Example: bankruptcy

Pipe Temperature Sensors - MAMAC Sys

DN703 Copyright 2013 Registered trademark MAMAC SYSTEMS, Waterside CentreSolihull ParkwayBirmingham West MidlandsB37 7YN United Kingdom01384-271113 Fax 01384-2711141 Fullerton Road #02-01 One FullertonSingapore 04921365-31581826 Fax 65-315818264 Armiger Court, Unit 2 Adelaide Australia08-8395-4333 Fax 08-8395-4433 675 Cochrane DriveEast Tower 6th FloorToronto OntarioL3R 0B8 Canada905-474-9215 Fax 905-474-08768189 Century Boulevard Minneapolis, MN 55317-8002 USA800-843-5116 952-556-4900 Fax Temperature SensorsModel TE-703 / 704 Four immersion thermowell installationoptions brass adapter with 304 SSprobe for adjustable insertion, plastic,galvanized steel or NEMA-4/IP-65 steelenclosure. Four strap on surface mountinstallation options rugged 304 SShermetically sealed probe, plastic,galvanized steel or NEMA-4/IP-65contact surface Temperature sensorsoffer the industry s most extensive rangeto satisfy all HVAC, appliance andindustrial applications.

3 TE-704 TE-704-A Strap On Probe Incorporates a 2" 304 SS probe with a 6 ft/1.8m plenum rated cable for pipe surface temperature sensing. Nylon ties are

Tags:

  Temperatures, Pipe, Sensor, Pipe temperature sensors

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Pipe Temperature Sensors - MAMAC Sys

1 DN703 Copyright 2013 Registered trademark MAMAC SYSTEMS, Waterside CentreSolihull ParkwayBirmingham West MidlandsB37 7YN United Kingdom01384-271113 Fax 01384-2711141 Fullerton Road #02-01 One FullertonSingapore 04921365-31581826 Fax 65-315818264 Armiger Court, Unit 2 Adelaide Australia08-8395-4333 Fax 08-8395-4433 675 Cochrane DriveEast Tower 6th FloorToronto OntarioL3R 0B8 Canada905-474-9215 Fax 905-474-08768189 Century Boulevard Minneapolis, MN 55317-8002 USA800-843-5116 952-556-4900 Fax Temperature SensorsModel TE-703 / 704 Four immersion thermowell installationoptions brass adapter with 304 SSprobe for adjustable insertion, plastic,galvanized steel or NEMA-4/IP-65 steelenclosure. Four strap on surface mountinstallation options rugged 304 SShermetically sealed probe, plastic,galvanized steel or NEMA-4/IP-65contact surface Temperature sensorsoffer the industry s most extensive rangeto satisfy all HVAC, appliance andindustrial applications.

2 304 SS thin wall probe with a cold rolledhermetically sealed end forms a monolithicencapsulated cavity for the sensor and isimmune to failures caused by highhumidity, contamination, thermal shockand vibration. Fast response brass contact sensor forstrap on applications is insulated fromthe enclosure to provide accurate pipesurface Temperature measurement. More than 16 types of interchangeable NTCthermistors, precision platinum, nickel orbalco RTDs are available for universal 703/704 Temperature Sensors offer the industry s most extensive range of enclosure, installation and sensor types to satisfy all HVAC, industrial and commercial applications. These revolutionary Sensors incorporate more than twenty five years of product development and experience drawn from millions of installations world wide in all types of applications. This product and process design combined with automated manufacturing processes yields a rugged, reliable, repeatable and stable Temperature sensor at a low cost.

3 The only line of Temperature Sensors offering lifetime warranty against moisture migration related failures. For large volume OEM customers, TE-703/704 Temperature Sensors are available in many custom configurations. Wire type, length or gage, terminals, connectors, probe lengths, enclosure options or sensor types may be customized based on volume. RoHSTE-7032TE-703-A Thermowell MountIncorporate a hermetically sealed 304 SS probe and a brassadapter with a compression sleeve providing a rugged assemblyfor immersion Temperature sensing if field adjustable insertiondepth is desired. The brass adapter is screwed in to the thermowell,compression sleeve is loosened, probe inserted to desired lengthand the sleeve is tightened. sensor has 6 plenum ratedcable for remote termination. TE-703-A Sensors provide a costeffective and reliable solution for hot/chilled water, condenserwater or low pressure steam applications which requireadjustable insertion EnclosureCorrosion free 30% glass filled polycarbonate enclosure designedto withstand Temperature extremes, mechanical shock andvibration.

4 304 SS probe crimp attached to the enclosure for alow profile mating surface. Patented locking thermowelladapter, single screw cover attachment, are some of the featureswhich improve reliability and lower installation costs. TE-703-Bsensors provide a cost effective and reliable solution forhot/chilled water, condenser water or low pressure Steel EnclosureIndustry standard NEMA-1 / IP-30 galvanized sheet metalenclosure designed for all industrial and commercial immersiontemperature sensing applications. Hermetically sealed, fastresponse 304 SS probe crimp attached to the enclosure for a lowprofile mating surface. Keyed enclosure cover to swing openwithout removing the screws, 1/2" conduit opening, are some ofthe features which improve reliability and lower installation Steel EnclosureRugged steel enclosure with welded seams, gasketed cover andpowder coated finish, rated NEMA-4 / IP-65 for harshenvironments.

5 TE-703-D has all other features including a 304SS probe, conduit opening similar to the TE-703-C series exceptdesigned for applications in unconditioned environments wherethe unit may be subjected to dirt, condensation, oil vapor andother Copyright 2013 Registered trademark MAMAC SYSTEMS, Temperature SensorImmersion Temperature SensorImmersion Temperature SensorImmersion Temperature Sensor3TE-704TE-704-AStrap On ProbeIncorporates a 2" 304 SS probe with a 6 plenum ratedcable for pipe surface Temperature sensing. Nylon ties areprovided to secure the probe to the pipe . TE-704-A provides acost effective and reliable solution for surface contact temperaturemeasurement of conditioned water pipes, low pressure steam orrefrigerant EnclosureCorrosion free 30% glass filled polycarbonate enclosuredesigned to withstand Temperature extremes, mechanical shockand vibration.

6 Fast response brass contact sensor attached to theenclosure for a low profile mating surface, mounting bracket forpipe clamp installation, single screw cover attachment, are someof the features which improve reliability and lower Steel EnclosureIndustry standard NEMA-1 / IP-30 galvanized sheet metalenclosure designed for all industrial and commercial surfacetemperature sensing applications. Fast response brass contactsensor attached to the enclosure for a low profile mating enclosure cover to swing open without removing thescrews, 1/2" conduit opening, are some of the features whichimprove reliability and lower installation Steel EnclosureRugged steel enclosure with welded seams, gasketed cover andpowder coated finish, rated NEMA-4 / IP-65 for harshenvironments. TE-704-D has all other features including a fastresponse brass contact sensor , conduit opening similar to theTE-704-C series except designed for applications in unconditionedenvironments where the unit may be subjected to dirt, condensation,oil vapor and other contaminants.

7 Surface Temperature SensorSurface Temperature SensorSurface Temperature SensorSurface Temperature SensorDN703 Copyright 2013 Registered trademark MAMAC SYSTEMS, Inc.(62 mm) (62 mm) (90 mm) (110 mm) (124 mm)(100 mm) (50 mm) (90 mm) (110 mm)1/4 ( mm) (62 mm) (50 mm) (124 mm)(100 mm)1/4 ( mm) (50 mm) 4TE-704-BTE-704-C/DTE-703-BTE-703-C/DSPE CIFICATIONS:Platinum RTD Sensors :+/- @ 0 C, Alpha : 385 per DIN 43760 Nickel RTD Sensors : (#2)+/- C @ 0 C, 5000 PPM/K RTD Sensors : (#4)+/- F @ 70 F / C, 6000 PPM/K RTD Sensors :+/- F @ 70 F C, 4300 PPM/K Sensors :+/- C interchangeability @ 77 F/ 25 CProbe Material: 1/4 / , / wall 304 Stainless SteelFlange Material: GalvanizedSteelBulkhead Fitting: Brass with poly compression sleevePlastic Enclosure: Polycarbonate 30% glass filled, rated UL 94V-5-0 Steel NEMA-1 / IP-30:18 Ga. Galvanized SteelSteel NEMA-4 / IP-65:18 Ga.

8 Cold Rolled Steel, Baked on EnamelOperating Temp:-40F/-40C to 210F/100 CAmbient Temp:-40F/-40C to 160F/70 CWarranty:Five Years (Lifetime on Moisture Migration). PATENT NO. 6457857, 6555748, 6599012, 70362241/4 ( mm)9/16 (30 mm)DN703 Copyright 2013 Registered trademark MAMAC SYSTEMS, Inc.(30 mm) (62 mm) (50 mm)TE-703/7045 ORDERING INFORMATION: TE-703 AImmersion style1100 ohm Platinum RTDA4 inches/100mm11/8" NPTWith adapter21,000 ohm Nickel RTD (5000 PPM)B6 inches/150mm21/4" NPTBP olycarb Plastic31,000 ohm Platinum RTDC8 inches/200mm31/2" NPTE nclosure IP-5441,000 ohm Nickel RTD (6000 PPM)CGalvanized Steel51,000 ohm Balco RTDE nclosure NEMA-1 / IP-30710,000 ohm NTC therm. (Type III)DPainted Steel810,000 ohm NTC therm. (Carel)Enclosure NEMA-4 / IP-65103,000 ohm NTC ,000 ohm NTC therm. (Type II)135,000 ohm NTC ,035 ohm Silicon PTC15100,000 ohm NTC ,000 ohm NTC ,252 ohm NTC ,800 ohm NTC : TE-703-A-10-A-3:Immersion style with 1/2" adapter, 3000 ohm thermistor and 4 inch : TE-703-D-10-C-2:NEMA-4 enclosure, 3000 ohm thermistor, 8 inch probe and 1/4" NPT brass INFORMATION: TE-704 ASurface Mount1100 ohm Platinum RTDS trap-on21,000 ohm Nickel RTD (5000 PPM)BPolycarb Plastic31,000 ohm Platinum RTDE nclosure IP-54 41,000 ohm Nickel RTD (6000 PPM)CGalvanized Steel51,000 ohm Balco RTDE nclosure NEMA-1 / IP-30710,000 ohm NTC therm.

9 (Type III)DPainted Steel810,000 ohm NTC therm. (Carel)Enclosure NEMA-4 / IP-65 103,000 ohm NTC ,000 ohm NTC therm. (Type II)135,000 ohm NTC ,035 ohm Silicon PTC15100,000 ohm NTC ,000 ohm NTC ,252 ohm NTC ,800 ohm NTC : TE-704-C-1:NEMA-1 enclosure with 100 ohm Platinum RTD surface mount sensor .* For sensor compatibility, please refer to ** For a complete Resistance vs Temperature tables, please refer to *Probe LengthAdapterInstallationSensor*16 10,000 ohm NTC thermistor (Eliwell)16 10,000 ohm NTC thermistor (Eliwell)DN703 Copyright 2013 Registered trademark MAMAC SYSTEMS, : MAMAC Systems, Inc. and its subsidiaries (hereinafter referred to as MAMAC Systems) warrants its products to be free of defects in material and workmanship for a period of five (5) years from date of shipment. If a unit is malfunctioning, it must be returned to the factory for evaluation.

10 A return authorization number (RMA) will be issued by the customer service department and this number must be written or prominently displayed on the shipping boxes and all related documents. The defective part should be shipped freight pre-paid to the factory. Upon examina-tion by MAMAC Systems, if the unit is found to be defective, it will be repaired or replaced at no charge to the customer. However, this warranty is void if the unit shows evidence of being tampered with, damaged during installa-tion, misapplied, misused, or used in any other operating condition outside of the unit s published Systems makes no other warranties or representations of any kind whatsoever, expressed or implied, except that of title. All implied warranties including any warranty of merchantability and fitness for a particular purpose are hereby disclaimed.


Related search queries