PLUTO Safety PLC Message and fault code list - ABB

English v14A2 TLC172005M0214_APLUTOS afety PLCM essage and fault code list 22 TLC172005M0214_AMessage and fault code Safety PLCNote: Reboot can either be made from PC computer or by power messagesNo:Description- - Power upN nRun mode (nn= station number)Lo Program load mode Lo , ready for self programming (program found in other unit)HA(SR11=7)Program execution stopped from PC computer or not started after program be started either from PC or by power Application specific user error, controlled by SR_PlutoDisplay in the PLC faultsNo.

2 2TLC172005M0214_A Message and fault code list. Pluto Safety PLC Note: Reboot can either be made from PC computer or by power off-on. Status messages No: Description

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of PLUTO Safety PLC Message and fault code list - ABB

1 English v14A2 TLC172005M0214_APLUTOS afety PLCM essage and fault code list 22 TLC172005M0214_AMessage and fault code Safety PLCNote: Reboot can either be made from PC computer or by power messagesNo:Description- - Power upN nRun mode (nn= station number)Lo Program load mode Lo , ready for self programming (program found in other unit)HA(SR11=7)Program execution stopped from PC computer or not started after program be started either from PC or by power Application specific user error, controlled by SR_PlutoDisplay in the PLC faultsNo.

2 fault and possible actionEr10* Dynamic output short circuited to foreign resetEr11* IQ_ for illuminated push button function. Missing diode Automatically resetEr12* Short circuit between two dynamic inputsAutomatically resetEr13* Static output ( ) short circuited to 0V orsafety Q2, Q3 overloadedAutomatically reset, K buttonEr14* Static output ( ) short circuited to 24V. Automatically resetEr15 Power supply below 18 VAutom. 3 min or K buttonEr16 Power supply above 30 VAutom.

3 3 min or K buttonEr17 Power supply below 15V. Critically 3 min or K buttonEr18 CAN-bus fault . (Short circuit, termination resistor, etc.) Autom. 3 min or K buttonEr19 Other unit with same station number on Can-busEr20 PLC-program not loadedLoad of PLC programEr21 PLC-program CRC-errorReload with valid PLC-programEr22 IDFIX problem. External IDFIX can not be (Replace IDFIX)Er23 Unmatched ID. IDFIX doesn t match declaration of identifiers or re-declaration of identifier Erroneous PLC-code.

4 Invalid with valid PLC-programEr25 For versions as B16 or B22. Non existing output used Baud rate conflict. Unit programmed for other baud ratethan current bus baud that PLUTO must be rebooted after change ofbaudrate in the PLC or rebootEr27 Wrong checksum for unit member in common or rebootEr28 PLC program does not match the PLUTO : [A/B/S/D 20, 16, 22], [B/S/D 45, 46], [ PLUTO AS-i, B42 AS-i]Change to other type of Plutoor change the Unsupported program version.

5 The program containsinstructions only supported by later customer specificoperating systems. **(See below)Update of operating systemEr30 Unsupported function block used. **(See below)Update of operating systemEr31 IDFIX-PROG program program to flash memorywith K button.*Combined with LED flashing for the affected I/O.**Additional information can be retrieved via PLUTO Manager. 32 TLC172005M0214_AI/O faultsNo: fault and possible actionEr40* Error Safety output Q2 or , Q3 connected together or to other negative , Q3 has too high capacitive load.

6 K buttonEr41* Error output Q2 or Q3. Overload or connected to foreignpositive voltage. K buttonEr42* Error relay output. No answer from internal relaymonitoring when output is off. K buttonEr43* Error relay output. (Self test of transistors)RebootEr44* Error relay output. Internal relay does not switch on. K buttonEr45 Analogue functions not must be be reset with K button butanalogue value will be Analogue input error. **(See below)Automatically resetEr47 Positive voltage on Q2 and/or reset*Combined with LED flashing for the affected I/O.

7 **Additional information can be retrieved via PLUTO faultsNo: fault and possible actionEr50* Input data difference between processor A and A and B reads an input differently. The fault isoften caused by a bad Output data difference between processor A and A and B sets a global variable differently.( , ). **(See below)RebootCheck PLC-programEr52 No answer from any internal relay when output is off.(Both relays stuck)RebootEr58 AS-i Safety code table CRC errorReboot,Teach AS-i Safety codesEr59 Calibration analogue functions CRC faultRebootEr60 System error Twin self test monitoringRebootEr61 System error Timer IRQ monitoringRebootEr62 System error Internal serial communication RebootEr63 Boot-flash CRCR ebootEr64 OS-flash CRCR eboot,Reload operating system (OS)

8 Er65 Plc-flash CRCR eboot, Reload PLC programEr665 volt under/over voltage monitoring **(See below)RebootEr67 CPU-test errorRebootEr68 Ram-test errorRebootEr69 Scan cycle time over run (PLC program to big)RebootEr70 System, sum of system and stack monitoringRebootEr71 PLUTO used for IDFIX writing. Normal operation ceased RebootEr72 System error. No communication AUX processorRebootEr73 System error. Wrong program version/CRC errorReload operating system (OS)Er74 Remanent memory errorReboot*Combined with LED flashing for the affected I/O.

9 **Additional information can be retrieved via PLUTO Manager. 42 TLC172005M0214_AAS-iNo: fault and actionAE 01 ASi power missingAutomatically resetAE 02No connection with ASi master (in Monitor mode)AE 03 Safety code missing by code teachingTeach AS-i Safety codesAE 04 Wrong code tableTeach AS-i Safety codesAE 05 Internal AS-i faultRebootAC [node no]Channel fault in Safety nodeSwitch off both channelsAb [node no]AS-i slave with bad or wrong Safety codeRoutine Single slaveexchange or teach safetycodes (PC) or exchangedefect [node no]Slave profile does not AS-i slaves (with PC)

10 CC [node no]Code Change. PLUTO prepared for exchange of safetyslave, one slave is missing.(Acknowledge with K button.)CCCode Change. PLUTO is prepared for connection of newsafety Found. Code in new Safety slave is available.(Acknowledge with K button.)CdCode Duplicate. Code already stored in Plutos LEDsThe status of the AS-i LEDs does not give any additional information than what is already given bythe error code (except in one case as illustrated by the table below), but green LED off and/or redLED on indicates an showserror code?