1 Series LFN170 Hot Water Master Tempering ValvesWatts Series LFN170 hot Water master tempering valves are especially designed for use on larger hot Water supply systems for mixing hot and cold Water for a variety of applications to extend the hot Water supply. This Series uses paraffin-based thermostat to sense and adjust outlet temperature. The LFN170s feature Lead free * construction to comply with Lead free * installation Lead free * brass body construction ASSE 1017 and IAPMO CUPC Listed LFN170 -M3 uses paraffin-based thermostat to sense and adjust outlet temperature Dirt and lime resistant poppet and seat design Virtual shutoff if supply pressure fails Vandal-resistant locking mechanism to secure temperature setting Factory testedSpecificationsMaximum Operating Pressure 125psig (861 kPa)Maximum Hot Water Temperature 200 F (93 C)
2 Minimum Hot Water 5 F (3 C) Above Set Point** Supply TemperatureTemperature Adjustment Range** 90 - 180 F (32 - 82 C)Hot Water Inlet Temperature Range 120 - 180 F (42 - 82 C)Cold Water Inlet Temperature Range 40 - 80 F (4 - 27 C)Listing ASSE 1017, IAPMO CUPC Approval Standards ASSE 1017, CSA CSUTFor Commercial ApplicationsES- LFN170 -M3 LEAD free *Job Name Contractor Job Location Approval Engineer Contractor s No.
3 Approval Representative Watts product specifications in customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently with governing authorities for local installation requirementsThe information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.
4 You are required to thoroughly read all installation instructions and product safety information before begin-ning the installation of this Hot Water Master Tempering Valves cannot be used for tempering Water temperature at fixtures. Severe bodily injury ( , scalding or chilling) and/or death may result depending upon system Water pressure changes and/or supply Water temperature changes. ASSE standard 1016, 1069 or 1070 listed devices such as Watts Series LFMMV, LFUSG, or LFL111 valves should be used at fixtures to prevent possible Watts Hot Water Tempering Valves are designed to be installed at or near the boiler or Water heater.
5 They are not designed to compensate for system pressure fluctuations and should not be used where ASSE standard 1016, 1069 or 1070 devices are required. These Watts valves should never be used to provide anti-scald or anti-chill ! * The wetted surface of this product contacted by consumable Water contains less than of lead by weight. ** With Equal Pressure** Low Limit cannot be less than the cold Water temperature. For best operation, hot Water should be at least 5 F (3 C) above desired set Capacity at 50-50 mixed Less CheckstopsPressure Drop Across ValveModelInlet / Outlet (NPT)Min.
6 Flow to ASSE 1017CV5psi10psi20psi30psi45psi60psi(34 kPa)(69 kPa)(138 kPa)(207 kPa)(310 kPa)(414 kPa)3/4" LFN170 -M33/4 x 3/4" 3 gpm21 gpm30 gpm37 gpm45 gpm 52 gpm11 lpm57 lpm79 lpm114 lpm140 lpm170 lpm197 lpm1" LFN170 -M31 x 1"4 gpm32 gpm45 gpm56 gpm68 gpm79 gpm 15 lpm87 lpm121 lpm170 lpm212 lpm257 lpm299 lpm11/4" LFN170 -M311/4 x 11/4"4 gpm45 gpm63 gpm76 gpm95 gpm110 gpm 15 lpm121 lpm170 lpm238 lpm288 lpm360 lpm416 lpm11/2" LFN170 -M311/2 x 11/2"5 gpm49 gpm 70 gpm86 gpm 105 gpm121 gpm 19 lpm134 lpm185 lpm265 lpm326 lpm397 lpm458 lpm2" LFN170 -M32 x 11/2 x 2" 7 gpm59 gpm83 gpm 102 gpm125 gpm144 gpm26
7 Lpm159 lpm223 lpm314 lpm386 lpm473 lpm545 lpmFlow Capacity at 50-50 mixed with CheckstopsPressure Drop Across ValveModelInlet / Outlet (NPT)Min. Flow to ASSE 1017CV5psi10psi20psi30psi45psi60psi(34 kPa)(69 kPa)(138 kPa)(207 kPa)(310 kPa)(414 kPa)3/4" LFN170 -M3 CSUT3/4 x 3/4" 3 gpm20 gpm28 gpm34 gpm42 gpm 48 gpm11 lpm53 lpm76 lpm106 lpm129 lpm159 lpm182 lpm1" LFN170 -M3 CSUT3/4 x 1"4 gpm30 gpm43 gpm52 gpm64 gpm74 gpm 15 lpm79 lpm114 lpm163 lpm197 lpm242 lpm280 lpm11/4" LFN170 -M3 CSUT11/4 x 11/4"4 gpm42 gpm60 gpm74 gpm90 gpm104 gpm 15 lpm114 lpm159 lpm227 lpm280 lpm341 lpm394 lpm11/2" LFN170 -M3 CSUT11/4 x 11/2"5 gpm47 gpm 67 gpm82 gpm 100 gpm115 gpm 19 lpm125 lpm128 lpm254 lpm310 lpm379 lpm435 lpm2" LFN170 -M3 CSUT11/4 x 2" 7 gpm57 gpm80 gpm 98
8 Gpm120 gpm139 gpm26 lpm151 lpm216 lpm303 lpm371 lpm454 lpm526 lpmCapacityTypical SpecificationMaster mixing valve shall feature paraffin-based, thermal actua-tion technology for precise temperature control. Valve shall be listed to ASSE 1017 and cUPC and shall be approved to ASSE 1017 & CSA standards. Master mixing valve shall have an approach temperature of 5 F (3 C). Valve shall have an outlet temperature range from 90 180 F (32 to 82 C) with a lockable temperature-setting feature. Valve shall be manufactured of cor-rosion resistant materials and feature a single-seat design for pos-itive shutoff.
9 It shall have a Lead free * brass body. Body shall be constructed using Lead free * brass. Lead free * master mixing valves shall comply with state codes and standards, where appli-cable, requiring reduced lead content. Minimum flows to ASSE 1017 shall be 3/4 LFN170 -M3 ( gpm, 11 lpm), 1 LFN170 -M3 ( gpm, 15 lpm), 11/4 LFN170 -M3 ( gpm, 15 lpm), 11/2 LFN170 -M3 ( gpm, 19 lpm), 2 LFN170 -M3 ( gpm, 26 lpm).Master mixing valves shall be of Watts Series LFN170 -M3. Any alternate must have a written approval prior to 1101 2011 WattsUSA: T: (978) 689-6066 F: (978) 975-8350 : T: (905) 332-4090 F: (905) 332-7068 America: T.
10 (52) 81-1001-8600 4 LFN170 -M33 4N/A3 4N/A41 2114N/A31 289N/A17 163635 89247 8124215 4 LFN170 -M3 CSUTN/A3 43 491 423541 2114117 1629131 289113 164617 163635 89247 8124215 LFN170 -M31N/A1N/A49 16116N/A31 289N/A17 163635 89247 8124215 LFN170 -M3 CSUTN/A3 41101 826449 16116129 1631931 289113 164617 163635 89247 8124215 4 LFN170 -M311 4N/A11 4N/A61 16154N/A37 1687N/A13 4443111 169451 413341 4 LFN170 -M3 CSUTN/A11 411 4121 1630661 16154151 1638337 168721 26413 4443111 169451 413341 2 LFN170 -M311 2N/A11 2N/A61 16154N/A37 1687N/A13 4443111 169451 413341 2 LFN170 -M3 CSUTN/A11 411 2131 433761 16154161 441337 168721 26413 4443111 169451 413341 LFN170 -M32 (Hot) 11 2 (Cold)N/A2N/A67 16164N/A33 1681N/A21 165237 89853 813741 LFN170 -M3 CSUTN/A11 42133 434967 16164163 442533 168121 26421 165237 89853 813741