Product Data WeatherMaker Single Packaged Rooftop Heat ...

2020 CarrierForm 50 TCQ-7-14-02PD Rev. A50 TCQ*07, 08, 12, 14 Electric Cooling Rooftop Units with Heat Pump andOptional Electric Heat with Puron (R-410A) RefrigerantProduct DataWeatherMaker Single Packaged RooftopHeat Pump Units6 to Nominal Tons2 The Carrier Packaged Heat Pump Rooftop unit (RTU) was designed by customers for customers. With no-strip screw collars, handled access panels, and more, we ve made your unit easy to install, easy to maintain and easy to to installAll WeatherMaker units are field-con-vertible to horizontal air flow whichmakes it easy to adjust to unexpected jobsite complications. Lighter units makeeasy replacement. Carrier 6 to ton50 TCQ rooftops fit on existing Carriercurbs dating back to 1989. Also, ourlarge control box gives you room to workand room to mount Carrier to maintainEasy access handles by Carrier providequick and easy access to all normallyserviced components.

1. Rated and certified under AHRI Standard 210/240 or 340/360, as appropriate. 2. Ratings are based on: Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F db outdoor air temp. IEER Standard: A measure that expresses cooling part-load EER efficiency for commercial unitary air conditioning and heat pump

Tags:

  Standards, Hari, Ahri standard

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Product Data WeatherMaker Single Packaged Rooftop Heat ...

1 2020 CarrierForm 50 TCQ-7-14-02PD Rev. A50 TCQ*07, 08, 12, 14 Electric Cooling Rooftop Units with Heat Pump andOptional Electric Heat with Puron (R-410A) RefrigerantProduct DataWeatherMaker Single Packaged RooftopHeat Pump Units6 to Nominal Tons2 The Carrier Packaged Heat Pump Rooftop unit (RTU) was designed by customers for customers. With no-strip screw collars, handled access panels, and more, we ve made your unit easy to install, easy to maintain and easy to to installAll WeatherMaker units are field-con-vertible to horizontal air flow whichmakes it easy to adjust to unexpected jobsite complications. Lighter units makeeasy replacement. Carrier 6 to ton50 TCQ rooftops fit on existing Carriercurbs dating back to 1989. Also, ourlarge control box gives you room to workand room to mount Carrier to maintainEasy access handles by Carrier providequick and easy access to all normallyserviced components.

2 Our no-strip screw system has superior holdingpower and guides screws into positionwhile preventing the screw from strip-ping the unit s to useThe central terminal board puts all yourconnections and troubleshooting pointsin one convenient place, standard. Mostlow voltage connections are made to thesame board and make it easy to findwhat you re looking for and easy toaccess it. Carrier rooftops have highand low pressure switches, a filter drier,and 2-in. (51 mm) filters standard. EER up to IEER up to with Single speedindoor fan motor and up to 2-speed/VFD indoor fan motor. 6 - ton units fit on existing Car-rier Rooftop curbs making the utilityconnections the same. This savestime and money on replacement jobs. Standardized components and lay-out. Standardized components andcontrols make service and stockingparts easier.

3 Scroll compressors on all units. Thismakes service, stocking parts,replacement, and trouble-shootingeasier. Crankcase heater on all modelsprovides added protection in allapplications. Precision-sized suction line accumu-lator provides high reliability by pre-venting liquid from entering thecompressor during low ambient con-ditions and reverse cycle switch over. Field convertible from vertical tohorizontal airflow configuration onall models. No special kit requiredon 07-12 models. Supply duct kitrequired for 14 model only. 4-way reversing valve rapidlychanges the flow of refrigerant toquickly changeover from cooling toheating and heating to cooling. Easy-adjust, belt drive motor avail-able on all sizes. There s no need forfield-supplied drives or motors. Provisions for bottom or side con-densate drain.

4 Capable of thru-the-base or thru-the-curb electrical routing. Dependable time / temperaturedefrost logic provides a defrostcycle, if needed, every 30, 60, 90,or 120 minutes and is adjustable. Single -point electrical connection. Sloped, composite drain pan won trust and is self draining. Standardized controls and controlbox layout. Standardized compo-nents and controls make stockingparts and service easier. Clean, large, easy to use control box. Standard coils are copper round tube,aluminum plate fin with optional coilcoatings and copper fin design. Color-coded wiring. Large, laminated wiring and powerwiring drawings which are affixed tounit make troubleshooting easy. Single , central terminal board fortest and wiring connections. Fast-access, handled, panels for easyaccess to the blower and blowermotor, control box, and compressors.

5 No-strip screw system guidesscrews into the panel and capturesthem tightly without stripping thescrew, the panel, or the unit. Exclusive, newly-designed indoorrefrigerant header for easier mainte-nance and replacement. Mechanical cooling (115 F to 25 For 46 C to 4 C) on Electro-mechanical (E/M) and Direct DigitalController (DDC) (PremierLink orRTU Open controller). 2-in. (51 mm) disposable filters onall units. High capacity refrigerant filter drieron each circuit. High pressure, loss of charge, andfreeze switches provide higher protec-tion for the unit refrigeration of contentsFeatures/Benefits.. 2 Model Number Nomenclature .. 3 Capacity Ratings .. 4 Physical Data.. 6 Options and Accessories.. 8 Base Unit Dimensions .. 12 Accessory Dimensions .. 26 Performance Data .. 29 Fan Data.

6 44 Electrical Data .. 52 Typical Wiring Diagrams .. 96 Sequence of Operation.. 102 Application Data .. 105 Guide Specifications.. 1063 Staged Air Volume (SAV ) fan speed system utilizes aVariable Frequency Drive (VFD) to automatically adjustthe indoor fan motor speed between cooling on Single stage cooling model 07 and 2-stagecooling models, 08-14 with electro-mechanical controlsor RTU Open controller. Note that SAV is required onall units for installation in the United States as per theDepartment of Energy (DOE) efficiency standard 0B2A0 Cooling Tons07 - 6 ton08 - ton09 - ton12 - 10 ton14 - ton1 Example:Position:234567891011 12 13 14 15 161718 Sensor OptionsA = NoneB = RA Smoke DetectorC = SA Smoke DetectorD = RA + SA Smoke DetectorE = CO2F = RA Smoke Detector and CO2G = SA Smoke Detector and CO2H = RA + SA Smoke Detector and CO2J = Condensate Overflow SwitchK = Condensate Overflow Switch and RA Smoke DetectorsL = Condensate Overflow Switch and RA and SA Smoke DetectorsIndoor Fan Options1 = Standard Static Option - Belt Drive2 = Medium Static Option - Belt Drive3 = High Static Option - Belt DriveC = High Static Option with High Efficiency Motor- Belt Drive (size 14 only)Coil Options - Round Tube/Plate Fin Condenser Coil (Outdoor Indoor Hail Guard)

7 A = Al/Cu Al/CuB = Precoat Al/Cu Al/CuC = E-coat Al/Cu Al/CuD = E-coat Al/Cu E-coat Al/CuE = Cu/Cu Al/CuF = Cu/Cu Cu/CuM = Al/Cu Al/Cu Louvered Hail GuardN = Precoat Al/Cu Al/Cu Louvered Hail GuardP = E-coat Al/Cu Al/Cu Louvered Hail GuardQ = E-coat Al/Cu E-coat Al/Cu Louvered Hail GuardR = Cu/Cu Al/Cu Louvered Hail GuardS = Cu/Cu Cu/Cu Louvered Hail GuardVoltage1 = 575/3/605 = 208-230/3/606 = 460/3/60 Design Revision = Factory Design Revision Base Unit Controls0 = Electro-mechanical Controls can be used with W7212 EconoMi$er IV (Non-Fault Detection and Diagnostic1 = PremierLinkTM Controller2 = RTU Open Multi-Protocol Controller6 = Electro-mechanical w/ 2-speed fan and W7220 Economizer controller Controls. Can be used with W7220 EconoMi$er X (with Fault Detection and Diagnostic)Intake / Exhaust OptionsA = NoneB = Temperature Economizer w/ Barometric ReliefF = Enthalpy Economizer w/ Barometric ReliefK = 2-Position DamperU = Temperature Ultra Low Leak Economizer with Barometric ReliefW = Enthalpy Ultra Low Leak Economizer with Barometric ReliefService Options0 = None1 = Unpowered Convenience Outlet2 = Powered Convenience Outlet3 = Hinged Access Panels4 = Hinged Access Panels and Unpowered Convenience Outlet5 = Hinged Panels and Powered Convenience OutletPackaging0 = Standard1 = LTLE lectrical Options A = NoneC = Non-Fused DisconnectD = Thru-The-Base ConnectionsF = Non-Fused Disconnect and Thru-The-Base ConnectionsG = 2-Speed Indoor Fan Controller (VFD))

8 J = 2-Speed Indoor Fan Controller (VFD) and Non-Fused DisconnectK = 2-Speed Indoor Fan Controller (VFD) and Thru-The-Base ConnectionsM = 2-Speed Indoor Fan Controller (VFD) with Non-Fused Disconnect and Thru-The-Base ConnectionsRefrig. Systems OptionsA = One Stage Cooling ModelsD = Two Stage Cooling ModelsSeries - WeatherMaker 50TC - Packaged RooftopQ = Heat Pump50 TCQ MODEL NUMBER NOMENCLATUREM odel number nomenclature4 LEGENDNOTES:1. Rated and certified under ahri standard 210/240 or 340/360, Ratings are based on:Cooling Standard: 80 F (27 C) db, 67 F (19 C) wb indoor airtemp and 95 F db outdoor air Standard: A measure that expresses cooling part-load EERefficiency for commercial unitary air conditioning and heat pumpequipment on the basis of weighted operation at variable All 50 TCQ units meet the DOE-2018 (Department of Energy),ASHRAE and IECC-2015 minimum efficiency require-ments when equipped with the SAV (staged air volume) RATINGS COOLING (TONS)NETCOOLINGCAPACITY(BTUH)TOTALPOWER (kW)EERIEER WITHSINGLE SPEEDINDOORMOTORIEER WITH2-SPEEDINDOORMOTORA0716 69,000 88,000 99,000 , , RATINGS HEATING MODE50 TCQHEATINGLOW AT 17 F ( 8 C) AMBIENTHEATINGHIGH AT 47 F (8 C) AMBIENTCAPACITY (BTUH)COPCAPACITY (BTUH)

9 COPA0731, , , , , , , , , , Air-Conditioning, Heating and Refrigeration InstituteASHRAE American Society of Heating, Refrigerating and Air-Conditioning EngineersCOP Coefficient of PerformanceEER Energy Efficiency RatioIECC International Energy Conservation CodeIEER Integrated Energy Efficiency RatioCapacity ratings5*Minimum electric heat CFM exceptions (see table below):LEGENDNOTES:1. Outdoor sound data is measured in accordance with AHRI stan-dard Measurements are expressed in terms of sound power. Do notcompare these values to sound pressure values because soundpressure accounts for specific environmental factors which do notmatch individual applications. Sound power values are indepen-dent of the environment and therefore more A-weighted sound ratings filter out very high and very low frequen-cies, to better approximate the response of an average humanear.

10 A-weighted measurements for Carrier units are taken inaccordance with ahri standard - MAXIMUM AIRFLOWS (CFM) COOLING AND ELECTRIC HEAT50 TCQUNITCOOLINGELECTRIC HEATERSMINIMUMMINIMUM2-SPEEDFAN MOTOR(AT HIGH SPEED)MINIMUM2-SPEEDFAN MOTOR(AT LOW SPEED)MAXIMUMMINIMUMMAXIMUMA071800180012 00300018003000D082250253516903750 2250*3750D092550287319154250 2250*4250D12300030002000500030005000D143 75040562704625037506250 UNITUNIT VOLTAGEHEATER kWUNIT CONFIGURATIONREQUIREDMINIMUM PERFORMANCE RATINGS50 TCQUNITOUTDOOR SOUND (dB) Decibel650 TCQ*07 PHYSICAL DATA50 TCQA07 REFRIGERATION SYSTEM# Circuits / # Comp. / Type1 / 1 / ScrollR-410A charge A/B (lbs - oz)17 - 10 / -oil A/B (oz)56 / -Metering deviceAccutrolHigh-pressure trip/reset (psig)630 / 505 Low-pressure trip/reset (psig)27 / 44 EVAP. COILM aterialCu / AlCoil type3/8-in. RTPFRows / FPI 4/ 15 Total face area (ft2) drain conn.