The panel cutout with proper dimensions as shown the unit into the panel with the help of clamp equipment in its installed state must not come inclose proximity to any heating sources, caustic vapors,oils, steam, or other unwanted process safety related codifications, symbols and instructions that appear in this operating manual or on the equipment must be strictly followed to ensure the safety of the operating personnel as well as the instrument. If the equipment is not handled in a manner specified by the manufacturer it might impair the protection provided by the equipment. Read complete instructions prior to installation and operation of the unit. WARNING : Risk of electric prevent the risk of electric shock power supply to theequipment must be kept OFF while doing the wiringarrangement. Do not touch the terminals while power isbeing eliminate electromagnetic interference use short wirewith adequate ratings; twists of the same in equal size shallbe made.

1.Prepare the panel cutout with proper dimensions as shown above. 2.Fit the unit into the panel with the help of clamp given. 3.The equipment in its installed state must not come in

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of OP TC544A TC244AX TC344AX DTC204A-2 …

1 The panel cutout with proper dimensions as shown the unit into the panel with the help of clamp equipment in its installed state must not come inclose proximity to any heating sources, caustic vapors,oils, steam, or other unwanted process safety related codifications, symbols and instructions that appear in this operating manual or on the equipment must be strictly followed to ensure the safety of the operating personnel as well as the instrument. If the equipment is not handled in a manner specified by the manufacturer it might impair the protection provided by the equipment. Read complete instructions prior to installation and operation of the unit. WARNING : Risk of electric prevent the risk of electric shock power supply to theequipment must be kept OFF while doing the wiringarrangement. Do not touch the terminals while power isbeing eliminate electromagnetic interference use short wirewith adequate ratings; twists of the same in equal size shallbe made.

2 For the input and output signal lines, be sure touse shielded wires and keep them away from each used for connection to power source, must have a2 cross section of 1mm or greater. These wires shallhaveinsulation capacity made of at least extending the thermocouple lead wires, always usethermocouple compensation wires for wiring. For the RTDtype, use a wiring material with a small lead resistance (5 max per line) and no resistance differentials among better anti-noise effect can be expected by usingstandard power supply cable for the powering up for the first time, disconnect theoutput Protection : The unit is normally supplied without apower switch and fuses. Make wiring so that the fuse isplaced between the mains power supply switch and thecontroller. (2 pole breaker fuse - rating : 275V AC,1A forelectrical circuitry is highly recommended) this is a built-in-type equipment (finds place in maincontrol panel), its output terminals get connected to hostequipment. Such equipment shall also comply with basicEMI/EMC and other safety requirements like BSEN61326-1and BSEN 61010 dissipation of equipment is met throughventilation holes provided on chassis of equipment.

3 Suchventilation holes shall not be obstructed else it can lead to asafety output terminals shall be strictly loaded to themanufacturer specified values / PRECAUTIONS DURING USEE lectrical noise generated by switching of inductive loads can create momentary disruption, erratic display, latch up, data loss or permanent damage to the instrument. To reduce noise:a) Use of snubber circuits across loads as shown above, is recommended. b) Use separate shielded wires for inputs. SAFETY PRECAUTIONSMECHANICAL INSTALLATIONNLC NOTCLOADR CTCS nubberMOVTCTCNLS nubberC NOR CContactorLOADCMOVFor bigger loads, use interposing relay / contactorFor load current less than Dimensions Panel Cutout SPECIFICATIONSD isplay4 + 4 digit, 7 segment digital display4 digit for DTC204A-2 / DTC324A-2 LED Indications1 : Output 1 ON2 : Output 2 ONT : Auto tuneS : Dwell timer* (Applicable for TCX44A/AX)Keys3 keys for digital settingINPUT SPECIFICATIONSI nput SignalThermocouple (J,K,T,R,S) / RTD (Pt100)Sampling time250 msInput Filter (FTC) to for TC/RTD input ( Fixed 1 for R & S type TC input )Temperature UnitoC / F selectableIndication AccuracyFor TC inputs : of 1 For R & S inputs : of 2 (20 min of warm up time for TC input)For RTD inputs.

4 Of 1 ( = Full Scale )FUNCTIONAL SPECIFICATIONSC ontrol Method1) PID control with auto tuning2) ON-OFF control3) Heat-Cool (with auto-tuning)Proportional Band (P) to Integral Time (I)0 to 9999 secDerivative Time (D)0 to 9999 secCycle to secHysteresis to Dwell Timer0 to 9999 min ( only for TCX44A/AX )Manual Reset to HEAT COOL PIDC ontrol Method equipment, being built-in-type, normally becomes apart of main control panel and in such case the terminals donot remain accessible to the end user after installation andInternal not allow pieces of metal, wire clippings, or fine metallicfillings from installation to enter the product or else it maylead to a safety hazard that may in turn endanger life orcause electrical shock to the breaker or mains switch must be installed betweenpower source and supply terminals to facilitate power 'ON'or OFF function. However this switch or breaker must beinstalled in a convenient position normally accessible to and store the temperature controller within thespecified ambient temperature and humidity ranges asmentioned in this to Cycle to BandSPLL to SPHL (Programmable)OUTPUT Control Output (Relay or SSR user selectable) :Relay Contact (SPDT) 05 A resistive@250V AC / 30V DC ( TC544A : SPST RLY) 10 A resistive*@250V AC / 30V DC(*For DTC204A-2 / DTC324A-2 )SSR Drive Output (Voltage Pulse)12V DC, 50 mAAuxiliary Output :Relay Contact (SPDT)05 A resistive@250V AC / 30V DC( TC544A : SPST RLY)SSR Drive Output (Voltage Pulse)12V DC, 50 mAPOWER SUPPLYS upply Voltage85 to 270V AC/DC (AC : 50 or 60 Hz )Optional - 24V AC/DCPower Consumption6 VA max@230V ACTemperatureOperating : 0 to 50 CStorage : -20 to 75 CHumidity (non-condensing)95% RHWeightTC544A : 142 gmsTC244AX / DTC204A-2 : 200 gmsTC344AX / DTC324A-2.

5 252 gmsA52B52C94D45E4F46G46 DIMMODELSTC544 AFGNEW selecTC544A / TC244AX / TC344AX / DTC204A-2 / DTC324A-2 Operating / DTC324A-2 TC244AX / DTC204A-2 INSTALLATION the specified size of crimp terminals ( screws)to wire the terminal block. Tighten the screws on theterminal block using the tightening torque within therange of not connect anything to unused proper input power cables with shortestconnections and twisted of connecting cables shall be away from anyinternal EMI service life of the output relays depends on theswitching capacity and switching conditions. Considerthe actual application conditions and use the productwithin the rated load and electrical service the relay output is rated at 5/10 amps it isalways necessary to use an interposing relay orcontactor that will switch the load. This avoids damage tothe controller in the event of a fault short developing onthe power output use a separate fused supply for the power load circuit and do not take this from the live and neutralterminals supplying power to the controller.

6 Equipment should be cleaned regularly to avoidblockage of ventilating the equipment with a clean soft cloth. Do not useIsopropyl alcohol or any other cleaning :TERMINAL CONNECTIONS TC544A +SSR1 SSR1TC /RTD1+TC /RTD2 RTD3NO2 COM1 SSR2+-NO1 COM2 ( )L+N ( )Doc. Name : OP INST TC544A / TC244AX / TC344AX / DTC204A-2 / DTC324A-2 OP294-V05 (Page 1 of 3)NO2 COM2TC / RTD1TC / RTD2 RTD3NC2NO1 COM1NC1891011121314 ( )L - +N ( )1234567 + - SSR1+-SSR2+-1 Process-value (PV) /Parameter name display1) Displays a process value (PV).2) Displays the parameter symbols at configuration mode/online ) Displays PV error conditions. (refer Table 2 on page 2)Use only the correct thermocouple wire or compensating cable from the probe to instrument terminals avoiding joints in the cable if possible. Failure to use the correct wire type will lead to inaccurate that the input sensor connected at the terminals and the input type set in the temperature controller configuration are the same.

7 TC244AX / DTC204A-2 TC344AX / DTC324A-2* SSR2 Not applicable for DTC204A-2 * SSR2 Not applicable for DTC324A-2110211514413615716817918TC /RTD1TC /RTD2 RTD3312+ - SSR1+-NO2 COM2NC2NO1 COM1 ( )L - +N ( )NC1 SSR2+-TERMINAL CONNECTIONSFRONT PANEL DESCRIPTION43121T25S6If upper display is selected as then,Pressing key will show on Upper display : Lower display : <50>Press + / keys to increment / decrement value. Range : SPLL to SPHLD efault : 50 Programming online parametersTCX44A/AXSetpoint 1If online parameter is selected as then,Pressing key will show on display : & then <50>Press + / keys to increment / decrement value. Range : SPLL to SPHLD efault : 50 Programming online parametersDTC204A-2 / DTC324A-2 Setpoint 1 Range : SPLL to SPHL Range : SPLL to SPHLS etpoint 2 / Dead bandSetpoint 2 / Dead bandDefault : 0 Default : 0 If upper display is selected as / then,Pressing key will show on Upper display : / Lower display: <0>Press + / keys to increment / decrement / value.

8 If upper display is selected as / then,Pressing key will show on display : / & then <0>Press + / keys to increment / decrement / value. If upper display is selected as / then, Pressing key will show on Upper display : Lower display : <OFF>Press + / keys to increment / decrement time value. Range : OFF, 1 to 9999 minDwell TimerDefault : OFF 5 Tune6 Dwell timerAuto tune : Blinking Blinking : Dwell timer is in ON : Time output 1 indication2 Parameter settingdisplayThe LED is lit when the control output 1 is ON1) Displays the parameter settings at configuration mode/online output 2 indicationThe LED is lit when the control output 2 is ONFUNCTIONSTo view Level 1To view Level 2To view Protection LevelKEY PRESSP ress key for 3 sec. Press key for 3 sec. Press + keys for 3 sec. FRONT KEYS DESCRIPTIONONLINETo view online parametersTCX44A/AXPROGRAMMING MODETo change online parameter valuesPress + / to changeparameter value.

9 Lower display selectable between SET1/SET2/TIME using key. To view parameters on the same level. or key once to view the next or previous function in operational increase or decrease the value of a particular parameter. + to increase and + to decrease the function : Parameter value will not alterwhen respective level is : The unit will auto exit programming mode after 30 sec. of inactivity. By pressing the or or + keys for 3 : Elapsed time / Remaining time dependent on the selection of ONL parameter in level1. (Not applicable for DTC204A-2 / DTC324A-2) To view online parametersDTC204A-2 / DTC324A-2 Display selectable between SET 1/SET 2 using key. Note : Display shows parameter SET 1 / SET 2 for 1 sec. (Not applicable for DTC204A-2 / DTC324A-2)(Not applicable for DTC204A-2 / DTC324A-2)INPUT RANGES (Table 1)When an error has occured, the upper display indicates error codes as given to 1350-199 to 4000 to 1750-199 to 999-199 to 400N/A-328 to 2462-328 to 75032 to 3182-199 to 999-199 to 750N/A C C C F F FFOR THERMOCOUPLER esolutionINPUTRANGESJ-199 to 750-199 to 750-328 to 1382-199 to 999 C to 1562-199 to 999 RANGESPt100 FOR RTD ResolutionINPUTS ensor break / over range conditionSensor reverse / under range conditionOFFOFFM eaningControl Output StatusERROR DISPLAY (Table 2) FKTR & S-150 to 850-150 to 850 CCALIBRATION CERTIFICATEDate :Model No :Claimed Accuracy: For TC inputs : of FS 1 For R & S inputs : of 2 (20 min of warm up time for TC input) For RTD inputs : of FS 1 Sources calibrated against : Multimeter calibration report no : The calibration of this unit has been verified at the following values.

10 JKPT100 SENSORCALIBRATIONTEMP ( C)DISPLAYVALUE ( C) thermocouple / RTD curves are linearised in this microprocessor based product; and hence the values interpolated between the readings shown above are also equally accurate; at every point in the curve. Unit is accepted as accuracy is within the specified limit of claimed accuracy and certificate is valid upto one year from the date of BY :Doc. Name : OP INST TC544A / TC244AX / TC344AX / DTC204A-2 / DTC324A-2 OP294-V05 (Page 2 of 3)Level 1 Level 2 DisplayDisplayDefaultValueDefaultValueRa ngeRangeJ/K/T/R/S/RTDOFF/ON1 to C/ F0 to 9999 secMin range of sensor selected to SPHL0 to 9999 secSPLL to Max rangeof sensor selected to to secRE/FDRE/FD/ to to PID/ to + to NO/YESOFF, 1 to 9999 to DisplayConditionDisplayConditionNot promptedfor R & S typeFor CNTL=ONFFor HC=NO orHC=YES &CNTL=ONFFor CNTL=PID& I=0 DescriptionInput type (Refer Table 1)Tune Display ResolutionProportional bandTemperature unitIntegral timeSet point low limitDerivative timeSet point high limitCycle time modeCycle timeCycle time-coolControl action forrelay 1 Control action forrelay 2 Factory default(Reset all)