Series DS-1 Dry-Type Sprinklers Quick response , Standard Coverage K-factor, 3/4 and 1-Inch NPTPage 1 of 10 OCTOBER 2010 TFP510 IMPORTANTA lways refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and in-stallation of sprinkler systems and components. Improper handling and installation can permanently dam-age a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate Services 800-381-9312 | +1-401-781-8220 Description The TYCO Series DS-1, K-factor, 3/4 and 1-Inch NPT, Quick response , Standard Coverage , Dry-Type Sprink-lers are decorative, 3-mm glass bulb automatic sprinklers de signed for com-mercial use.

Series DS-1 Dry-Type Sprinklers Quick Response, Standard Coverage 5.6 K-factor, 3/4 and 1-Inch NPT Page 1 of 10 OCTOBER 2010 TFP510 IMPORTANT

Tags:

  Response

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Quick Response, Standard Coverage General Model/Sprinkler ...

1 Series DS-1 Dry-Type Sprinklers Quick response , Standard Coverage K-factor, 3/4 and 1-Inch NPTPage 1 of 10 OCTOBER 2010 TFP510 IMPORTANTA lways refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and in-stallation of sprinkler systems and components. Improper handling and installation can permanently dam-age a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate Services 800-381-9312 | +1-401-781-8220 Description The TYCO Series DS-1, K-factor, 3/4 and 1-Inch NPT, Quick response , Standard Coverage , Dry-Type Sprink-lers are decorative, 3-mm glass bulb automatic sprinklers de signed for com-mercial use.

2 Dry-Type Sprinklers are typically used where: pendent sprinklers are re quired on dry pipe systems that are exposed to freezing tempera tures; for example, sprinkler drops from un heated por-tions of buildings. sprinklers and/or a portion of the con-necting piping are exposed to freezing temperatures; for example, sprinkler drops from wet sys tems into freezers, sprinkler sprigs from wet systems into unheated attics, or horizontal piping extensions through a wall to protect an unheated areas such as loading docks, overhangs, and building exteriors. sprinklers are used on sys tems that are seasonally drained to avoid freezing; for example, vacation Series DS-1 Dry-Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the National Fire Protection Association, in addition to the standards of any authorities hav ing jurisdiction.

3 Failure to do so may impair the performance of these de vices. Owners are responsible for maintain ing their fire protection system and de vices in proper operating condition. The in-stalling contractor or sprinkler manu-facturer should be contacted with any questions. The Series DS-1 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Model/Sprinkler Identification Numbers (SINs)3/4-Inch NPT: TY3935 - Pendent TY3735 - Horizontal Sidewall 1-Inch NPT: TY3235 - Pendent TY3135 - Upright TY3335 - Horizontal SidewallTFP510 Page 2 of 10 1-INCH NPTTY3235 Pendent with Standard Recessed Escutcheon (Figure 4)TY3235 Pendent with Standard Escutcheon (Figure 3) with Deep Escutcheon (Figure 5) without Escutcheon (Figure 6) TY3135 Upright without Escutcheon (Figure 7)TY3335 Horizontal Sidewall with Top of Deflector-to-Ceiling Distance of 4 to 12 inches (100 to 300 mm) with Standard Escutcheon (Figure 8) with Deep Escutcheon (Figure 9) without Escutcheon (Figure 10)Temperature RatingBulb Color CodeFinishNatural BrassChrome PlatedWhite PolyesterNatural BrassChrome PlatedWhite PolyesterNatural BrassChrome PlatedWhite Polyester135 F (57 C)

4 Orange1, 2, 31, 21, 2, 31, 2 1*, 2*, 3**1*, 2*155 F (68 C)Red1, 2, 31, 21, 2, 31, 21*, 2*, 3**1*, 2*175 F (79 C)Yellow1, 2, 31, 21, 2, 31, 21*, 2*, 3**1*, 2*200 F (93 C)Green1, 2, 31, 21, 2, 31, 21*, 2*, 3**1*, 2*286 F (141 C)BlueN/A1, 2, 31, 21*, 2*, 3** 1*, 2*TABLE B 1-INCH NPT AND ISO 7-R1, SERIES DS-1 Quick response , Standard Coverage DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALSN otes:1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 inches).2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 inches).3. Approved by Factory Mutual Research Corporation (maximum order length of 48 inches).4. The Upright Sprinkler without an Escutcheon (TY3135) is available in 1-Inch NPT only.

5 * Light and Ordinary Hazard Occupancies Only / ** Light Hazard Occupancies Only / N/A - Not AvailableTABLE A 3/4-INCH NPT, SERIES DS-1 Quick response , Standard Coverage DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS3/4-INCH NPTTY3935 Pendent with Standard Recessed Escutcheon (Figure 4)TY3935 Pendent with Standard Escutcheon (Figure 3) with Deep Escutcheon (Figure 5) without Escutcheon (Figure 6)TY3735 Horizontal Sidewallwith Top of Deflector-to-CeilingDistance of 4 to 12 inches (100 to 300 mm) with Standard Escutcheon (Figure 8) with Deep Escutcheon (Figure 9) without Escutcheon (Figure 10)Temperature RatingBulb Color CodeFinishNatural BrassChrome PlatedWhite PolyesterNatural BrassChrome PlatedWhite PolyesterNatural BrassChrome PlatedWhite Polyester135 F (57 C)Orange1, 21, 21*, 2*155 F (68 C)Red1, 21, 21*, 2*175 F (79 C)Yellow1, 21, 21*, 2*200 F (93 C)Green1, 21, 21*, 2*286 F (141 C)BlueN/A1, 21*, 2*Notes:1.

6 Listed by Underwriters Laboratories, Inc. (maximum order length of 48 inches).2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 inches).* Light and Ordinary Hazard Occupancies Only / N/A - Not AvailableTFP510 Page 3 of 10 WATERTUBEVENT HOLEGUIDETUBESEALINGPLUG WITHDEFLECTORSPRINGASSEMBLYFRAME3 mm BULBINSERTYOKESCREWINLETCASINGBULBCOMPRE SSIONSEATINLETBANDWATERTUBEVENT HOLEGUIDETUBE3 mm BULBINSERTSPRINGSCREWINLETSEALINGPLUG WITHCASINGDEFLECTORBULBYOKECOMPRESSIONSE ATASSEMBLYFRAMESPRINGPLUGINLETBANDFIGURE 2 SERIES DS-1, 1-INCH NPT AND ISO 7-R1, Quick response DRY-TYPE SPRINKLER ASSEMBLYFIGURE 1 SERIES DS-1, 3/4-INCH NPT, Quick response DRY-TYPE SPRINKLER ASSEMBLYT echnical DataApprovalsUL and C-UL ListedFM ApprovedRefer to Tables A and Working Pressure175 psi (12,1 bar)

7 Inlet Thread Connection3/4-Inch NPT1-Inch NPT or ISO 7-R1 Discharge CoefficientK = GPM/psi1/2(80,6 LPM/bar1/2)Temperature RatingsRefer to Tables A and : Natural Brass, Chrome Plated, White Polyester Escutcheon: White Coated, Chrome Plated, Brass PlatedPhysical Characteristics Copper Plug .. Copper Yoke ..Stainless Steel Casing ..Galvanized Carbon Steel Insert .. Bronze Bulb Seat ..Stainless Steel Bulb ..Glass Compression Screw ..Bronze Deflector .. Bronze Frame ..Bronze Guide Tube ..Stainless Steel Water Tube ..Stainless Steel Spring ..Stainless Steel Plug Spring*..Stainless SteelSealing Assembly .. Beryllium Nickel w/Teflon** Escutcheon ..Carbon Steel Patents Patent No. 5,188,185 *For 3/4-Inch NPT only **Registered trademark of DuPont TFP510 Page 4 of 10 FIGURE 5 TY3235 AND TY3935 PENDENTWITH DEEP ESCUTCHEON ORDER LENGTHS:INCREMENTS4-1/4" 1/8"(108,0 3,2 mm)IN 1/4" (6,4 mm)(12,7 to 1168,4 mm)1/2" to 46"FACE OFCEILING(88,9 mm)3-1/2" " DIA.

8 (63,5 mm)FITTINGFACE OFSPRINKLERCRITERIA SECTION)(REFER TO DESIGNSPRINKLER FITTINGFIGURE 6 TY3235 AND TY3935 PENDENTWITHOUT ESCUTCHEON FIGURE 3 TY3235 AND TY3935 PENDENTWITH Standard ESCUTCHEON FIGURE 4 TY3235 AND TY3935 PENDENT WITH Standard RECESSED ESCUTCHEON2-1/4" DIA.(57,2 mm)1-3/8" 1/8"(34,9 3,2 mm)2-7/8" DIA.(73,0 mm)IN 1/4" (6,4 mm)3-3/4" to 48"INCREMENTS(95,3 to 1219,2 mm)ORDER LENGTHS:SPRINKLERFACE OFFITTINGCEILINGFACE OFCRITERIA SECTION)(REFER TO DESIGNSPRINKLER FITTINGORDER LENGTHS:(69,9 to 1219,2 mm)2-3/4" to 48"IN 1/4" (6,4 mm)INCREMENTSFITTINGFACE OFSPRINKLERSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)(76,2 mm)3" " DIA.(44,5 mm)(55,6 3,2 mm)2-3/16" 1/8"CEILINGFACE OFSPRINKLERFACE OFFITTING(127,0 to 1219,2 mm)INCREMENTSIN 1/4" (6,4 mm)ORDER LENGTHS:5" to 48"DEFLECTORTO CEILING1-3/4" (44,5 mm)MINIMUMSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FIGURE 7 TY3135 UPRIGHT WITHOUT ESCUTCHEON 1-INCH NPT ONLY TOP OFDEFLECTORCRITERIA SECTION)(REFER TO DESIGNSPRINKLER FITTINGSPRINKLERFITTINGFACE OFIN 1/4" (6,4 mm)INCREMENTS(127,0 to 1219,2 mm)5" to 48"ORDER LENGTHS:TFP510 Page 5 of 10 OperationWhen the TYCO Series DS-1 Dry-Type Sprinkler is in service, water is prevent-ed from entering the assembly by the Plug with Sealing Assembly in the Inlet of the Sprinkler.

9 See Figures 1 and glass Bulb contains a fluid that ex-pands when ex posed to heat. When the rated tem perature is reached, the fluid expands sufficiently to shatter the glass Bulb, and the Bulb Seat is released. The compressed Spring is then able to ex pand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet and allowing the sprin kler to activate and flow water. Design CriteriaThe TYCO Series DS-1 Sprinklers are intended for use in fire sprinkler sys-tems designed in accordance with the Standard installation rules recognized by the applicable Listing or Approval agency; for example, UL Listing is based on NFPA 13 requirements.

10 Sprinkler FittingsInstall the 3/4 or 1-inch NPT Series DS-1 Dry-Type Sprinklers in the 3/4 or 1-inch NPT outlet or run of the follow-ing fittings: malleable or ductile iron threaded tee fittings that meet the dimensional re-quirements of ANSI (Class 150) cast iron threaded tee fittings that meet the dimensional requirements of ANSI (Class 125). Do not install the DS-1 Sprinklers into an elbow fittings. The Inlet of the sprin-kler can contact the interior of the el-bow, potentially damaging the Inlet unused outlet of the threaded tee is plugged as shown in Figures 12 and 13. You can also install the Series DS-1 Dry-Type Sprinklers in the 3/4 or 1-inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee. However, the use of the Figure 730 Tee for this arrangement is limited to wet pipe configuration shown in Figure 12 is only applicable for wet pipe systems where the sprinkler fitting and water-filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry-Type Sprinkler has the minimum exposure length depicted in Figure 11.