Example: confidence

SDT Static Dissipative Tile - Armstrong Flooring

SDT Static Dissipative Tile Armstrong SDT is part of a complete Flooring system designed to control Static in most nonexplosive manufacturing and working areas. SDT dissipates Static charges away from people and equipment in order to increase personal comfort and safety and help prevent sensitive equipment damage. In addition to Static control, SDT offers the practical benefits of VCT, including durability, ease of maintenance and low installed cost. Post-installation electrical properties can be evaluated by a qualified third party. Contact your Armstrong representative for details.

Material, Pattern and Colors A composition of polyvinyl chloride resin, plasticizers, stabilizers, fillers, pigmentsand antistatic additive. Colors

Tags:

  Material, Static, Ielts, Dissipative, Sdt static dissipative tile

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SDT Static Dissipative Tile - Armstrong Flooring

1 SDT Static Dissipative Tile Armstrong SDT is part of a complete Flooring system designed to control Static in most nonexplosive manufacturing and working areas. SDT dissipates Static charges away from people and equipment in order to increase personal comfort and safety and help prevent sensitive equipment damage. In addition to Static control, SDT offers the practical benefits of VCT, including durability, ease of maintenance and low installed cost. Post-installation electrical properties can be evaluated by a qualified third party. Contact your Armstrong representative for details.

2 SDT is styled and constructed for use in light industrial, education and office applications, including computer classrooms and repair labs as well as electronic testing facilities. 51953 pearl white 51950 marble beige 51951 armor gray SDT provides Static Dissipative protection using a complete 4-part system. These components must be used together to obtain the Static Dissipative performance requirements. 1. Tile with integral Static Dissipative elements 2. S-202 Static Dissipative adhesive 3. Copper grounding strips 4. S-392 Static Dissipative polish 51954 sandstone beige 51956 fossil gray 51955 moss green Visit / commercial Call 1 888 Armstrong .

3 Specialty Flooring SDT Static Dissipative Tile Specification Data material , Pattern and Colors Comparative Subjective Property Ratings tile; individuals removing tile and/or adhesive should A composition of polyvinyl chloride resin, plasticizers, Durability Very Good wear cotton gloves and follow the general practices stabilizers, fillers, pigments and antistatic additive. Colors Maintainability Good outlined in the current edition of the Resilient Floor and pattern are dispersed uniformly throughout the Resilience Good Covering Institute (RFCI) publication Recommended Work thickness of the material .

4 Color pigments are insoluble Practices for the Removal of Resilient Floor Coverings. in water and resistant to cleaning agents and light. Subjective ratings (excellent, very good, good, fair) are The tile should be disposed of in accordance with in relation to other Armstrong commercial resilient normal procedures for nonasbestos floor tile. If Size (nominal) floors. Ratings are not directly related to any one test. Armstrong SDT (an individual tile, for example) is 12 in. x 12 in. (305 mm x 305 mm) They are broadly based on tests and experience of broken, damaged, or in need of repair and requires Armstrong Research and Development under varying replacement, it must be replaced with SDT in order Gauge (nominal thickness) conditions and circumstances.

5 These ratings should to continue to provide Static Dissipative properties. 1/8 in. ( mm) not be used for comparison to ratings used by other manufacturers to rank their own products. MAINTENANCE. Limitations Note: See surface water instructions under Limitations.. SDT should not be used in the following areas: Fire Test Data Note: If electrical certification of an installation is n Munitions facilities. ASTM E 648 Flooring Radiant Panel Critical Radiant required, do not perform any maintenance procedures n Facilities containing explosives or explosive materials. Flux watts/cm2 or more, Class I until after that certification has been completed.

6 N Areas requiring conductive Flooring . ASTM E 662 Smoke Chamber Specific Optical Smoke n Hospital operating rooms. Density 450 or less Initial Maintenance Immediately After Installation n Heavy industrial and exterior areas. a. Sweep or vacuum thoroughly. n Commercial kitchens and commercial food Numerical flammability ratings alone may not define the b. Damp mop with a dilute neutral detergent solution processing areas. performance of the product under actual fire conditions. such as Armstrong S-485 Floor Cleaner carefully n Where pointed spikes such as golf or track shoes will These ratings are provided only for use in the selection wiping up black marks and excessive soil.

7 Be used. of products to meet the specified limits. c. Apply a minimum of three coats of Armstrong S-392. n Where the floor will be subjected to unusually floor polish. S-392 IS THE REQUIRED POLISH. concentrated Static or dynamic loads. Electrical Properties FOR USE WITH SDT. Other polishes will interfere n Do not install SDT in areas subjected to excessive Installed as a system using the required adhesive, with the electrical properties and/or the appearance surface water, such as areas where frequent spills grounding strips and polish, SDT yields the following of this Flooring .

8 Are common. Excessive and/or prolonged exposure electrical properties: d. Do not wash or scrub the floor for at least four to five to surface water may interfere with the bond of SDT Resistance: days after installation. to the subfloor. If a surface spill occurs, it must be and ASTM F-150. contained and removed immediately. Point to point and point to ground: 106 to 109 ohms Preparation for Commercial Use Static Generation: For specific, ongoing maintenance procedures see Suitable for Application Over ESD STM ( Flooring in combination with Armstrong Commercial Resilient Flooring Maintenance n Concrete subfloors which are suspended, on grade footwear and a person) Recommendations booklet, F-8663B.

9 Or below grade. at 40% with ESD shoes: <10 volts n Suspended wood subfloor construction with at 12% with ESD shoes: <100 volts WARRANTIES. approved wood underlayments, and a minimum of Static Decay: Armstrong warrants its regular (first quality) commercial 18 in. ( cm) well-ventilated air space below. Flooring in combination with footwear (ESD shoes) floors and wall base to be free from manufacturing n Radiant-heated subfloors with a maximum surface and a person (5000 volts to zero): seconds avg. defects and warrants the installation integrity for five temperature of 85 F (29 C).

10 Fed. Test 101C, Method 4046 (5000 volts to zero): years from the date of purchase, if installed according < seconds to the Armstrong Installation /Maintenance Tip Sheet, Unsuitable for Application Over F-7903. This warranty extends only to the original n Existing resilient Flooring , ceramic, marble, terrazzo, INSTALLATION end-user. See Armstrong Commercial Floor Warranty, metal or other nonporous substrates. Job Conditions F-3349 or visit for warranty details, n Subfloors where excessive moisture or alkali is present. Subfloors/underlayments shall be dry, clean, and smooth.


Related search queries