Example: confidence

On-Line Partial Discharge Testing - WMEA

OnOn-- line Partial line Partial Discharge TestingDischarge TestingSkip HicksDirector -New Business DevelopmentWhat Is Partial Discharge ?What Is Partial Discharge ?What Is Partial Discharge ?zAccording the the International ElectrotechnicalCommission (IEC) International Standard 60270, Section published in 2000, the definition of Partial Discharge is: Localized electrical Discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor. IEC 60270 Section NotesIEC 60270 Section NotesIEC 60270 Section Notesz Partial discharges are in general a consequence of local electrical stress concentrations in the insulation or on the surface of the z Corona is a form of Partial Discharge that occurs in gaseous

On-Line Partial . Discharge Testing. Skip Hicks. Director - New Business Development

Tags:

  Testing, Discharge, Line, Partial, On line partial discharge testing, On line partial, Discharge testing

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of On-Line Partial Discharge Testing - WMEA

1 OnOn-- line Partial line Partial Discharge TestingDischarge TestingSkip HicksDirector -New Business DevelopmentWhat Is Partial Discharge ?What Is Partial Discharge ?What Is Partial Discharge ?zAccording the the International ElectrotechnicalCommission (IEC) International Standard 60270, Section published in 2000, the definition of Partial Discharge is: Localized electrical Discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor. IEC 60270 Section NotesIEC 60270 Section NotesIEC 60270 Section Notesz Partial discharges are in general a consequence of local electrical stress concentrations in the insulation or on the surface of the z Corona is a form of Partial Discharge that occurs in gaseous media around conductors which are remote from solid or liquid z Partial discharges are often accompanied by emission of sound, light, heat.

2 And chemical Paper-Insulated Lead CablePaperPaper--Insulated Lead CableInsulated Lead CableExtruded MV Cable ConstructionExtruded MV Cable ConstructionExtruded MV Cable ConstructionEPR Cable ConstructionEPR Cable ConstructionEPR Cable ConstructionJacket____Jacket____SC*_____ SC*_____Strand Screen_*Strand Screen_*__Shield__Shield*Insulation*Insu lationConductorConductorEPR Insulation in Cable AccessoriesEPR Insulation in Cable AccessoriesEPR Insulation in Cable AccessorieszMost Pre-Molded Cable Terminations, Stress Cones and other Cable Accessories are manufactured from an EPR compound because of it s great resistance to treeing and the effects of corona Discharge around terminations and of Cable FailuresTypes of Cable FailuresTypes of Cable FailureszLaminar Insulation FailureszVoltage Stress Related Failures in Extruded InsulationzCable Accessory FailureLaminar Cable Insulation FailureLaminar Cable Insulation FailureLaminar Cable Insulation FailurePicture Provided By Pirelli WireLaminar Cable Insulation

3 FailureLaminar Cable Insulation FailureLaminar Cable Insulation FailurePicture Provided By Pirelli WireTape removed showing electrical treeingVoltage Stress Related Failures in Extruded InsulationVoltage Stress Related Failures in Voltage Stress Related Failures in Extruded InsulationExtruded InsulationzOverloads, defects or weak spots in insulation lead to chemical breakdown of the insulation, producing thermal runaway leading to decreased Insulation Resistance, increased leakage current and , manufacturing or workmanship results in voids or contamination which produce Partial Discharge and ultimate Trees Form and convert to Electrical Trees and lead to ultimate Stress Related Failures in Extruded InsulationVoltage Stress Related Failures in Voltage Stress Related Failures in Extruded InsulationExtruded Insulation[2]zWater migration into the insulation leads to water trees.

4 Water Trees lead to decreased insulation resistance and very slight increase in leakage current. Water Trees do not directly produce Trees lead to electrical treeswhich produce Partial Discharge and ultimate failure.[5]Water TreesWater TreesWater TreesWater TreeingWater TreeingWater TreeingEPR InsulationPicture Provided By General CableTRXLPE InsulationPicture Provided By General CableBowtie TreesBowtie TreesBowtie Trees[9]Bowtie Tree in XLPEB owtie Tree in EPRW ater Tree ConversionWater Tree ConversionWater Tree Conversion[2]

5 ZVoltage surges occur on systems due to lightning and/or high electric field caused by these surges result in power dissipation in the water channels existing in insulation sufficient to raise the temperature of the water and increase pressure in the water tree phenomena generates cavities sufficient to support Partial TreeingWater TreeingWater TreeingHMWPE InsulationPicture Provided By General CableXLPE InsulationPicture Provided By General CableWater Tree ConversionWater Tree ConversionWater Tree ConversionzPD Inception voltage is exceeded by lightning and other surges causing a PD in drops to below PD Extinction voltage and PD occurrence at which PD occurs causes the size and geometry of the insulation void to change.

6 Lowering the PD inception and extinction PD extinction voltage drops below system nominal voltage, PD s are continuous leading to electrical tree formation and ultimate insulation Tree ConversionWater Tree ConversionWater Tree Conversion500010000150002000025000300003 50004000045000 Impulse 1 Impulse 2 Impulse 3 Impulse 4 Impulse 57200 VInsulation FailureInsulation FailureInsulation FailurePicture Provided By Pirelli WireFailures in Cable AccessoriesFailures in Cable AccessoriesFailures in Cable AccessorieszThe majority of failures on distribution systems occur in terminations.

7 Splices and other cable mechanisms reported in Cable Accessories are predominantly involve Partial Discharge Deterioration caused by voids, contaminants and workmanship Partial Discharge ProcessThe Partial Discharge ProcessACOUSTICSACOUSTICSHEAT/CHEMICAL HEAT/CHEMICAL REACTIONSREACTIONSLIGHTLIGHTEM WAVESEM WAVESIEEE Standard 400-2001 Notes:IEEE Standard 400 IEEE Standard 400--2001 Notes:2001 Notes:z Partial Discharge measurement is an important method of assessing the quality of the insulation of power cable z A Partial Discharge is an electrical Discharge (formation of a streamer or arc) that does not bridge the entire space between two electrodes.

8 ZPartial discharges may occur in a a at the tip of a well-developed water The Partial Discharge ProcessThe Partial Discharge ProcessMicroscopic spaces ( voids ) may be formed in insulation systems due to water tree growth, aging, installation or manufacturing defects. Continued stress and overvoltagescan initiate PD in and other forms of energy released by PD cause erosion of the internal surface of the erosion forms channels that develop into so-called electrical trees in the System FailureContinued PD produces further erosion until the electrical tree bridges the Test for Partial Discharges?

9 Why Test for Partial Discharges?Why Test for Partial Discharges?zPartial Discharge Testing can detect: Insulation defects that may have occurred during cable system installation or the manufacturing process Insulation deterioration due to normal service operating conditionszPartial Discharge Testing is a PREDICTIVE qualitative analysis tool that can warn of a potential upcoming system Partial Discharge Testing program can locate problem areas (cable, splices, and/or terminations) in a cable Discharge test results can be trended over traditional High Potential Testing , Partial Discharge Testing is not destructiveto an insulation system.

10 (Hipottesting is typically a go-no-go test --the cable either fails or it doesn t). In addition, even massive insulation defects in extruded dielectric insulation cannot be detected with according to the IEEE 400-2001 Partial Discharge REQUIREMENTSAEIC Partial Discharge AEIC Partial Discharge REQUIREMENTSREQUIREMENTSM anufacturers Maximum Permissible PartialDischarge (pC) at % of rated Voltage-Ground150%200%250%300%400%197353 055808019755203550--19825203550--1987555 510199655555 Historical Testing MethodsHistorical Testing MethodsHistorical Testing MethodszOff- line Testing Techniques High Potential Testing Power Factor/Dissipation Factor Testing Very Low Frequency Testing (VLF)