Example: air traffic controller

PRPGE14 - Armstrong Air

PRPGE14 14 SEER GAS ELECTRIC. PRODUCT SPECIFICATIONS PACKAGED UNIT. FORM NO. PRPGE14 -100 (01/2017). REFRIGERANT SYSTEM. Environmentally friendly R410A refrigerant Copper tubing with enhanced fin coils Internal service gauge ports Sleeved distributor tubes Microban Antimicrobial Drain Pan High and Low Threaded pressure switches for system protection HEAT EXCHANGER. L models comply with California Energy Commission Low NOx regulations Aluminized Tri-Dimple tubular heat exchanger for increased efficiency Pest protected flue outlet CABINET CONSTRUCTION.

GAS ELECTRIC PACKAGED UNIT PRPGE14 Page 3 BLOWER PERFORMANCE Model Blower Tap CFM @ ext. Static Pressure in in. wc without filter, dry coil

Tags:

  Model, Pressure, Prpge14

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of PRPGE14 - Armstrong Air

1 PRPGE14 14 SEER GAS ELECTRIC. PRODUCT SPECIFICATIONS PACKAGED UNIT. FORM NO. PRPGE14 -100 (01/2017). REFRIGERANT SYSTEM. Environmentally friendly R410A refrigerant Copper tubing with enhanced fin coils Internal service gauge ports Sleeved distributor tubes Microban Antimicrobial Drain Pan High and Low Threaded pressure switches for system protection HEAT EXCHANGER. L models comply with California Energy Commission Low NOx regulations Aluminized Tri-Dimple tubular heat exchanger for increased efficiency Pest protected flue outlet CABINET CONSTRUCTION.

2 Rounded corners for safety and an attractive, clean appearance One piece base design for strength and stability WARRANTY. Drain ports for condensate management and coil runoff 10 year limited parts and compressor warranty/lifetime heat exchanger Low profile, with compact footprint warranty available. See limited warranty document for details. Insulation to minimize heat loss plus reduce sound Textured pre-painted steel cabinet finish Superior service access to components Louvered coil guard protection One piece no leak top design BLOWER. Insulated compartment to reduce sound Efficient multispeed motor for wide airflow range Slide out blower housing for easy service CONTROLS.

3 Solid state integrated blower control board with self diagnostics Direct spark ignition Color coded wiring for easy service INSTALLATION. Horizontal or down discharge capable Utility connections on right side . Tabbed duct flanges for simple duct connection ACCESSORIES. Hinged roofcurb Lifting brackets LP Gas Conversion Internal Filter Kits Page 1. GAS ELECTRIC PACKAGED UNIT PRPGE14 . model NUMBER GUIDE. PRP GE 14 36 -090 L P -1 A. PREMIUM RESIDENTIAL PACKAGE MINOR REVISION CODE. UNIT. MAJOR REVISION CODE. UNIT TYPE. GE = GAS ELECTRIC VOLTAGE. SEER FAMILY LOW NOx HEATING INPUT: 54, 72, 90, 108, 126.

4 TONNAGE: 24, 30, 36, 42, 48, 60. ELECTRICAL AND PHYSICAL DATA. Max Condenser Blower Min Volts Refrig. Fuse/ Compressor Motor Motor Exhaust Motor Weight model Voltage Phase Hz @ MCA Charge HACR (lbs.). 60 hz (oz.). Breaker RLA LRA RLA HP RLA HP RLA HP. PRPGE1424-054(L)P 352. 25 70. PRPGE1424-072(L)P 358. 1/4. PRPGE1430-054(L)P 364. 64 77. PRPGE1430-072(L)P 1/6 370. PRPGE1436-054(L)P 30 377. PRPGE1436-072(L)P 2 1/3 79 383. PRPGE1436-090(L)P 208-230 1 60 197 1/50 389. PRPGE1442-072(L)P 454. 85 1/3 84. PRPGE1442-090(L)P 460. 40. PRPGE1448-108(L)P 470.

5 96 1/4 1/2 82. PRPGE1448-126(L)P 476. PRPGE1460-108(L)P 507. 60 125. PRPGE1460-126(L)P 513. PERFORMANCE. COOLING HEATING. Rated Rated Sound model AHRI Sensible Input Output Efficiency Temp Rise SEER EER CFM dBA. Capacity Capacity BTUH BTUH AFUE Range F. Btuh Btuh PRPGE1424-054(L)P 54,000 43,800 30-60. 22,600 16,500 800. PRPGE1424-072(L)P 72,000 58,400 40-70. PRPGE1430-054(L)P 54,000 43,800 30-60. 28,400 20,700 1000. PRPGE1430-072(L)P 72,000 58,400 40-70. PRPGE1436-054(L)P 54,000 43,800 30-60. PRPGE1436-072(L)P 34,000 25,800 1200 72,000 58,400 35-65.

6 PRPGE1436-090(L)P 90,000 72,900 81% 40-70 78. PRPGE1442-072(L)P 72,000 58,400 30-60. 40,000 30,000 1400. PRPGE1442-090(L)P 90,000 72,900 40-70. PRPGE1448-108(L)P 108,000 87,500 40-70. 46,000 35,000 1600. PRPGE1448-126(L)P 126,000 102,100 45-75. PRPGE1460-108(L)P 108,000 87,500 40-70. 57,000 41,600 1800. PRPGE1460-126(L)P 126,000 102,100 45-75. *Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240. Page 2. GAS ELECTRIC PACKAGED UNIT PRPGE14 . BLOWER PERFORMANCE. CFM @ ext. Static pressure in in.

7 Wc without filter, dry coil model Blower Tap 2 1350 1310 1270 1210 1140 1080 1020 950. PRPGE1424 3 1110 1080 1050 1000 970 920 870 800. PRPGE1430 4 970 950 920 890 850 820 770 710. 5 840 820 800 770 750 720 680 620. 2 1460 1380 1280 1190 1100 990 880 760. PRPGE1436 3 1350 1280 1200 1130 1060 950 870 750. 4 1080 1030 960 900 830 750 700 650. 2 1790 1740 1670 1590 1510 1410 1310 1210. PRPGE1442 3 1500 1470 1430 1370 1310 1240 1140 1010. 4 1070 1050 1010 980 920 870 820 690. 2 1970 1890 1790 1690 1600 1510 1400 1280. PRPGE1448 3 1730 1690 1600 1540 1450 1360 1270 1150.

8 4 1520 1480 1430 1370 1310 1230 1140 1050. 1 1400 1320 1260 1200 1120 1060 980 900. PRPGE1460* 2 1920 1870 1820 1770 1720 1670 1450 1360. 3 2240 2200 2140 2100 2060 2020 1980 1950. * TAPs 4 & 5 are for Furnace mid point rise. COOLING PERFORMANCE - EXTENDED RATINGS. Outdoor Temperature - DB F. Indoor Outdoor Temp DB/ 65 82 95 105 115 . model WB F. Btuh S/T kW Btuh S/T kW Btuh S/T kW Btuh S/T kW Btuh S/T kW. 85/72 31,700 29,100 27,100 25,000 22,900 80/67 28,600 25,700 23,600 22,200 20,900 PRPGE1424. 75/63 26,100 24,000 22,300 20,800 19,400 75/57 22,400 20,800 19,600 19,100 18,700 85/72 36,800 34,200 32,200 29,800 27,300 80/67 33,100 31,400 28,900 26,900 24,800 PRPGE1430.

9 75/63 30,000 28,200 26,800 25,100 23,300 75/57 27,500 25,000 23,200 22,900 22,600 85/72 45,000 41,300 38,400 36,100 33,700 80/67 41,200 37,400 34,500 32,800 31,100 PRPGE1436. 75/63 38,500 35,300 32,900 31,000 29,100 75/57 35,500 33,000 31,000 29,500 27,900 85/72 53,600 50,200 47,600 43,600 39,500 80/67 50,200 46,000 42,700 39,500 36,300 PRPGE1442. 75/63 47,200 42,800 39,500 36,600 33,800 75/57 42,800 38,500 35,300 34,000 32,700 85/72 64,900 58,200 53,100 48,600 44,100 80/67 59,200 52,300 47,500 44,100 40,800 PRPGE1448. 75/63 53,200 47,400 42,900 40,500 38,000 75/57 46,500 42,100 38,700 37,800 36,800 85/72 70,300 66,100 62,800 59,100 55,500 80/67 65,700 61,000 57,400 54,300 51,200 PRPGE1460.

10 75/63 61,400 56,300 52,300 50,200 48,000 75/57 54,500 50,100 46,700 46,300 45,900 Page 3. GAS ELECTRIC PACKAGED UNIT PRPGE14 . DIMENSIONS (IN.). model A B C D E F G H J. PRPGE1424. PRPGE1430 14 PRPGE1436. PRPGE1442. PRPGE1448 PRPGE1460. Page 4. GAS ELECTRIC PACKAGED UNIT PRPGE14 . Page 5. GAS ELECTRIC PACKAGED UNIT PRPGE14 . ROOF CURB DIMENSIONS. 10. 44-5/8 (254) C. (1133). 33 B A. (838). Unit Mounting H. Brackets (4). F 1-7/8. Insulated (48) Pan 5/8 . SUPPLY. OPENING Unit Mounting G. Brackets (4). 8 (203). 14 (356) 5/8 RETURN I. OPENING. 8. (203).