Transcription of Okonite-FMR Okoseal
1 ABEDCI nsulationOkonite-FMR is Okonite s trade name for itsheat, moisture, flame and chemical resistant,mechanically rugged ethylene-propylene in-sulating properties of Okonite-FMR insulationsubstantially enhance the well known fea-tures of ethylene-propylene rubber JacketThe Okoseal (PVC) jacket is mechanicallyrugged and has excellent resistance to Okoseal Type TC-ER tray ca-ble is permitted for use on power, lighting,control, and signal circuits; indoors or out-doors; in cable trays, raceways, direct burialin the ground, or where supported in outdoorlocations by a messenger wire; for Class 1circuits as permitted in Article 725 of theNEC; and in cable trays in ClassI, Division 2hazardous locations in industrial establish-ments where the conditions of maintenanceand supervision assure that only qualifiedpersons will service the installation.
2 Cablesmarked TC-ER may also be used between acable tray and the utilization equipment ordevice, when installed in accordance withNEC (7).As Type Oko-Marine cable, it is suitable foruse in marine shipboard and off-shore plat-form applications in accordance with API andABS :Uncoated soft copper perASTM B-3. Sizes smaller than #8 are com-press stranded per ASTM B-8. Sizes #8 andlarger are compact stranded per : Okonite-FMR meets or exceedsrequirements of UL 1581, ICEA S-73-532(NEMA WC57) and ICEA S-95-658 NEMAWC70 Coding:Base colors and tracers asshown on reverse of Data Sheet and forsizes #8 AWG and larger black conductorswith surface printing of numbers per ICEAS-73-532 NEMA/WC57 Method Conductor:Where indicated,bare stranded copper per ASTM B-8, orcompact round per ASTM B-496, Class B &NEC Table :Conductors cabled in accor-dance with UL 1277 and 1309 using fill-ers, as necessary, with a cable Jacket:Complies with UL 1277and 1309.
3 The Okoseal compound meetsor exceeds the requirements of UL Listed as Type TC or TC-ER cablewith a sunlight resistant low temperaturejacket and for direct burial and TypeOko-Marine 4 AWG and larger without agrounding conductor are Type TC only(not ER).Product FeaturesInsulated conductors are UL ratedXHH/XHHW-2, cUL rated RW75/RW90,VW-1, PR I, and -40 C continuous rating in wet or drylocations130 C emergency overload rating250 C short circuit Okoseal Type TC-ER andOko-Marine cables are quality control in-spected to meet or exceed applicable in-dustry to moisture and most stability at elevated , easy to install and dielectric Temperature -40 Standards UL listed for cable tray use, directburial, in ducts, and sunlight resistant.
4 Vertical Tray Flame Tests;IEEE 383-1974, FT4/IEEE 1202, UL1277, Sizes 250 kcmil and larger meetICEA T-29-520 (210,000 BTU/hr). OSHA Acceptable UL 1309-Oko-Marine UL certified to IEEE 1580 - MarineShipboard Cable rated 600/1000V. ABS Type approved; API-RP-14F,IEEE 1202, 46 CFR CSA No. 239 Type CIC for sizes4/0 AWG and smaller. CSA No. 230 Type TC-ER forsizes 14 through 4/0 AWG. 1000V CSA Type CIC available forsizes 4/0 AWG and Okoseal UL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600/1000V Power & ControlTray CableMultiple copper Conductors With or WithoutGrounding Conductor/90 C Wet or Dry600/1000V Marine Shipboard CableFor Cable Tray Use - Sunlight Resistant - For Direct BurialProduct DataSection 4: Sheet 5 AStranded copper ConductorsBOkonite-FMR InsulationCFillers, as necessaryDBinder TapeEOkoseal Jacket BlackULRAWG CU Okonite-FMR PVC 600/1000 VcULRUL TYPE.
5 TC-ERs202-10-3203s202-10-320414(7X)3430 (7X)3330 12* *10(7X)3345530 10* 's web site, contains the most up to date Okoseal UL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600/1000V Power & Control Tray CableMultiple copper Conductors With or WithoutGrounding Conductor/90 C Wet or Dry600/1000V Marine Shipboard CableFor Cable Tray Use - Sunlight Resistant - for Direct BurialProduct DataSection 4: Sheet 5sAuthorized stock item Available from our Service Grounding Conductor: Any conductor in these cables may be per-manently re-identified during installation as the equipment grounding conductorin accordance with Section (B) of the NEC. Cross-sectionalarea for calculation of cable tray fill in accordance with Sec-tion of the NEC.
6 *Method 4 Color Code(1) AmpacitiesAmpacities are based on Table of the National Electrical Code for con-ductors rated 90 C, in a multi-conductor cable, at an ambient temperature of30 C (86 F). The 75 C column is provided for additional ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within the cable is in accor-dance with NEC Section (C)(1).The ampacities shown also apply to cables installed in cable tray in accordancewith NEC Section SizeAWG/kcmilNumber of ConductorsGrounding Conductor AWGC atalog NumberJacket Thickness (mils)90 C Wet or DryNEC Ampacity (1)*Jacket Thickness (mm)Cross-SectionalArea (sq.)
7 In.)=Approx. (In.)Approx. Net Approx. Ship Approx. (mm)Insulation Thickness (mils)cULR75 C WetNEC Ampacity (1)**Current limited to 15, 20 and 30 amps per Section (D) of the NEC for #14, #12 and #10 AWG, (7X)TC-ER334445 10* 10* (7X)TC-ER334445 8* 8* (7X)TCTC-ERTCTC-ER334445 8* 8* (7X)TCTC-ERTCTC-ER334445 6 (19X)TCTC-ERTCTC-ER334455 6 (19X)TCTC-ERTCTC-ER334455 6 (19X)TCTC-ERTCTC-ER334455 6 (19X)TCTC-ERTCTC-ER334455 4 2462257632063320260527193383349726026020 8208230230184184112-10-3928112-10-392911 2-10-3930112-10-3931250(37X)TCTC-ERTCTC- ER334465 4 2904302938934000304732064159426529029023 2232255255204204112-10-3932s112-10-39331 12-10-3934112-10-3935350(37X)TCTC-ERTCTC -ER334465 3 3995416452435394426144305590574135035028 0280310310248248112-10-3936s112-10-39371 12-10-3938112-10-3939500(37X)TCTC-ERTCTC -ER334465 2 5549574372377425593961337796798443043034 4344380380304304112-10-3940112-10-394111 2-10-3942112-10-3943750(61X)TCTC-ERTCTC- ER334480 1 8277851510942111578904914211704119195355 35428428475475380380112-10-3944112-10-39 45112-10-3946112-10-39471000(61X)TCTC-ER TCTC-ER334480 1/0 1 1095311237143371463211715120001527015565 615615492492545545436436 Note: Sizes 4 AWG & larger without a grounding conductor are type TC only (not ER rated).
8 *Ground size marked with asterisk are green insulated. **Grounds may be 's web site, contains the most up to date DataSection 4: Sheet 5 Approx. Net 75 C Wet NECA mpacity (1)90 C Wet or DryNEC Ampacity (1)Approx. Ship Conductor SizeAWG/kcmilNumber of ConductorsGrounding Conductor AWG**UL TC TYPEJ acket Thickness (mils)Jacket Thickness (mm)Insulation Thickness (mils)Cross-SectionalArea (sq. In.)=Approx. (In.)Approx. (mm)Catalog NumberOkonite-FMR OkosealUL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600/1000V Power & Control Tray CableMultiple copper Conductors With or WithoutGrounding Conductor/ 90 C Wet or Dry600/1000V Marine Shipboard CableFor Cable Tray Use - Sunlight Resistant - For Direct BurialConductor Color Coding SequenceSizes 14, 12 & 10 AWGC onductorColor Coding per ICEA Method 1,NumberBase ColorTracer ColorE-2 (except 202-10-3505 - Method 4)1 BlackSizes 8 AWG and larger.
9 2 RedSurface Printing of Numbers per3 BlueICEA Method 44 Orange5 Yellow6 Brown7 RedBlack8 BlueBlack9 OrangeBlack10 YellowBlack11 BrownBlack12 BlackRed13 BlueRed14 OrangeRed15 YellowRed16 BrownRed17 BlackBlue18 RedBlue19 OrangeBlue20 YellowBlue21 BrownBlue22 BlackOrange23 RedOrange24 BlueOrange25 YellowOrange26 BrownOrange27 BlackYellow28 RedYellow29 BlueYellow30 OrangeYellow31 BrownYellow32 BlackBrown33 RedBrown34 BlueBrown35 OrangeBrown36 YellowBrown37 BlackSpecial Order:Any or all of the following conductors may be added when specifi-cally requested by the customer to meet their specific application conductor codings comply with UL and NEC ColorTracer ColorEquipment GroundingUninsulatedGreenGreen1 or more continuous yellow stripesGroundedWhiteWhiteWhiteWhiteWhite WhiteWhiteBlack continuous stripeRed continuous stripeBlue continuous stripeOrange continuous stripeBrown continuous stripeNumeric PrintingV/22070405 Product DataSection 4: Sheet 5 ULRTHE OKONITE COMPANYR amsey,NewJersey07446cULR