Introduction to Modbus Serial and Modbus TCP

Table 1. Modbus over Serial Line uses a three-layer 1. A slave address field and error check wrap around a Modbus 2. RTU framing is more condensed than ASCII (No part of the Extension may be reproduced without the written consent of Contemporary Controls.)Volume9 Issue5 SEPTEMBER OCTOBER 2008 2008 Contemporary Control Systems, George Thomas, Contemporary ControlsIn this second part of a two-partseries on Modbus , we will discusstwo implementations of the ModbusProtocol that were introduced in ourprevious article. The first implemen-tation is the traditional implementa-tion of Modbus over a Serial second implementation is moremodern with Modbus operating overa TCP/IP network. Both implementa-tions remain over Serial has released a Modbusover Serial Line Specification andImplementation Guide provides guidance when usingModbus with Serial links. As mentioned in our previous article, Modbus was originally intended tobe used with point-to-point EIA-232 Cinterfaces with the master being aHuman Machine Interface (HMI) anda PLC as the slave.

specifically, IP/Ethernet networks. Modbus.org authored the Modbus Messaging on TCP/IP Implementation Guide V1.0bfor this very purpose. Instead of a three-layer model that was used for Modbus over Serial Line, a five-layer Internet model was used for Modbus TCP as shown in Table 2. Instead of a long discussion on physical and data link

Tags:

  Messaging, Messaging on tcp ip

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Introduction to Modbus Serial and Modbus TCP

1 Table 1. Modbus over Serial Line uses a three-layer 1. A slave address field and error check wrap around a Modbus 2. RTU framing is more condensed than ASCII (No part of the Extension may be reproduced without the written consent of Contemporary Controls.)Volume9 Issue5 SEPTEMBER OCTOBER 2008 2008 Contemporary Control Systems, George Thomas, Contemporary ControlsIn this second part of a two-partseries on Modbus , we will discusstwo implementations of the ModbusProtocol that were introduced in ourprevious article. The first implemen-tation is the traditional implementa-tion of Modbus over a Serial second implementation is moremodern with Modbus operating overa TCP/IP network. Both implementa-tions remain over Serial has released a Modbusover Serial Line Specification andImplementation Guide provides guidance when usingModbus with Serial links. As mentioned in our previous article, Modbus was originally intended tobe used with point-to-point EIA-232 Cinterfaces with the master being aHuman Machine Interface (HMI) anda PLC as the slave.

2 Multiple slavesconnected to one master would thenrequire multiple links which isinconvenient and expensive. Itwould be only natural to change thepoint-to-point link to a multipointserial infrastructure such as EIA-485which would allow one master tocommunicate to multiple slaves overa common Serial line. This approachis encouraged in the , but not mentioned in theoriginal Modicon Modbus ProtocolReference Layer ModelInstead of the traditional seven-layerISO Open Systems InterconnectionReference Model, the Modbus overSerial Line model is collapsed tothree layers as shown in Table 1. Atthe top is the application layer thatwas discussed in part 1. This iscalled the Modbus ApplicationProtocol or simply the ModbusProtocol. Layers 3 6 are not used instead, the model relies on theapplication layer to ensure end-to-end delivery of a message. The datalink (layer 2) is occupied by theModbus Serial Line Protocol. Finally,the physical layer (layer 1) allows for either the EIA-232C or EIA-485implementation.

3 With only three layers, Modbus over Serial Line iseasier to understand than otherindustrial protocols. Since theModbus Application Protocol wasdiscussed in part 1, it will not berepeated here. Instead, only the data link and physical layers will be discussed. Data Link LayerMuch about the Modbus over SerialLine Protocol Data Unit (PDU) wasmentioned in part 1 but will be summarized below. Referring toFigure 1, note that the PDU consistsof four elements. In the middle isthe Modbus PDU consisting of afunction code and data. MostModbus implementations only use asubset of all the available functioncodes. The data structure maychange depending upon the functioncode. Wrapping the Modbus PDU isan address field and an error checkfield. The address field only containsslave addresses or the broadcastaddress. The master address is notrequired and not referenced sincethis is a master/slave protocol withcommands originating from a unique mentioned in part 1, the actualframing of Modbus over Serial Linemessages depends on whether ASCIIor RTU transmission mode is is the most popular mode andis shown in Figure 2.

4 It is a verycompact frame with only one bytereserved for the slave or broadcastaddress, one byte for the functioncode and two bytes for the CRCerror check. A single byte carries thefunction code. Notice that there is no end-of-frame sequence. WithRTU, end-of-frame is indicated character times of silence. Introduction to Modbus Serial and Modbus TCP2 The largest frame occupies only 256bytes. With RTU each byte is sentusing 11 bits. Each data characterrequires eight bits. There is one start-bit, one stop-bit and one parity-bit. Ifparity is not used, another stop-bit issent in its place. If parity is employed,it can be odd or ASCII message format in Figure3 requires two bytes for the slaveaddress as well as for the functioncode. Unlike RTU, the ASCII frameuses a two-byte LRC for the errorcheck field. The advantage of theASCII format is that it is human readable. Notice that there is an end-of-frame sequence composed of carriage return and line feed (CR,LF).Inter-frame spacing is not is represented as a hexadecimalvalue coded as ASCII.

5 Therefore,only 7 bits are required for everyASCII character, but two charactersare required for each byte of start-bit and one stop-bit areused. If a parity-bit is used, eitherodd or even parity can be sent. If noparity is sent, then another stop-bit issent. This means each byte in ASCIIis sent as 10 bits. Physical Layer The original Modbus protocol calledfor a point-to-point EIA-232C linkbetween a host computer and a option remains today. But theModbus over Serial Line specificationencourages the use of the multipointEIA-485 standard supporting upto 32 devices over a common can be implemented with eithera two-wire or four-wire cabling configuration. With any of the serialline implementations, a wide rangeof baud rates from kbps to 115kbps are allowed, but all implemen-tations must at least support kbpsand kbps. The default rate NetworkFigure 4 shows a recommended two-wire interface for EIA-485 networkswith applied line polarization. Asexpected, there is one master trans-ceiver and multiple slave transceiversconnected to a common 2-wire buswith the wires labeled D1 and D0.

6 At a minimum, a total of 32 devicesmust be supported. With a 2-wirebus, the output of the transmitter isdirectly tied to the input of a receiverat each device. Even though this iscalled a 2-wire bus, there is a common reference connectionlabeled common. Each device mustshare its common with all otherdevices on the bus to ensure that themaximum common-mode voltagerating of the device is not line polarization network (consisting of a pull-up and pull-down resistor) is shown near themaster, but its location is not arequirement only a polarization is used to force thebus into a known state when nodrivers are active. EIA-485 receiversrequire a 200 mv failsafe bias toensure they detect a floating line asan off state. This is why line polarization is typically referred to asfailsafe bias. At each end of the busare line terminators (LT) to matchthe natural impedance of the pull-up and pull-down resistors interact with the two terminationresistors to create the failsafe Modbus over Serial Line specification recommends that thepull-up and pull-down resistors havevalues between 450 and 650 ohms,and that only one network is assumes that failsafe bias isneeded at all.

7 Some transceivershave built-in bias so external bias isnot NetworkFigure 5 shows a recommendedfour-wire interface still using EIA-485devices. The transmitter of eachdevice is separated from the device sreceiver. The master has its transmitterconnected to all the slaves receiverswhile all the slaves transmitters areconnected to the master s bias and termination are stillused but their requirements aredoubled in a four-wire the four-wire arrangementrequires a fifth wire and that is the Modbus over SerialLine specification supports both a 2-wire and 4-wire arrangement, the2-wire implementation is the mostpopular. Although it is possible tohave a full-duplex link with 4 wires,the Modbus protocol is strictly half-duplex. The master imitates commands to a particular slave whileawaiting the slave s response. This ishandled quite effectively with a 2-wire 3. ASCII framing requires start-of-frame and end-of-frame 4. A two-wire Serial line implementation actually requires three TCPThe Modbus protocol continues tosurvive in an automation world more interested with connecting toEthernet networks and more specifically, IP/Ethernet authored the Modbus messaging on TCP/IPImplementation Guide thisvery purpose.

8 Instead of a three-layermodel that was used for Modbusover Serial Line, a five-layer Internetmodel was used for Modbus TCP asshown in Table 2. Instead of a longdiscussion on physical and data linklayer issues, the standard only needsto point to the 1500 page IEEE There is no mention ofhow to physically attach stations orwhat cabling or connectors to messaging standard only talksabout how a Modbus PDU (consisting of a function code anddata) is encapsulated into a higherlevel protocol. Another significant change (shown inFigure 6) is that the Modbus bus isactually an IP bus. The physical anddata link layers are not of having one masterattached to multiple slaves, the termsclient and server are used. Clientscould be HMIs or PLCs, while serverscould be input/output racks. Like amaster, clients initiate commands to aserver. Like a slave, servers respondto client commands. However, theproper terminology with client/servercommunications is that clients initiaterequests with servers providingresponses.

9 It is actually a bit moreinvolved than that. *A Requestis sent by the client toinitiate a transaction.* An Indicationis sent by the server to confirm that a request was received.*A Responseis sent by the server to comply with the client request.* A Confirmationis sent by the client to acknowledge receipt of the is significant in this model isthat several clients can reside on theIP network and access a common setof servers. This is a fundamentalchange in how the Modbus protocolworks. There is no single mastercontrolling a defined set of slaves. Figure 5. A four-wire Serial line implementation actually requires five 2. Modbus TCP uses a five-layer Internet 6. Instead of using master and slaves, the Modbus TCP model uses clients and issues of the copyrighted Extension are available. Please visit our web site Select Support and clickon Extension number of clients can accessany number of servers. Is it possibleto have conflicts with clients makingcontradictory requests of a particularserver?

10 Yes, that is the risk this modelpresents with its newly gained MBAP HeaderFigure 7 shows how a new ModbusTCP/IP Application Data Unit (ADU)is formed. The traditional ModbusPDU of the Modbus over Serial Linemethod is still present. The functioncode and data definitions remainintact. What is appended to this PDUis a Modbus Application Protocol(MBAP) header, details of which areshown in Figure 8. The TransactionIdentifier is supplied by the clientand used to keep track of specificrequests. The server is to send backthe same identifier with its client is allowed to send multiple requests to a server without waiting for individual Protocol Identifier would allowsupport for multiple protocols. ForModbus the value is zero. TheLength field identifies the length ofall remaining fields including theModbus PDU fields. Finally, the UnitIdentifier provides the address of aModbus Serial Line slave that mustbe accessed through a gateway. With Modbus TCP clients andservers, station addressing occurs byusing IP addresses.