:1 6:1 6:1 Tonnage boiler (90% efficiency) tons/hr Fan motor horsepower HP(KW) 1(.75) 1(.75) 2( ) 5( ) 5( ) ( ) 10( ) 10( ) 10( ) 15(11) 20(15) 25(19) Furnace pressure (inch W. C.) 4 4 4 4 6 6 6 6 6 6 6 6 Furnace pressure (mBar) 10 10 10 10 15 15 15 15 15 15 15 15 Gas pipeline diameter (inches) (mm) (33) (33) (48) (48) (48) (48) (48) (60) (60) (60) (73) (73) Low gas pressure (PSI) 1 1 1 2 2 2 2 2 2 2 2 2 Low gas pressure (mBar) Manifold gas pressure (inch) 12 12 17 32 17 21 23 9 10 12 16 21 Manifold gas pressure (mBar) 30 30 41 80 42 51 57 22 24 30 40 52 Excess air (%) 60 60 60 60 60 60 60 60 60 60 60 60 Air pressure (inches) 6 6 6 12 5 8 12 4 6 9 12 16 Air pressure (mBar) The amount of air cubic feet / minute (SCFM)
6 261 391 652 913 1095 1369 1643 2191 2738 3286 3834 4173 The amount of air Nm3 / min 7 11 18 26 31 39 46 62 77 93 108 118 Burner diameter (inch) 6 6 6 6 10 10 10 15 15 15 15 15 Inner diameter of the burner (mm) 152 152 152 152 241 241 241 381 381 381 381 381 Burner Length (inch) 10 12 20 17 21 26 32 27 34 40 47 47 Burner length (mm) 254 305 508 432 533 660 800 686 864 1016 1194 1194 Flame Diameter(inch) 12 12 14 14 16 16 18 21 21 23 23 23 Flame diameter (mm) 305 305 356 356 394 394 445 533 533 584 584 584 Flame Length (inch) 20 22 30 27 31 36 37 44 50 57 57 Flame length (mm) 508 559 762 686 787 914 1054 940 1118 1270 1448 1448 Mouth length (inch) Mouth length (mm) 305 305 305 305 305 458 458 458 559 559 559 559 Burner Model MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- MTH- 210 252 294 336 378 400 420 504 540 630 Number 5 6 7 Gas volume - high calorific value (MBTU/h) HHV 21000 25200 29400 33600 37800 40000 42000 50400 54000 63000 Turndown (max.)
7 6:1 6:1 6:1 6:1 6:1 6:1 6:1 6:1 6:1 6:1 Tonnage boiler (90% efficiency) tons/hr Fan motor horsepower HP(KW) 25(19) 40(30) 50(37) 50(37) 60(45) 60(45) 75(56) 75(56) 100(75) 100(75) Furnace pressure (inch W. C.) 7 9 8 8 8 8 8 Furnace pressure (mBar) Gas pipeline diameter (inches) (mm) (89) (89) (114) (114) (114) (114) (114) (114) (114) (114) Low gas pressure (PSI) 3 3 4 4 4 4 5 5 5 5 Low gas pressure (mBar) Manifold gas pressure (inch 36 38 40 46 52 52 52 52 52 52 Manifold gas pressure (mBar) 90 95 100 114 129 129 129 129 129 129 Excess air (%) 60 60 60 60 60 60 60 60 60 60 Air pressure (in ) 11 11 9 9 9 9 9 Air pressure (mBar) The amount of air cubic feet / minute (SCFM))
8 5477 6572 7668 8763 9858 10432 10954 13144 14083 16430 The amount of air Nm^3/min 155 186 217 248 279 295 310 372 399 465 Burner diameter (inch) 20 20 26 26 26 26 32 32 32 32 Inner diameter of the burner (mm) 508 508 660 660 660 660 813 813 813 813 Burner Length (inch) 48 56 51 60 60 60 50 60 60 70 Burner length (mm) 1219 1422 1295 1524 1524 1524 1270 1524 1524 1778 Flame diameter (inch) 26 26 34 34 36 36 40 40 42 42 Flame diameter (mm) 660 660 864 864 914 914 1016 1016 1067 1067 Flame Length (inch) 58 66 61 70 70 70 60 70 70 80 Flame length (mm) 1473 1676 1549 1778 1778 1778 1524 1778 1778 2032 Mouth length (inch) Mouth length (mm) 565 565 565 565 565 565 565 565 565 565 The quantity of gas is based on the calorific value of the fuel and the altitude of 2,000 feet or less.
9 If the altitude > 2,000 ft then derate input by 4% for every 1,000 ft above 2,000 ft. For altitudes > 8,000 ft consult with factory. The amount of gas depends on 1,000 Btu / cubic foot (Btu / ) and specific gravity gas. When using the 50 Hz power supply, please consult the factory. MTH models have UL / cUL certification from 2,500 to 16,000 MBtu (other models are also available). MTH Series Standard Dimensions Accompanying dimensions are for layout purposes only. Burner Number Size Size Size Size Size Size DIM 2 3 4 5 6 7 Length in inches Overall Burner Length J 83 150 154 181 Overall Burner Length (mm) J 3810 Length of Element C 78 82 92 Length of Element (mm) C Mounting Flange to Panel H 72 72 89 Mounting Flange to Panel (mm) H Width in inches Center line to right side T 24 29 36 Center line to right side (mm) T Center line to left side K 24 30 Center line to left side (mm)
10 K 762 Height in inches Center line to top A 17 Center line to top (mm) A Center line to bottom P 33 Center line to bottom (mm) P Hinge pivot point in inches Mounting flange to hinge B Mounting flange to hinge (mm) B Center line to hinge L Center line to hinge (mm) L 221 Burner support in inches Length of support F 9 12 Length of support (mm) F Width of support R 8 10 Width of support (mm) R 254 Mounting flange to support G Mounting flange to support (mm) G 696 Mounting flange dimensions in inches Outer diameter N 23 28 33 39 45 Outer diameter (mm) N 1143 Bolt circle diameter M 21 26 31 37 43 Bolt circle diameter (mm) M Bolt hole quantity W 8 8 8 12 16 16 Bolt hole diameter V Bolt hole diameter (mm) V Gas inlet dimensions in inches Center line to main gas inlet S Center line to main gas inlet (mm)