SITRANS F M MAGFLO - PRTS

ManualOrder no.: - A5E00253213*083R9141* SITRANS F M MAGFLO Electromagnetic flowmetersSignal converter types MAG 5000, MAG 6000[]sSITRANS F M MAGFLO outputCurrent0-20 mA, 4-20 mA or 4-20 mA + alarmLoad< 800 ohmTime s adjustableDigital outputFrequency0-10 kHz, 50% duty cycleTime s adjustableActive24 V , 30 mA, 1 K Rload 10 K , short-circuit-protectedPassive3-30 V , max. 110 mA, 200 Rload 10 K RelayTime constantChangeover relay, time constant same as current time constantLoad42 V A, 24 V input11-30 V , Ri = K Activation time50 msCurrentI11 V = mA, I30 V = 7 mAFunctionsFlow rate, 2 totalizers, low flow cut-off, empty pipe cut-off, flow direction, error system, operating time,uni/bidirectional flow, limit switches, pulse output, control for cleaning unit and batch2)Galvanic isolationAll inputs and outputs are galvanically isolatedCut-offLow of maximum flowEmpty pipeDetection of empty pipe1)TotalizerTwo eight-digit counters for forward, net or reverse flowDisplayBackground illumination with alphanumerical text, 3 20 characters to indicate flow rate, totalizedvalues, settings and faultsReverse flow indicated

SITRANS F M MAGFLO 4 DKFD.PS.027.Z4.02 2.1 Signal converter MAG 5000 & MAG 6000 connection diagram Grounding PE must be connected due to safety class 1 …

Tags:

  Strain, Magflo, Sitrans f m magflo

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SITRANS F M MAGFLO - PRTS

1 ManualOrder no.: - A5E00253213*083R9141* SITRANS F M MAGFLO Electromagnetic flowmetersSignal converter types MAG 5000, MAG 6000[]sSITRANS F M MAGFLO outputCurrent0-20 mA, 4-20 mA or 4-20 mA + alarmLoad< 800 ohmTime s adjustableDigital outputFrequency0-10 kHz, 50% duty cycleTime s adjustableActive24 V , 30 mA, 1 K Rload 10 K , short-circuit-protectedPassive3-30 V , max. 110 mA, 200 Rload 10 K RelayTime constantChangeover relay, time constant same as current time constantLoad42 V A, 24 V input11-30 V , Ri = K Activation time50 msCurrentI11 V = mA, I30 V = 7 mAFunctionsFlow rate, 2 totalizers, low flow cut-off, empty pipe cut-off, flow direction, error system, operating time,uni/bidirectional flow, limit switches, pulse output, control for cleaning unit and batch2)Galvanic isolationAll inputs and outputs are galvanically isolatedCut-offLow of maximum flowEmpty pipeDetection of empty pipe1)

2 TotalizerTwo eight-digit counters for forward, net or reverse flowDisplayBackground illumination with alphanumerical text, 3 20 characters to indicate flow rate, totalizedvalues, settings and faultsReverse flow indicated by negative signTime constantTime constant as current output time constantZero point adjustmentAutomaticElectrode input impedance> 1 x 1014 Excitation frequencySensor size depending pulsating current (125 mA)Ambient temperatureDisplay version during operation: 20 to +50 CBlind version during operation: 20 to +60 CDuring storage: 40 to +70 C (RH max. 95%)Custody transfer approvalPTB DANAK OIML R752)DANAK OIML R1172)(cold water)(hot water)(cold water/milk, beer etc.)CommunicationStandardPrepared for client mounted add-on modules2)OptionalHART, Profibus PA, Profibus DP, CANopen, DeviceNet as add-on module2), HART (MAG 5000)CompactEnclosure materialFibre glass-reinforced polyamideEnclosure ratingIP 67 to EN 60529 and DIN 40050 (1 m for 30 minutes)Mechanicalload18-1000 Hz random, G rms in all directions to EN 60068-2-3619" insertEnclosure materialStandard 19" insert of aluminium/steel (DIN 41494)Width: 21 TEHeight: 3 HEEnclosure ratingIP 20 to EN 60529 and DIN 40050 Mechanical loadVersion: 1 G, 1-800 Hz sinusoidal in all directions to EN 60068-2-36 EMC performanceEmission: EN 50081-1 (Light industry)Immunity: EN 50082-2 (Industry)Supply voltage115-230 V +10% to 15%, 50-60 Hz11-30 V or 11-24 V consumption230 V.

3 9 VA24 V : 9 W, IN = 380 mA, IST = 8A (30 ms)12 V : 11 W, IN = 920 mA, IST = 4A (250 ms) Signal converter type MAG 5000 & MAG 6000 MAG 5000 accuracy 6000 accuracy ) Special cable required in separate mounted installation2) MAG 6000 only1. Technical dataSITRANS F M MAGFLO characteristicsBidirectional modeUnidirectional mode0-20 mA4-20 mAFrequencyPulse outputRelayPower downActiveError relayNo errorErrorLimit switch or1 set point2 set pointsdirection switchLow flowIntermediate flow(Reverse flow)High flowHigh flow/(Forward flow)Low flowBatch on digitaloutput(MAG 6000 only)Batch on relayHoldBatch(MAG 6000 only) characteris-tics MAG 5000 &MAG Sensor cables andconductivity Minimum acceptdata for cableCoil cableElectrode cableBasic dataNo.

4 Of conductors23 Min. sqr. mm2 ScreenYesYesMax. pF/mMax. cable loopMedia temperature:< 100 C40 < 200 C6 ofCompact installation: Liquids with an electrical conductivity 5 a conductivity between 5 and 10 S/cm, the repeatability may degrade to of actual :NoteFor detection of empty sensor the min. conductivity must always be 20 S/cm and the of electrode cable when remote mounted is 50 metres. Special cable must be remote mounting in Ex applications special cable cannot be used, empty sensor cannotbe detected and the electrically conductivity must be 30 remote mounted CT installations the max. cable length is 200 cableSpecial cable1. Technical dataSITRANS F M MAGFLO Signal converter MAG5000 & MAG 6000connection diagramGroundingPE must be connected due to safety class 1 power countersWhen mounting a mechanical counter to terminals 57 and 58 (active output), a 1000 F capacitormust be connected to the terminals 56 and + is connected to terminal 56 and capacitor to terminal cablesIf long cables in noise environment, we recommend to use screened cablesDotted connections only to be when using special electrode cable with indi-vidual wire shields (shownas dotted lines) are onlyrequried when using emptypipe function or longcables.

5 (See Technical data chapter 2 in the handbookfor further details.)2. Electrical connectionSITRANS F M MAGFLO Compact installationMAG 5000 & MAG 6000- Compact polyamideStep 1 Remove and discard the terminal box lid of the PG cable glands for the supply andoutput 2 Remove the two black plug assemblies for coiland electrode cables in the terminal box andconnect them to their corresponding terminalnumbers on the connection 3 Connect an earth wire between PE on connec-tion board and bottom of connection the 2 pin connector and 3 pin connectoras earlier version the 3 pin connector was a 5pin 4 Mount the connection plate in the terminal SENSORPROM unit connections will beestablished automatically when the connectionplate is mounted in the terminal that your connection board lines up withthe SENSORPROM unit.

6 If not, move theSENSORPROM unit to the other side of theterminal 5 Fit the supply and output cables respectivelyand tighten the cable glands to obtain refer to the wiring diagram in chapter 7 Electrical connections in the the signal converter on the will not registerflow if black plugs are notconnected to connectionboard3. Installation of signal converterSITRANS F M MAGFLO Remote installation -At the sensorFit and connect the electrode and coil cablesas shown in chapter 7 Electrical connections in the unscreened cable ends must be kept asshort as electrode cable and the coil cable must bekept separate to prevent the cable glands well to obtain opti-mum the SENSORPROM unit from thesensor and mount it on the connection plate inthe signal Remote installation -Wall mountingconverterMount wall bracket on a wall or on a pipe usingordinary hose clips or duct the SENSORPROM memory unit fromthe sensor.

7 Mount the SENSORPROM unit inthe wall mounting unit as shown. The text onthe SENSORPROM unit must face towardsthe wall an earth wire between PE on connectionboard and bottom of connection Installation of signal converterSITRANS F M MAGFLO Remote installation -Wall mountingconverter (continued)Mount the connection plate in the terminal the connection plate with the two diagonalopposite the coil, electrode, supply and output cablesrespectively and tighten the cable glands toobtain optimum sealing. Please see the wiringdiagram in chapter 7 Electrical connections inthe the signal converter on the terminal Remote installation -Signal converter in19" insert1. Fit the SENSORPROM memory unit on the connection board supplied with the signalconverter.

8 The SENSORPROM unit is supplied with the sensor in the terminal Mount the guide rails into the rack system as shown. Distance between guide rails is 20 rails are supplied with the rack system and not with the signal Mount the connection board as Connect the cables as shown under "Electrical connection", chapter 7 in the handbook .5. Insert the signal converter into the rack Installation of signal converterSITRANS F M MAGFLO 5000 & MAG 6000 4. CommissioningSITRANS F M MAGFLO 4. 5000 & MAG 6000 (continued) SITRANS F M MAGFLO modeBasic settingsOperator activeService modeOutputOperator inactiveOperator menuExternal inputProduct identitySensor characteristicsLanguage modeReset Keypad and displaylayoutKeypadThe keypad is used to set the flowmeter.

9 The function of the keys is as follows:TOP UP KEYThis key (hold 2 sec.) is used to switch between operator menuand setup menu. In the converter setup menu, a short press willcause a return to the previous KEYThis key is used to step forward through the menus. It is the onlykey normally used by the KEYThis key is used to step backward through the KEYThis key changes the settings or numerical KEYThis key selects the figures to be KEYThis key allows the operator to change settings and gives accessto display is alphanumerical and indicates flow values, flowmeter settings and error upper line is for primary flow readings and will always show either flow rate, totalizer 1 or totalizer2. The line is divided into 3 : Sign fieldP: Primary field for numerical valueU: Unit fieldThe centre line is the title line (T) with individual information according to the selected operatoror setup lowest line is the subtitle line (ST) which either will add information to the title line or keepindividual information independent of the title : The alarm field.

10 Two flashing triangles will appear by a fault : The mode field. The symbols indicate the for changeAccess to submenuValue lockedRESET MODE: Zero setting oftotalizers and initialization of settingL: The lock field. Indicates the function of the lock CommissioningSITRANS F M MAGFLO Basic settingsComma for flow rate, totalizer 1 and totalizer 2 can be individually positioned. open the respective window. ensure that the cursor is positioned below the comma. Use the SELECT KEY . move the comma to the requested position. Use the CHANGE KEY .Units are changed by means of the CHANGE KEY with the cursor placed below the unitselected. Select units (cursor moved) by means of the SELECT KEY .Totalizer 2 is not visible when batch is selected as digital 2 - is only visible when it has been choosen as external frequencyTo select the main power supply frequency correspondingto the country in which the flowmeter is installed.