1 ENH Series Cool ChangerSuper-thermal conductive pipe (heat pipe)type heat exchanger for control panelInstruction ManualInside-the-panel mount type(Standard voltage model and irregular voltage model)ENH-105L/110L/115L/115S/130L/165 LOutside-the-panel mount type(Standard voltage model)ENH-115L-O/115S-O/130L-O/165L-OCAU TION Be sure to read this Instruction Manual beforeusing this equipment. Keep this Instruction Manual with 0755-26497123 0755-264971242 This Instruction Manual uses the following symbols to allow users to recognize important instructions at a glance. Before reading this Manual , become familiar with these symbols. The degrees of the danger and damage resulting from negligence of these safety instructions or improper use of this equipment are classified with the following sym-bols: Before using this equipment, read this Instruction Manual carefully and understand its contents thoroughly.
2 This Instruction Manual will not be reissued. Keep this Manual with care. We cannot guarantee the safety of this equipment, if you use it in an unintended manner other than specified in this Instruction Manual . Be sure to comply with the safety instructions , cautions, and warnings described in this Manual . The types of instructions to be complied with by users are classified with the following symbols:The following symbols are typical and DefinitionWARNINGCAUTIONCAUTIONF ailing to comply with the instructions described here may result in physical injury (electric shock, burn, etc.)Failing to comply with the instructions described here may result in failure of this symbol indicates an Instruction that calls user s symbol indicates an inhibited operation or symbol indicates a compulsory operation or symbol indicates precautions to be taken to avoid electric shock.
3 Safety InstructionsThis Instruction Manual contains important information and instructions necessary to ensure safe opera-tion and proper maintenance of this using this equipment, read carefully the following safety Introduction 2. Part Names 3. Installation 3-1 Mounting the ENH Unit 3-2 Mounting the filter and protective covers 4. Wiring 5.
4 Operation Starting Operation 6. Inspection and Maintenance 6-1 Fan Replacement 6-2 Procedure for Replacing the Fans 6-3 Filter Replacement 6-4 Outside air fins cleaning procedure 7. Outer Dimensions 8.
5 Diagram of Installation Work 9. Specifications 10. Repair/Warranty 4455677788810101116182014 Introduction2 Part Names8050100 1060120180 This equipment consists of fans and a heat pipe, and ithas a structure to isolate the air inside the inner fan draws the hot air inside the control panelto the area around the lower section of the heat heat is released into the outside air by using theconductivity of the heat pipe so that an increase in theair temperature can be the heat pipe is a vacuum and a small amount of workingfluid. When the hot inside air is drawn to the area around the heat-absorbing section, the working fluid absorbs the heat, vaporizesand immediately ascends inside the pipe.
6 The evaporated fluidreleases the heat at the upper section of the pipe, is cooled by theoutside air, and then condenses and returns to cycle of the absorption of latent heat, heat dissipation, andcondensation is repeated continually inside the heat pipe at conditionAs shown in the figure below, half the length of a super-thermal conductive pipe isimmersed in a hot water bath maintained at 80 C. The graph shows the increasein the temperature of the upper end of the pipe immediately after immersion bycomparing it with the result of a normal copper pipe.* The super-thermal conductive pipeis generally called a heat pipe. Itsprinciple was found by Gaugler(General Motors, ) in 1942and was named by Grover in 1963. Response of super-thermal conductive pipe<Inside-the-panelmount type> <Outside-the-panelmount type>Outside airHeat pipeInside thecontrol panelInside thecontrol panelOutside airHeat pipeHeat-dissipating sectionThe fluid vaporizesand fluidHeat-dissipating sectionTemperature of hot water (80 C)Super-thermal conductivepipeTime (second)Nomal copper pipeTemperature of upper end ( C)Super-thermal conductive pipeBathHot waterHeater<Inside-the-panel mount type> <Outside-the-panel mount type>FilterOutsideair fanTerminalblock forpower supplyPanel coverOutsideair fanFilterOutsideair fanPanel cover35 InstallationCAUTION Cut a hole in the appropriate section of thecontrol panel according to the panel workdimensions.
7 Mount the equipment securely with properscrews. Be sure to mount the equipment with its heat-absorbing section at the bottom (for inside aircirculation). Be sure to mount the equipment in a verticalposition. Consider the mounting position carefullybecause objects near the air inlet/outlet willaffect the cooling ability. Take extra care not to cut your fingers orhands with the aluminum fin on the outlet port. Do not use the ENH heat exchanger outdoors. Do not use the equipment in a place where the temperature exceeds or drops below theallowable ambient temperature or where corrosive or flammable gases may be generated. Do not use the equipment in a place where it may be exposed to vibration or shock. Avoid installing the equipment in a place where it may be exposed to vapor or water. Because this is heat-exchanging type cooling equipment, it cannot cool the air inside thecontrol panel to a temperature lower than that of the outside air.
8 Depending on the position of the devices inside the control panel, the air circulation may beinsufficient, resulting in an uneven temperature inside the control panel. In such a case,provide additional appropriate circulation or change the positions of the devices susceptibleto heat to the lower section of the control Mounting the ENH Unit1. Test the machine before installing the unit. Before cutting the control panel, cover the equipment in the panel with a plastic sheet tokeep metal chips out. Install this equipment horizontally or vertically. The securing screws (four) for the protection cover are set on the heat exchanger unitupon product delivery. Make sure to remove the screws before installing the main unit.(These instructions are for the inside-the-panel mount type only. Screws are provided in abag with the outside-the-panel mount type.)
9 Please take the following precautions when installing the to the Installation Work Diagram in section 8 to perforate the surface of the control panel to whichyou want to install the unit.<Inside-the-panelmount type> <Outside-the-panelmount type>Outside theControlpanelInside theControlpanelOutside theControlpanelInside theControlpanel63. Installation3-2 Mounting the filter and protective that the power has been turned off beforemounting.<Inside-the-panel mount type> the protective covers in the designatedpositions with four fixing screws for the filter from the upper side of the protec-tive cover for the air intake port. CAUTION Attach the protective cover of the ENH-105L to the mounting surface on the control that the power has been turned off the protective covers in the designatedpositions with four fixing screws for each.
10 <Outside-the-panel mount type> the filter from the upper side of the protec-tive cover for the air intake port. Protective coverFilterProtective cover7 Set the power supply breaker to ON to start Connect the power supply using proper cables. Tighten the screws a crimp terminal (with an insulating cap) to connect the power supply cable to the power supply the fan starts, check that the fan rotates in the proper direction and that there is no abnormalitysuch as vibration or Be sure to use the rated power supply. Check the specifications and provide an appropriate breaker (commercial product) betweenthe heat exchanger and the power supply. Be sure to ground the grounding terminal (FG). Double-check the voltage and wiring before turning on the Note that the internal circulation fan starts continuous operation immediately after thepower is turned careful not to catch your fingers between the operating fan and the fan guard.