Example: dental hygienist

MULTIRANGER PLUS - PRTS

33455130 Rev. PLUSI nstruction Manual PL-513 January 2001 MULTIRANGER plus Siemens Milltronics Process Instruments Inc. 2001 Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of others, and toprotect the product and the connected equipment. These warning notices are accompaniedby a clarification of the level of caution to be PersonnelThis device/system may only be set up and operated in conjunction with this personnel are only authorized to install and operate this equipment in accordancewith established safety practices and : This product can only function properly and safely if it is correctly transported,stored, installed, set up, operated, and : Always use product in accordance with Siemens Milltronics ProcessInstruments Inc.

Table of Contents General Information About This Manual 7 About the MultiRanger Plus 7 Specifications MultiRanger Plus 9 Programmer 10 Transducer 10

Tags:

  Plus, Multiranger plus, Multiranger

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of MULTIRANGER PLUS - PRTS

1 33455130 Rev. PLUSI nstruction Manual PL-513 January 2001 MULTIRANGER plus Siemens Milltronics Process Instruments Inc. 2001 Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of others, and toprotect the product and the connected equipment. These warning notices are accompaniedby a clarification of the level of caution to be PersonnelThis device/system may only be set up and operated in conjunction with this personnel are only authorized to install and operate this equipment in accordancewith established safety practices and : This product can only function properly and safely if it is correctly transported,stored, installed, set up, operated, and : Always use product in accordance with Siemens Milltronics ProcessInstruments Inc.

2 2000. All Rights ReservedDisclaimer of LiabilityThis document is available in bound version and inelectronic version. We encourage users topurchase authorized bound manuals, or to viewelectronic versions as designed and authored bySiemens Milltronics Process Instruments Milltronics Process Instruments Inc. willnot be responsible for the contents of partial orwhole reproductions of either bound or we have verified the contents ofthis manual for agreement with theinstrumentation described, variationsremain possible. Thus we cannotguarantee full agreement. Thecontents of this manual are regularlyreviewed and corrections are includedin subsequent editions. We welcomeall suggestions for data subject to is a registered trademark of Siemens Milltronics Process Instruments SMPI Technical Publications at the following address:Technical PublicationsSiemens Milltronics Process Instruments Technology Drive, Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: the library of SMPI instruction manuals, visit our Web site.

3 Of ContentsGeneral InformationAbout This Manual7 About the MULTIRANGER Plus7 SpecificationsMultiRanger Plus9 Programmer10 Transducer10 Temperature Sensor10 Current Output Isolator 10 Cabling 10 InstallationMultiranger Plus11 Outline and Mounting11 Circuit Board Layout12 Recommendations13 Interconnection14 System Diagram14 Installing the Transducer14 Selecting Temperature Source15 Current Output15 Current Output Isolator16 Synchronization17 Power Connections18 Programmer19 Start UpGeneral21 Programmer Keypad Run Mode22 Program Mode23 Legend24 Parameter Entry24PL-5133 Common Display Messages26 FunctionalTransceiver27 Damping and Process Rate27 Temperature Compensation28 Sound Velocity28 Blanking29 Agitator Discrimination30 RelaysGeneral30 Function Alarm31 Pump32 Miscellaneous33 Analog Output36 Applications37 Simple Level Application 39 Pump Control Applications 41 Pump Run-On44 Pump Totalizer Application47 Volume Application 50 Common Tank Shapes51 Custom Design Tanks52 Compensation55 Differential Level Application59 OCM Applications63 Single Exponential 69 Palmer-Bowlus73H Flumes74 Other 75 Applications with Standpipes78PL-5134 Parameter DescriptionParameters79 TroubleshootingGeneral105 Oscilloscope105 Troubleshooting Guide107 Maintenance Maintenance111 AppendicesSound Velocities113 Glossary114 Alphabetical Parameter Listing116PL-5135PL-5136 GENERAL INFORMATIONABOUT THIS MANUALF irst

4 And foremost it is essential that this manual be read and understood beforeinstallation and start up of the MULTIRANGER plus . As the MULTIRANGER plus requires anultrasonic transducer to make a working system, refer to the associated transducermanual as well."Applications" provides a general description of the common applications found inindustry and illustrates them with examples. It is suggested that you refer to thesub-section which most suits your application. The programming of the MultiRangerPlus can be optimized by referring to Parameter Description or Appendices \Alphabetical Parameter THE MULTIRANGER PLUSThe MULTIRANGER plus is to be used only in the manner outlined in this instruction MULTIRANGER plus is a multi-purpose liquid level monitoring device used inconjunction with an ultrasonic MULTIRANGER plus emits an ultrasonic pulse via the transducer.

5 The echo isreflected from the material and received by the transducer. The echo is processed bythe MULTIRANGER plus and the time at which the ultrasonic pulse hits the level or targetis extracted and compared to the time at which it was sent. The time differential isthen converted into distance, material level, volume, flow or differential level as abasis for display, relay control, analog output and well as simple level measurement, the MULTIRANGER plus was designed to handlespecific applications such as: pumped volume totaling, differential level and openchannel flow PLUSP ower: 100/115/200/230 V ac 15%, 50/60 Hz, 15 VA optional: 12 V dc model, 10 to 15 V dc, 15W 24 V dc model, 18 to 30 V dc, 15W fuse FU2, Belling Lee, L754, 4000A HRC, ceramic type, 50mA, 250V FU3, Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250 VEnvironment: location: indoor / outdoor altitude: 2000 m max ambient temp.

6 : 20 to 50 C relative humidity: suitable for outdoor(Type 4X/NEMA 4X/IP65 enclosure) installation category: II pollution degree: 4 Range: to 15 m (1 to 50 ft)Accuracy: of range or 6 mm ( "), whichever is greaterResolution: of range or 2 mm ( "), whichever is greaterMemory: EEPROM (non-volatile) no back-up battery requiredDisplay: Liquid Crystal Display of 4 digits, 18mm ( ") highOutputs:transducer drive: 41 KHz, 400 V peak pulses of 1 msecmax duration at a max repetition rate of 300 msecanalog: 0 - 20 or 4 - 20 mA max loading: 350 ohms, return to ground 750 ohms, return to 12 V resolution: of range optional mA isolatorrelays: 5 multipurpose relays (for alarms, pump control,..) 1 Form "C" SPDT contact per relay, rated 5 A at 250 V ac non-inductive adjustable deadbandAll relays are certified for use in equipment where the short circuit capacity of the circuits in which they are connected is limited by fuses having ratings not exceeding the rating of the : Type 4X / NEMA 4X / IP65 160 mm W x 250 mm H x 82 mm D( " W x "H x "D) polycarbonate98\06\15PL-5139 Approvals: CE*, FM, CSA NRTL/C* EMC performance available upon kg (4lb)PROGRAMMERE nclosure: general purpose 67 mm W x 100 mm H x 25mm D( " W x 4" H x 1" D) ABS plasticOperating Temperature: 20 to 50 C ( 5 to 122 F)Power:9 V battery (style - ANSI/NEDA 1604)TRANSDUCERC ompatible Models.

7 ST-H and Echomax models XPS-10/10F, XPS-15/15F, XCT-8, XCT-12 and XRS-5 Refer to associated Transducer SENSORR efer to associated Temperature Sensor manualCURRENT OUTPUT ISOLATOR (Optional)Model: LIs-1 loop isolatorInput: 4 - 20 mA dc (from MULTIRANGER plus )Output: 4 - 20 mA dc into 600 ohm maxCABLINGO ptional: RG-62A/U coax max distance to electronics: 365 m (1200 ft) must be run in grounded metal conduitTemperature Sensor: Belden 8760, 2 wire shielded max distance to electronics: 365 m (1200 ft) can be run with transducer cablePL-51310 INSTALLATIONI nstallation shall only be performed by qualified personneland in accordance with local governing PLUSThe MULTIRANGER plus should be mounted in an area that is within the unit s ambienttemperature range, and is suitable for the specified enclosure.

8 The front cover shouldbe accessible for programming and is advisable to keep the MULTIRANGER plus away from high voltage or current runs,contactors and SCR control product is susceptible to electrostatic proper grounding mm( ")131 mm( ")lid screws(6 places)97 mm( ")82 mm( ")240 mm( ")programmer228 mm(9")Suitable location for conduit recommends using a punch for making holes in mountingscrewmounting holes(accessed under mm ( ") dia. 4 placesOUTLINE AND MOUNTINGNon metallic enclosure does not provide grounding between conduitconnections. Use grounding type bushings and isolatordaughter boardmotherboard10 to 15V dc operation12 V dc model18 to 30V dc operation 24 V dc modelCIRCUIT BOARD LAYOUTR elay contact terminals are for use with equipment having no accessiblelive parts and wiring having insulation suitable for at least 250 maximum allowable working voltage between adjacent relay contacts shall be 250 voltage present on transducer terminals during terminals shall be supplied from an SELV source in accordance with IEC 1010-1 Annex field wiring must have insulation suitable for at least 250 mA output, N12, sync, temp sensor circuits (ter.))

9 1-7), 14-20 Awg., copper wire,shielded- Trans circuit (ter. 8-9), Coaxial cable RG - 62 A/U- Relays, AC input circuit (ter. 10-28), 12-14 Awg., copper- dc input (ter. 27-28), 14-20 Awg., copper wire, shieldedRecommended torque on terminal clamping screws, 5-7 ( Nm).98\06\15drill for 1/2"conduit hubs(2 places) " " " " " "drill for 3/4"conduit hub(1 only)PL-51313 INTERCONNECTIONSYSTEM DIAGRAMM aximum system capability. Not all components or their maximum quantity may be THE TRANSDUCERR efer to transducer manual for wiring detailsBasic Wiringblackwhite /shieldDifferential Level - Basic Wiringtransducer#2transducer#1white /shieldblackwhite /shieldMultiRanger PluscustomerdeviceMilltronics TS-3,temperature sensor(optional)Milltronicstransducer,se eSpecificationscustomer alarm,pump or controldevicemA outputrelay outputPL-51314 SELECTING TEMPERATURE SOURCECURRENT OUTPUT to customer s equipmentmaximum loading 350 mA Output - GROUNDED(additional to basic wiring)Note : TB1-2 is internally connected to electrical ground Output - FLOATING (additional to basic wiring)mA output wiring into floating input ONLY.

10 750 max. Do Not Ground!board B Transducer with built-intemperature sensorTS-3 or Programboard B Note: If TRANS is selected butthe transducer does not have abuilt-in temperature sensor,then CAbL/LOE will flash whenthe unit is in run mode. (For example, an ST 25 or ST 50transducer requires a setting ofTS/P65)06/28/99PL-51315 CURRENT OUTPUT ISOLATORIf the isolator has not been factory installed, mount it on the upper left hand corner ofthe motherboard using the two long machine screws provided. The input terminals ofthe isolator are then connected to the motherboard output terminals,TB-1, usingtwisted pair maximum 16 gauge shielding and grounding are required in order to minimize noise levels thatcould otherwise affect weak receiver signals by introducing false isolator enclosure is grounded by the mounting bolts to the motherboard.


Related search queries