XL-Trace SystemInstallatIon and operatIon manual for pIpe freeze protectIon and flow maIntenanceThermal 18/01 Important Safeguards and Warnings WarnIng: FIre anD ShOCK heat-tracing systems must be installed cor-rectly to ensure proper operation and to prevent shock and fire. read these important warnings and carefully follow all the Installation instructions. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Thermal management requirements, agency certifications, and national elec-trical codes, ground-fault equipment protection must be used on each heating cable branch circuit.

XL-Trace System InstallatIon and operatIon manual for pIpe freeze protectIon and flow maIntenance Thermal managemenT WWW.PenTaIrThermal.COm

Tags:

  System, Freeze, Trace, Trace system

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Raychem XL-Trace System Installation and …

1 XL-Trace SystemInstallatIon and operatIon manual for pIpe freeze protectIon and flow maIntenanceThermal 18/01 Important Safeguards and Warnings WarnIng: FIre anD ShOCK heat-tracing systems must be installed cor-rectly to ensure proper operation and to prevent shock and fire. read these important warnings and carefully follow all the Installation instructions. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Thermal management requirements, agency certifications, and national elec-trical codes, ground-fault equipment protection must be used on each heating cable branch circuit.

2 Arcing may not be stopped by conventional circuit breakers. approvals and performance are based on the use of Thermal management-specified parts only. Do not sub-stitute parts or use vinyl electrical tape. Bus wires will short if they contact each other. Keep bus wires separated. Connection kits and cable ends must be kept dry before and during Installation . The black heating cable core is conductive and can short. It must be properly insulated and kept dry. Damaged bus wires can overheat or short. Do not break bus wire strands when preparing the cable for connection.

3 Damaged heating cable can cause electrical arcing or fire. Do not use metal attachments such as pipe straps or tie wire. Use only Thermal management approved tapes and cable ties to secure the cable to the pipe. Do not attempt to repair or energize damaged heating cable. remove damaged sections at once and replace them with a new length using the appropriate Raychem splice kit. replace damaged connection kits. Use only fire-resistant insulation materials such as fiberglass wrap or flame-retardant : Pipes are shown without insulation for illustrative purposes only.

4 All pipe installations must be fully cov-ered with thermal 18/01 Table of Contents1 general Information Use of the Manual XL-Trace Applications Safety Guidelines Approvals 32 Installation guidelines Heating Cable Storage Pre- Installation Checks Heating Cable Installation Heating Cable Connections 173 Thermal Insulation Insulating the System Insulation Installation 254 Power Supply and electrical Protection Voltage Rating Circuit Breaker Sizing Electrical Loading Ground-Fault Protection Important Power Supply Safeguards 295 Control.

5 Monitoring and Power Distribution Control Systems Power Distribution 336 Commissioning and Preventive maintenance Tests 367 Test Procedures System Tests Fault Location Tests 438 Troubleshooting guide 489 appendix 5010 Installation and Inspection records 56ivraychem-Im-h58033-XlTracePipeFreezeP rotectionCOm-en 18/011raychem-Im-h58033-XlTracePipeFreez eProtectionCOm-en 18/011 general Use of the manualThis manual covers the Installation of Raychem XL-Trace self-regulating heating cables and con-nections for commercial construction pipe systems in ordinary (nonhazardous) areas.

6 The manual cov-ers general heating cable Installation procedures and specific Installation details and shows available connection kits for the different applications. The manual also discusses controls, testing, and periodic manual assumes that the proper heat-tracing design has been completed according to the Pipe freeze Protection and Flow Maintenance Design Guide (H55838). Only the applications described in Section are approved by Thermal Management for XL-Trace systems when used with approved Raychem connection kits.

7 The instructions in this manual and the Installation instructions included with the connection kits, control systems, power dis-tribution systems, and accessories must be followed for the Thermal Management warranty to apply. Contact your Thermal Management representative for other applications and additional information, contact:Thermal management7433 Harwin Drive Houston, TX 77036 USA Tel: + : + : + : 18/011 general XL-Trace applicationsXL- trace heat-tracing systems are approved and qualified for the applications listed protection general water piping.

8 freeze protection (40 F (4 C) maintain) of insulated metallic or plastic water piping. Sprinkler piping systems. freeze protection (40 F (4 C) maintain) of insulated metallic standpipes and supply piping up to 20".Flow maintenance greasy waste lines. Flow maintenance (110 F (43 C) maintain) of insulated-grease disposal lines. Fuel lines. Flow maintenance (40 F (4 C) main-tain) for insulated metallic piping containing #2 fuel heating cable applications other than those listed above, please see your Thermal Management repre-sentative or call us at (800) Safety guidelinesAs with any electrical equipment, the safety and reli-ability of any System depends on the quality of the products selected and the manner in which they are installed and maintained.

9 Incorrect design, handling, Installation , or maintenance of any of the System connection kits could damage the System and may result in inadequate performance, overheating, electric shock, or fire. To minimize these risks and to ensure that the System performs reliably, read and carefully follow the information, warnings, and instructions in this special attention to the following: Important instructions are marked Important Warnings are marked WarnIng3raychem-Im-h58033-XlTracePipeFre ezeProtectionCOm-en 18/011 general approvalsXL- trace heat-tracing systems carry agency approvals for the different applications shown in Section For detailed information on which approvals are carried for the specific applica-tion, refer to the Pipe freeze Protection and Flow Maintenance design guide (H55838).

10 WarrantyThermal Management standard limited warranty applies to all extension of the limited warranty period to ten (10) years from the date of Installation is available if a properly completed online warranty form is submit-ted within thirty (30) days from the date of installa-tion. You can access the complete warranty on our web site at 18/012 Installation heating Cable Storage Store the heating cable in a clean, dry location. Temperature range: 0 F ( 18 C) to 140 F (60 C).