PRODUCT DATA SHEET September 2013 - Metacaulk

PRODUCT data SHEET September 2013 . Metacaulk MC150+ Firestopping Sealant Classified System Numbers CAJ 2348, CAJ 3134, FC 8007, WL 1253, WL 2262, WL 1144, WL 1140, WL 3108, WJ 1109, WJ 2088, HWD 0197, WWD 0028. 1. PRODUCT Description Metacaulk MC 15 0 + for 5 gallon ( liter) 1155 cu. in. Metacaulk MC 150+ is a one Features (18,927 cm3). component, general purpose fire rated sealant and smoke seal for VOC Negligible construction joints and through- Water Based penetrations. Metacaulk MC 150+ Excellent Freeze-Thaw ASTM E 84, UL 723 Tunnel Test is a water based, non-sag caulking Flexible Set grade sealant that is easy to apply Paintable Flame Spread 10. as well as to retrofit. It cures to an VOC Compliant Smoke Index 0.

PRODUCT DATA SHEET September 2013 Metacaulk® MC150+ Firestopping Sealant 1. Product Description Metacaulk ® MC 150+ is a one component, general purpose fire rated sealant and smoke seal for

Tags:

  Product, Sheet, Data, 2013, September, Product data sheet september 2013

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of PRODUCT DATA SHEET September 2013 - Metacaulk

1 PRODUCT data SHEET September 2013 . Metacaulk MC150+ Firestopping Sealant Classified System Numbers CAJ 2348, CAJ 3134, FC 8007, WL 1253, WL 2262, WL 1144, WL 1140, WL 3108, WJ 1109, WJ 2088, HWD 0197, WWD 0028. 1. PRODUCT Description Metacaulk MC 15 0 + for 5 gallon ( liter) 1155 cu. in. Metacaulk MC 150+ is a one Features (18,927 cm3). component, general purpose fire rated sealant and smoke seal for VOC Negligible construction joints and through- Water Based penetrations. Metacaulk MC 150+ Excellent Freeze-Thaw ASTM E 84, UL 723 Tunnel Test is a water based, non-sag caulking Flexible Set grade sealant that is easy to apply Paintable Flame Spread 10. as well as to retrofit. It cures to an VOC Compliant Smoke Index 0.

2 Elastomeric seal that is suitable where dynamic movement is expected. Safe and Easy to Use In the event of a fire, Metacaulk Minimum 3 Year Shelf Life Sound Transimission Class MC 150+ will prevent the spread Intumescent STC Rating 51*. of flames, smoke, hot gases and water through joint openings and *Tested in a UL 411 wall assembly/section to ASTM E90. through-penetrations. No dilution or 2. Material Properties mixing is required for use. No special Asbestos Fillers None 3. Applications skills are necessary for installation. Solvents None Metacaulk MC 150+ can be used Metacaulk MC 150+ is applied with in interior applications as a general Hazardous Ingredients None purpose fire rated sealant and smoke a conventional caulking gun, bulk seal for construction joints on both loading gun or can be troweled from Application Caulking vertical and horizontal surfaces.

3 The pail. For large applications, it Gun or Metacaulk MC 150+ is also an can be pumped directly from the pail. Trowel excellent fire rated acoustical sealant Metacaulk MC 150+ systems are and can be used in areas under rated for 1 and 2 hours in accordance Color Red constant vibration or movement. with ASTM E814 (UL1479) and ASTM Metacaulk MC 150+ can also be used E1966 (UL 2079) test standards. MC Cure Time 3to4weeks on various penetrations such as EMT, 150+ is protected in a wet stage (at 77 F/ 25 C) telephone & power cables in concrete as well as in a dry stage against floors and walls , gypsum walls as mold growth with a combination well as wood floors. Use Metacaulk . Density + MC 150+ to prevent the spread of of biocides.

4 Fire and smoke through joints in fire rated gypsum wallboard partitions, Use Metacaulk MC 150+ for various Elastomeric Yes concrete block or concrete walls and/. applications: or concrete or corrugated steel deck Freeze-Thaw Excellent floor/ceiling assemblies. Top of the Wall Construction Joints Deflection Track Wall Systems Skin Over Time 30 min. 4. Installation data Up to 2" (51 mm)PVC/CPVC & ABS (at 77 F/ Install Metacaulk MC 150+ using (Closed) 25 C) standard caulking techniques or Steel, Copper, Cast Iron and trowel from pails. Metacaulk MC. EMT Pipe 150+ may also be pumped from the pH Value 7 to 8. pails. When damming materials are Telephone, Communication and needed, use only materials approved Power Cables Volume Coverage: for the specific application.

5 For oz. tube (304ml) 18 cu. in. For a complete list of PRODUCT (295 cm3). applications or for additional technical information, call RECTORSEAL for the latest information. Metacaulk MC 150+. TYPICAL GYPSUM WALLBOARD For additional information, refer to Material Safety data SHEET . INSTALLATION. 6. Storage & Handling Metacaulk MC 150+ should be For additional technical service, Step 1) stored between 35 F (2 C) and 120 call: 1-800-231-3345. Cut opening in wall. F (49 C) to obtain a minimum 3 year fax: 1-800-452-2824. shelf life. NOTE: Do not dilute, no Step 2) mixing is required. Best if protected RECTORSEAL. 2601 Spenwick Drive, HOUSTON, TEXAS 77055. Clean penetration opening and from freezing.

6 If freezing occurs, surfaces from loose debris, dirt, oil thaw completely before using. Keep and wax. products stored under protective cover in original containers. Step 3). If required, install sleeve or wire mesh and backing material. 7. Availability Metacaulk MC 150+ is available in STEP 4) oz. (304 ml) and 30 oz.(887 ml). Gun the sealant as required to the caulking tubes , oz. (597 ml). specified depth. Trowel surface flush sausage packs and in 5 gallon ( with wall. L) pails. (Application designs vary, please 8. Limitations contact RectorSeal for exact Metacaulk MC 150+ is not designed details.). Consult UL Directory for complete to be used in areas under continuous instructions and system listings.

7 Immersion or in areas which would be continuously wet. Metacaulk MC. 150+ should not be used against hot 5. Testing data uninsulated surfaces above 300 F. For specific test criteria, refer to (149 C). UL's Fire Resistance Directory or call RECTORSEAL. 9. Cautions FOR CHEMICAL EMERGENCY, SPILL, Metacaulk MC 150+ was tested at LEAK, FIRE, EXPOSURE OR ACCIDENT, CALL CHEMTREC-DAY OR NIGHT 1-800- positive pressure with a minimum 424-9300. ( Pa) inches water and in accordance with ASTM E814 (UL PRECAUTIONS: Do not take internally. May 1479) and ASTM E1966 (UL 2079). be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given.

8 Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Inhalation-Remove to fresh FBC System Compatible* indicates air. Ingestion-Only if conscious, give large that this PRODUCT has been tested, and amounts of water and INDUCE VOMITING. FIRE. is monitored on an ongoing basis, to AND SPILLS: Use water fog, CO2, foam, or dry assure its chemical compatibility with chemicals. Wipe up spills to prevent footing FlowGuard Gold , BlazeMaster and hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from Corzan pipe and fittings. FBC, FlowGuard Gold , BlazeMaster and Corzan are heat sources. Keep container closed. Do not licensed trademarks of the Lubrizol Corporation.

9 Reuse empty container. KEEP OUT OF REACH. OF CHILDREN. 10. LIMITED WARRANTY. RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED. EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages.

10 Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. I-13.