MODEL ESP-D SYSTEM INSTALLATION, …

SECTION 1: INTRODUCTIONS pacePak SYSTEM Distribution Distribution of 2: SYSTEM INSTALLATIONStep 1: Locating The 2: Cutting Return Air 3: Attaching Supply Air Plenum 4: Setting The 5: Connecting Refrigerant 6: Installing The Condensate Trap & 7: Wiring The 8: Installing Air Distribution 3: START UP & OPERATIONS equence Of To Start-Up & Cooling Only Affecting the Balance of the 4: MAINTENANCEB efore Each Cooling SYSTEM Fails To UNITED STATES: 260 NORTH ELM ST.

2 SPACEPAK SYSTEM DESIGN SpacePak is a hi-velocity central air conditioning system which utilizes a conventional outdoor condensing unit matched with the indoor Model ESP-D fan coil unit to

Tags:

  System, Model, Installation, Model esp d system installation, Model esp

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of MODEL ESP-D SYSTEM INSTALLATION, …

1 SECTION 1: INTRODUCTIONS pacePak SYSTEM Distribution Distribution of 2: SYSTEM INSTALLATIONStep 1: Locating The 2: Cutting Return Air 3: Attaching Supply Air Plenum 4: Setting The 5: Connecting Refrigerant 6: Installing The Condensate Trap & 7: Wiring The 8: Installing Air Distribution 3: START UP & OPERATIONS equence Of To Start-Up & Cooling Only Affecting the Balance of the 4: MAINTENANCEB efore Each Cooling SYSTEM Fails To UNITED STATES: 260 NORTH ELM ST.

2 WESTFIELD, MA 01085 (413) 564-5530/FAX (413) 564-5815IN CANADA: 7555 TRANMERE DRIVE, MISSISSAUGA, ONTARIO, L5S 1L4 (905) 672-2991/FAX (905) 672-2883 Central Air Conditioning Series2 to 5 TonsFan Coil Unit/Air SupplyComponentsMODELESP-D SYSTEMINSTALLATION,OPERATION& MAINTENANCEMANUAL ESPD2-1105W30-WG0133-022 SPACEPAK SYSTEM DESIGNS pacePak is a hi-velocity central air conditioning systemwhich utilizes a conventional outdoor condensing unitmatched with the indoor MODEL ESP-D fan coil unit to provide conditioned air through the specially-designed,pre-fabricated, pre-insulated flexible duct SYSTEM .

3 Thesystem and its basic components operate the same as inany conventional air-to-air cooling SpacePak SYSTEM is covered by the following :3,507,354;3,575,234;3,596,936;3,605,797 ; 3,685,329; 4,045,977; 4,698,982; 926,673and Canadian Patents: 891,292; 923,935; 923, COMPLIANCEFan coil unit installation must conform to the require-ments of the local authority having jurisdiction or, in theabsence of such requirements, to the National Board ofFire Underwriters regulations. Fan coil unit meets ETLlisting electrical wiring must be in accordance with theNational Electrical Code ANSI/NFPA No.

4 70-latest edition and any additional state or local code require-ments. If an external electrical source is utilized, the fancoil unit, when installed, must be electrically : It is a requirement of the InternationalMechanical Code ( ) to install a secondarydrain or an auxiliary drain pan where damage to anybuilding components will occur as a result ofoverflow from the equipment drain pan or stoppagein the condensate drain piping from a cooling or anevaporator DISTRIBUTION SYSTEM COMPONENTREQUIREMENTSAir distribution components installation must conform tothe requirements of local authority having jurisdiction or,in the absence of such requirements.

5 To the NationalFire Protection Association 90A or not begin the installation of the SYSTEM without asystem layout and material take-off. If a layout plan is notalready available and room terminator requirementsdetermined, then refer to the SpacePak ApplicationManual, SP9, to complete this information. A descriptionof air distribution SYSTEM components is shown in Figure 1: INTRODUCTION The following terms are used throughout this manual to bring attention to the presence of potentialhazards or to important information concerning theproduct.

6 Indicates an imminently hazardoussituation which, if not avoided, will result in death,serious injury or substantial property an imminently hazardoussituation which, if not avoided, could result indeath, serious injury or substantial property an imminently hazardous situation which, if not avoided, may result in minor injury or property : Used to notify of special instructions oninstallation, operation or maintenance which areimportant to equipment but not related to personal injury AIR DUCTCLAMP BANDRETURN AIR BOXPLENUM DUCTFAN COIL UNITPLENUM CAPPLENUM TEEPLENUM TAKEOFFKWIK CONNECTSSOUND ATTENUATING TUBINGTERMINATOR PLATESORIFICERIGID 90 ELBOW3 installation KIT COMPONENTST erminator plateswith clips and screwsSound Attenuating tube w/ kwik-connects installed Kwik-connects,Plenum Take-offs,clips and gaskets.

7 15%, 35% and 50% balancing orificesRETURN AIR BOX (SPC-1D, AC-RBF-3, SPC-3D):Each includes filter grill with metal frame, permanent filter, and 2 clamp bands. SPC-1D is for is for ESP-3642D and SPC-3D is for AIR DUCT (SPC-4,5, & 6): Flexible, 10 feetlong with round shape. SPC-4 (15" dia.) for (19" dia.) for ESP-3642D and SPC-6 (24" dia.) isfor DUCT & COMPONENTS:May be round orsquare, fiberboard or sheet metal duct types as speci-fied by the installing contractor. Above layout is shownas an illustrative reference TUBING (SPC-25-100):Flexible, insulated, 2" and 3 1 4" Each section is 100 feet SUPPLY TUBING (AC-ST8-50):Flexible, R8 insulated,2" and 6-1/4" Each section is 50 feet KITS:Each contains a specifiedamount of sound attenuating tubes, kwik-connects,plenum take-offs, terminator plates, winter supply airshut-offs and balancing orifices to complete installationof room COMPONENTS (not shown)WINTER SUPPLY SHUT OFF (SPC-42-10).

8 To keepmoisture from collecting in ductwork during CONNECT WALL ELBOW (AC-KCWE):To allowfor wall terminations in 2" X 4" stud (SPC-72):To assure full setting of all clips (fasteners) in plenum DRAIN PAN:Specifically sized forSpacePak horizontal fan coil units. Constructed ofdurable polyethylene. Fan coil unit sets directly on topand can be installed with threaded : AIR DISTRIBUTION SYSTEM COMPONENTS4 Plenum DuctThe plenum duct can be run in practically any locationaccessible for the attachment of the supply tubing (seesuggested layouts in Figure ).

9 The plenum is normallylocated in the attic or basement, and it is usually moreeconomical to run the plenum where it will appreciablyshorten the lengths of two or more supply some two-story split level homes, it may be advanta-geous to go from one level to another with the plenumduct. Whenever necessary, either between floors or alongthe ceiling, the small size of the plenum makes it easy to box ESP- 4860 ONLYPLENUMFAN COILUNITPLENUMFAN COILUNITPLENUMFAN COILUNITPLENUMFAN COILUNITFIGURE : PLENUM/TUBING LAYOUT EXAMPLES (FOR GUIDANCE ONLY)The fan coil unit is designed to operate with a total exter-nal static pressure of inches of water column (mini-mum - maximum ).

10 Excessive static pressureincreases the air flow in individual runs and may causesome or all terminators to be systems with a tee installed as on Unit No. 1 ( ), the best results are obtained if not more than60% of the total number of SYSTEM outlets are attached to any one branch of the tee. For systems with a teeinstalled as on Unit No. 2 ( ), not more than 30% of the total number of SYSTEM outlets should beattached to the perpendicular branch of the larger SYSTEM capacities (ESP-4860D) are effectedmore by higher SYSTEM static pressure than the smallersystems.