Example: marketing

PARKING LOT & STREET LIGHT POLE BASE DETAIL

1" RIGID GALV. CONDUIT WITHINSULATING BUSHINGS OR PVCSCHEDULE 40 ELBOW 3#12 IN 1" PVC CONDUIT TO NEXT POLE, ORPROVIDE SPARE 1" C. STUBBED OUT 5'-0"FOR FUTURE POLE OR TO LOCATIONSHOWN ON PLANS. STUB OUT ADDITIONAL1" C. FOR DATA/COMM. WITH TRACER WIRESOLDERLESS CONNECTION WRAPPEDWITH VINYL PLASTIC TAPEWATER TIGHT RUBBER MOLDEDFUSE HOLDER, FUSE @ 4 AMPS SEEDETAIL 26 56 00 - 05 FOR MORE #12 TO FIXTURE(S)POLE HANDHOLE#2 BARE COPPER GROUNDWIRE WITH GROUND WIRELUG INTEGRAL TO POLE3/4" CHAMFER AND TOOL FINISHED GROUTJOINT ALL AROUNDPROVIDE RAISED BASE FOR ALLPOLES IN PAVED PARKING AREASAND AREAS WITHIN 24" OF CURBFROM EDGE OF POLE BASEPROVIDE CONCRETE BASEWITH 4 #6 REBAR VERT.

method *l length 2'-6" 30'-0" max. refer to lumnaire schedule 3" ... parking lot & street light pole base detail no scale 1 e1.01 handhole at top of pole. provide surge protection device within. see detail 26 56 00 - 05 for more info. parking lot & street light

Tags:

  Methods, Parking, Parking lot

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of PARKING LOT & STREET LIGHT POLE BASE DETAIL

1 1" RIGID GALV. CONDUIT WITHINSULATING BUSHINGS OR PVCSCHEDULE 40 ELBOW 3#12 IN 1" PVC CONDUIT TO NEXT POLE, ORPROVIDE SPARE 1" C. STUBBED OUT 5'-0"FOR FUTURE POLE OR TO LOCATIONSHOWN ON PLANS. STUB OUT ADDITIONAL1" C. FOR DATA/COMM. WITH TRACER WIRESOLDERLESS CONNECTION WRAPPEDWITH VINYL PLASTIC TAPEWATER TIGHT RUBBER MOLDEDFUSE HOLDER, FUSE @ 4 AMPS SEEDETAIL 26 56 00 - 05 FOR MORE #12 TO FIXTURE(S)POLE HANDHOLE#2 BARE COPPER GROUNDWIRE WITH GROUND WIRELUG INTEGRAL TO POLE3/4" CHAMFER AND TOOL FINISHED GROUTJOINT ALL AROUNDPROVIDE RAISED BASE FOR ALLPOLES IN PAVED PARKING AREASAND AREAS WITHIN 24" OF CURBFROM EDGE OF POLE BASEPROVIDE CONCRETE BASEWITH 4 #6 REBAR VERT.

2 AND#4 REBAR HORZ. AT 12" 467 LISTED, CORROSIONRESISTANT, COMPRESSION OREXOTHERMIC WELDEDGROUND BOND TO REBARANCHOR BOLTS PERMANUFACTURERSRECOMMENDATIONSFINISHEDL EVELING NUTS WITH CAPS AND ROUNDSTEEL BASE COVER TO MATCH POLE3" (NOM) TOP, BOTTOM ANDALL SIDES OF BASE CASTING3"RIGID GALV. TO PVC TRANSITION(WHERE APPLICABLE)18"MIN3500 PSI ROUND POUREDCONCRETE BASE, SIZE PERSCHEDULE ABOVEBACKFILL WITH D-1 MATERIAL 12" AROUNDALL SIDES OR BASE. COMPACT TO 95%PER MODIFIED PROCTOR DENSITYMETHOD*L LENGTH2'-6"30'-0" TO LUMNAIRE SCHEDULE3" WHERE PVC ELBOWS AREPROVIDED, PROVIDE FLATTYPE PULL LINE/ DSX SERIES -4000K CCT, BLACK FINISH, PER7 SEVEN-WIRE RECEPTACLE, DRIVECURRENT & DISTRIBUTION BYDESIGN PER NU GUIDELINESSEE LUMINAIRE SCHEDULEROUND TAPERED STEEL POLEWITH VIBRATION DAMPENERSCOORDINATE WITH UNL PM & PROVIDE PHOTOCELL DLL127 LP BKPER PROJECT REQUIREMENTS.

3 REFER TO PLANS & LUMINAIRESCHEDULE FOR EXACT FIXTURE TYPE & QUANTITY OF OF POLEHEIGHT(HT) AFG 0' < HT < 15' 48" L x 16" D15' < HT < 29' 60" L x 20" D29' < HT < 40' 72" L x 24" DCONCRETE BASELENGTH BELOWGRADE & DIAMETER* POLE BASE LENGTH (L) BELOW FINISHEDGRADE AND DIAMETER (D) AS FOLLOWS:*DDIAMETERSCALE: PARKING LOT & STREET LIGHTPOLE BASE DETAILNO AT TOP OF POLE. PROVIDESURGE PROTECTION DEVICE WITHIN. SEEDETAIL 26 56 00 - 05 FOR MORE LOT & STREET LIGHTPOLE BASE DETAIL26 56 00 - 2020 DETAIL No.

4 :Scale:Date: DETAIL Title:Facilities Planning & ConstructionStandard DETAIL