Transcription of Model DPL - SENSYS
1 Model DPLD ifferential Pressure Transmitter with Local IndicationDescriptionDPL Model is ideal for the application (such as HVAC) with differential pressure, vacuum pressure, gauge pressure and especially low pressure of non-corrosive gases or air measured. Analog output 4~20mA, 2wire and it provides LCD 3 1/2 digit LCD display 2 Wire 4~20mA analog output Measuring range 0~300Pa .. 100kPa diff. accuracy Piezoresistive silicon cell Use with non-corrosive, non-ionic mediaApplications Airflow Measurement Room Static Pressure VAV Box Lab/Fume Hood Control Clean Room ControlSpecificationsRange0~300, 500Pa / 1, 2, 5, 10, 20, 50, 100kPaPerformanceAccuracy 1digitThermal Effect on Zero CThermal Effect on Span CCompenated Temperature Range0 ~ 50 COperating Temperature Range-10 ~ 70 CElectricalDisplay 1999(3 1/2) Digit LCDE xitation14 ~ 28 VDCO utput4~20mA (2 Wire)Electrical ConnectionCable GlandPhysicalProof Pressure300%FS Pressure500%FS {5G}, 10~500 HzShock490m/s2{50G}Pressure Port1/8", 3/16" NippleMedia-Wetted MaterialsBrass(Ni plated), SiO2, Si RubberProtectionIP66 WeightApprox.
2 350gSENSOR SYSTEM TECHNOLOGY CO., : , Ansan Digital Park, 81, Neungan-ro, Danwon-gu, Ansan-si, Gyeonggi-do, KoreaTEL : 82-31-310-8910~9 FAX : 82-31-310-8920 : Specifications are subject to change without 2016 SENSOR SYSTEM TECHNOLOGY CO., LTD.(20161027)DimensionOrdering Information DPLH 0750 AModel NamePressure UnitA : PaR : kPaPressure RangeD : mmH2OC : cmH2OK : kgf/ H : mmHgB : barP : psiPin +Input +Earth -Output +