1 REACTV ariable-flow commissioning damperQUICK FACTS Damper for flow regulation Rapid access to readings via the controller display Simple to commission Can be easily anti-condensation insulated in the duct system A factory-insulated model is available for circular duct connection circular connections: 100-630 mm Rectangular connections: 200x200-1600x700 Other rectangular sizes are also available on request Master/slave control has to have the same dimension Variants: Standard analogue signal Modbus control Spring return type motor F L O W R A N G EREACTMin.
2 *Max. (nom.)Sizel/sm3/hl/sm3/h1005186222312593 3102367160165817663420025902801008250401 4 44561642315632277302628400102367120 0432050016459018506660630300108028921041 0*The minimum flow varies, see page 6 for more informationREACT2 Swegon reserves the right to alter speci cations. 20180705 ContentsTechnical description ..3 Design ..3 Features ..3 Materials and surface treatment ..3 Accessories ..3 Commissioning and maintenance ..3 Environment ..3 Planning ..4 General ..4 Control ..4 Electrical data.
3 4 Control Example ..4 Slave control - Example ..4 Installation ..5 Installation circular version ..5 Installation rectangular version ..5 Technical data ..6 Air flows all versions ..6 Measurement accuracy all versions ..6 Sound data circular version ..6 Air flows circular version ..6 Sound power in octave bands ..6 Transmitted sound through uninsulated casing ..6 Transmitted sound through insulated casing - IR ..6 Engineering graphs circular , all versions ..7 Air flows and measures rectangular version.
4 9 Engineering graphs rectangular version ..9 Dimensions and weights ..10 Ordering key ..12 Product designation ..12 Accessories ..12 Specification example ..12320180705 Swegon reserves the right to alter speci 3. REACT CU, for slave control of REACT 0-10 V 4. Accessories. 1. RTC room thermostat. 2. DETECT Quality carbon dioxide- and temperature sensor. 3. DETECT Occupancy occupancy 1. REACT , circular and rectangular 2. REACT , rectangular design. Explanations of figure 2:1. Mode Edit wheel.
5 3. Gear release button. Technical descriptionDesign Variable-flow commissioning damper with control and measure-ment function Equipped with a compact regulator (motor included). REACT and REACT MB with compact controller. REACT GUAC with spring return actuator and separate controller. The controller has a display enabling direct reading. Easy commissioning and handling without the need for a sepa-rate hand unit. All you need is screw driver. Available in the following designs: circular version Rectangular version With Modbus With spring return actuatorFeatures Intended for heated spaces (0 - 50 C).
6 Storage and transportation, -20 - 50 C Ductwork Leakage Classes in accordance with SS-EN 1751 Leakage class C to the surroundings. circular version: class 4, closed damper Rectangular version: class 3, closed damper Air flow is measured over one or more measuring rods. All settings are displayd in actual values. Changes of min. and max flows are made directly in the control-ler through potentiometers. Distance inbetween the motor shelf and the damper (30 mm) is dimensioned for easy condensation isolation in duct systems.
7 Running time open/close (90 degrees): 5 Nm - 100 s 10 Nm - 150 s 15 Nm - 150 s Spring return actuator, running time electricity: 5 Nm - 100 s 10 Nm - 150 s Running time spring max 20 s (90 degrees)Materials and surface treatment All sheet metal parts are made of galvanised sheet steel. Measurement rods are of extruded RTC Room thermostat for temperature control of a room, (connects to the REACT regulator). DETECT Quality Carbon dioxide sensor with integrated tempera-ture sensor, for either room or duct installation.
8 DETECT Occupancy Presence detector for switching to mini-mum air flow when a room is unoccupied or two-flow control min-max. REACT CU Sensor unit for slave control of one or more REACT units. 0-10 V signal only. FSR Clamp/quick fit connector for simple dismantling when cleaning a circular and maintenanceSee the separate commissioning of construction materials is available from 123227 VMMade in Germany24 VAC/DC 50/60 +50 C IP 42 Edit10 VnomFlowVminVmaxTestModeAdrDo notopenI/sTe stm /h31234 VnomFlowVminVmaxTestModeAdrI/sTe stm /h3 REACT4 Swegon reserves the right to alter speci cations.
9 20180705 PlanningGeneral Designed for demand-controlled ventilation in rooms with variable loads. Intended for comfort ventilation. Humid, cold or aggressive environments should be avoided. Environmental and/or air temperatures should be within 0 - 50 C. Can be installed in both supply and extraxt air systems. Pressure-independent but requires a minimum air flow equivalent to the open damper pressure drop to fun-ction properly. Factory calibrated with a nominal air flow (Qnom) When carrying out design work, the minimum air flow required by REACT has to be taken in to Controlled by heat, carbon dioxide or occupancy.
10 The factory setting is always 0-100% = 0 l/s Qnom. Can be forced controlled to: maximum and minimum air flow. fully open or fully closed damper When used for slave control, slave and master units must be of the same dimension. Can be used as a constant flow damper. (Qmax= 0 and Qmin = desired constant flow) Delivered with 0 - 10V set value and actual value signal. Adjustable to 2 - 10V set value and actual value signal. REACT can be analogically connected to Building Management Systems (BMS) Possible to obtain with Modbus control Possibility to obtain REACT with spring return dataNOTE: To obtain the correct functionality of the control and regulating equipment it is of great importance that all interconnected regulating equipment has the same voltage24 VDC/24 VAC , 50-60 HzPower consumption, for transformer rating.