MINNESOTA STATE FACILITIES DESIGN STANDARDS

MINNESOTA STATE FACILITIES DESIGN STANDARDS 10/5/17 MINNESOTA STATE FACILITIES DESIGN STANDARDS 7th Edition June 21, 2016 Use only the most current copy of these DESIGN STANDARDS . Most current Edition including revisions can be found at the MINNESOTA STATE FACILITIES website. MnSCU FACILITIES DESIGN STANDARDS 07/31/17 FACILITIES DESIGN STANDARDS 7th Edition Revised July 2016 Section Article Title - Change Rev. Date Appendix 1 NA Revised Window/CW Mfgr list 7/21/2016 Index III Change Tiltle to "Project Phase Requirements" 7/21/2016 II Quality Assurance and Quality Control 7/21/2016 III NA Change Tiltle to "Project Phase Requirements" 7/21/2016 III DESIGN Development - Structural Drawings 7/21/2016 III Construction Documents 7/21/2016 IV DIV 00 - General 7/21/2016 IV DIV 00 - General 7/21/2016 IV 3 DIV 01 - 01 33 00 Submittal Procedures 7/21/2016 IV 3 DIV 01 - 01 45 00 Quality Control 7/21/2016 IV DIV 01 - 01 45 00 Quality Control 7/21/2016 IV Table DIV 01 - 04 42 00 Brick Precon Test - delete water permeance 7/21/2016 IV 1 DIV 01 - 07 27 00 Air Barrier 7/21/2016 IV Table DIV 01 - 07 27 00 Air Barrier - revise testing requirements 7/21/2016 IV 1 DIV 01 - 01 57 23 Temporary Storm Water Pollution Controls 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone - revised 7/21/2016 IV

MnSCU Facilities Design Standards 07/31/17 IV 8.4.16 DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV 10.1 DIV 23 - 23 05 93 Testing, Adjusting, & Balancing 7/21/2016

Tags:

  States, Design, Standards, Testing, Facilities, Minnesota, Adjusting, Minnesota state facilities design standards

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of MINNESOTA STATE FACILITIES DESIGN STANDARDS

1 MINNESOTA STATE FACILITIES DESIGN STANDARDS 10/5/17 MINNESOTA STATE FACILITIES DESIGN STANDARDS 7th Edition June 21, 2016 Use only the most current copy of these DESIGN STANDARDS . Most current Edition including revisions can be found at the MINNESOTA STATE FACILITIES website. MnSCU FACILITIES DESIGN STANDARDS 07/31/17 FACILITIES DESIGN STANDARDS 7th Edition Revised July 2016 Section Article Title - Change Rev. Date Appendix 1 NA Revised Window/CW Mfgr list 7/21/2016 Index III Change Tiltle to "Project Phase Requirements" 7/21/2016 II Quality Assurance and Quality Control 7/21/2016 III NA Change Tiltle to "Project Phase Requirements" 7/21/2016 III DESIGN Development - Structural Drawings 7/21/2016 III Construction Documents 7/21/2016 IV DIV 00 - General 7/21/2016 IV DIV 00 - General 7/21/2016 IV 3 DIV 01 - 01 33 00 Submittal Procedures 7/21/2016 IV 3 DIV 01 - 01 45 00 Quality Control 7/21/2016 IV DIV 01 - 01 45 00 Quality Control 7/21/2016 IV Table DIV 01 - 04 42 00 Brick Precon Test - delete water permeance 7/21/2016 IV 1 DIV 01 - 07 27 00 Air Barrier 7/21/2016 IV Table DIV 01 - 07 27 00 Air Barrier - revise testing requirements 7/21/2016 IV 1 DIV 01 - 01 57 23 Temporary Storm Water Pollution Controls 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone - revised 7/21/2016 IV

2 DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV DIV 04 -04 20 00 Masonry & Stone 7/21/2016 IV 6 DIV 05 -05 12 23 Structural Steel Framing 7/21/2016 IV DIV 07 - Thermal & Moisture Protection - General revised 7/21/2016 IV 2 DIV 07 - 07 27 00 Air Barrier - added 7/21/2016 IV - DIV 08 - 08 41 13 Aluminum Entrance Frames 7/21/2016 IV misc. DIV 08 - 08 80 00 Glazing 7/21/2016 IV DIV 23 - HVAC - General 7/21/2016 IV DIV 23 - HVAC - Mechanical Rooms 7/21/2016 IV DIV 23 - Heating, Ventilation & Air Conditioning 7/21/2016 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 MnSCU FACILITIES DESIGN STANDARDS 07/31/17 IV DIV 23 - HVAC Ducted Air Systems 7/21/2016 IV DIV 23 - 23 05 93 testing , adjusting .

3 & Balancing 7/21/2016 V Table Contents Materials & Use Specifications - 07 27 00 added 7/21/2016 V Intro 01 57 23 Temporary Storm Water Pollution Controls 7/21/2016 V page 12 2 57 23 Notice of Termination of permit 7/21/2016 V new 07 27 00 Fluid Applied Membrane Air/Moisture Barrier 7/21/2016 V 08 41 13 Aluminum Framed Entrances - add & deletion 7/21/2016 V 08 41 13 Aluminum Framed Entrances - deletion 7/21/2016 V - 08 41 13 Aluminum Framed Entrances - add 7/21/2016 V 12 08 41 13 Aluminum Framed Entrances - deletion 7/21/2016 V 08 44 13 Aluminum Curtain Walls - revised 7/21/2016 V 08 44 13 Aluminum Curtain Walls - revised 7/21/2016 V 08 51 13 Aluminum Windows - revised 7/21/2016 V 08 51 13 Aluminum Windows - revised 7/21/2016 V 08 51 13 Aluminum Windows - deleted & renumbered 7/21/2016 V 08 51 13 Aluminum Windows - deleted & renumbered 7/21/2016 General All Changed MnSCU to MINNESOTA STATE 10/5/2017 Intro.

4 NA Updated web link 10/5/2017 II Misc. Updated web links 10/5/2017 II Deleted Made in MINNESOTA Solar Program 10/5/2017 III Misc. Updated web links 10/5/2017 III Side lights in classrooms, labs, and offices 10/5/2017 IV Misc. Updated web links 10/5/2017 IV Revised freeze-thaw brick test frequency 10/5/2017 IV DIV05 Updated minimum dimensions for consistency 10/5/2017 IV DIV07 Flashings Added stainless steel as primary option 10/5/2017 IV DIV08 CW Added Sunscreen requirement 10/5/2017 IV DIV08 Reinstated tempered glass heat-soak testing requirement 10/5/2017 IV DIV14 Clarified requirement for cab size to accommodate stretcher 10/5/2017 IV DIV23 Added coded references 10/5/2017 IV DIV23 Added Underground Storage Tank requirements 10/5/2017 V 015800 Revised Temp. Project Sign for branding updates 10/5/2017 V 071300 Below grade waterproofing updated manufacturers 10/5/2017 V 085113 Windows Corrected air leakage std.

5 For operable windows 10/5/2017 V 085113 Windows - Misc. corrections 10/5/2017 Appendix 1 NA Added Zero Net to Curtain Wall products Revised manufacturers on multiple Sonoborn products 10/5/2017 Appendix 1 NA Added stainless steel through-wall flashing 10/5/2017 NA MINNESOTA STATE FACILITIES DESIGN STANDARDS 10/5/17 FACILITIES DESIGN STANDARDS i Preface ii Introduction I. DESIGN Philosophy 1. Mission 2. DESIGN Principles II. General Requirements 1. Owner Provided Information 2. Owner Reviews 3. Construction Contracts 4. Quality Assurance and Quality Control 5. Sustainable Building Guidelines 6. Products 7. Hazardous Materials 8. Site Property & Topographic Survey 9. Geotechnical Investigation 10. Utilities 11. Temporary FACILITIES 12. Estimated Construction Costs 13. Bid Contingency Plan 14. Revisions to the DESIGN STANDARDS III. Project Phase Requirements 1. Schematic DESIGN 2. DESIGN Development 3. Construction Documentation 4.

6 Bidding 5. Construction Administration IV. DESIGN STANDARDS V. Guideline Specifications VI. Appendices 1. Approved Product List 2. Definitions MnSCU FACILITIES DESIGN STANDARDS 07/31/17 i Preface MINNESOTA STATE Colleges and Universities (hereinafter MINNESOTA STATE ) is the fifth-largest system of higher education in the United states . It is comprised of 37 two-year and four-year STATE colleges and universities with 54 campuses located in 47 MINNESOTA communities. The System serves approximately 396,000 students and produces approximately 41,000 degrees, certificates and diplomas each year. FACILITIES range from those at the older, venerable STATE universities to the most modern at many sites. Each institution strives to maintain their collegiate ambiance so that students know they are attending an institution of higher learning. Each institution has a unique identity that expresses its history, mission and personality.

7 Whenever facility changes are made at a specific institution, that uniqueness should capture major landscape, historic and geographic features. Collectively we are short term stewards of our STATE s long-term higher education assets. Buildings and campus infrastructure shall be designed and built to last for many years. Decisions concerning these assets must be grounded in solid, long-range planning and execution to reach 50 years or more into the future. MnSCU FACILITIES DESIGN STANDARDS 6 7/31/2017 ii Introduction The FACILITIES DESIGN STANDARDS are intended to be used by architects, consultants, and campus FACILITIES personnel during the planning, DESIGN , and construction of new and remodeled buildings, and for maintenance of campus FACILITIES and infrastructure throughout the MINNESOTA STATE colleges and universities system. The purpose of these FACILITIES DESIGN STANDARDS is to communicate the basic minimum requirements to ensure that a project is complete, durable, easily maintained, safe, and compatible with existing and planned FACILITIES .

8 The information included contains procedures to be followed, materials to be used, or DESIGN STANDARDS which are deemed appropriate to assure the quality desired by MINNESOTA STATE now and into the future. FACILITIES personnel within the MINNESOTA STATE , as well as outside architects, consultants, and contractors should become familiar with these DESIGN STANDARDS . The FACILITIES DESIGN STANDARDS are divided into five sections. Section I. The Mission Statement and the DESIGN Principles. Section II. General DESIGN Requirements. Section III. Summarizes the DESIGN Phase Requirements where procedures and DESIGN phase submittal requirements are described for each phase from Schematic DESIGN to Construction Administration. Section IV establishes DESIGN STANDARDS and criteria for all work in the 49 divisions of the Construction Specifications Institute (CSI) MasterFormat 2014, where applicable to a specific project.

9 Section V contains sample specifications for some of the key divisions, which may applicable to a specific project. Not all divisions are included in this section. Section VI Appendices, includes approved manufacturer s product lists, definitions and a DESIGN STANDARDS Variance Request Form. In the future we hope to add examples of drawing details for building envelope DESIGN . The DESIGN team shall be responsible for producing designs that comply with the DESIGN STANDARDS in addition to all applicable codes, ordinances, statutes, regulations, and laws. If there is a conflict with any requirement in the DESIGN STANDARDS , the applicable building codes shall take precedence. The DESIGN STANDARDS are not intended to be used as the specifications for a particular project, but shall form the basis for creating the specifications. The use and inclusion of the DESIGN STANDARDS , specifications, or example drawing details as part of the Contract Documents does not relieve the DESIGN team of their responsibilities or legal liability for any Contract Documents they create.

10 All DESIGN and construction shall comply with the FACILITIES DESIGN STANDARDS herein. There may be instances where the DESIGN STANDARDS may not be appropriate for a particular situation or project. In this situation, a DESIGN variance is required. Any DESIGN variance from the DESIGN STANDARDS must be submitted for review as a formal written request from the DESIGN team to the system office Program Manager. DESIGN Standard variance request forms are available in the appendix or at , under 2. Project Phases, Schematic DESIGN , , DESIGN STANDARDS Variance Request Form. DESIGN variance requests should be made as early as possible, but no later than during the DESIGN Development phase. To request a DESIGN variance from the DESIGN STANDARDS , the following information should be included: MnSCU FACILITIES DESIGN STANDARDS 7 7/31/2017 Date, Project, College/University, Name of Requestor and contact information. Applicable DESIGN STANDARDS reference(s).