Example: confidence

SECTION Fuel Systems

Principles and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel Fuel NFIP Fuel Storage Calculation of Buoyancy Fuel Lines, Gas Meters, Control : An outline of a fuel system with the fuel tank elevated on a platform beside a house on a crawl space in a flood-prone : A fuel tank elevated above the DFE on a platform in a velocity flow area : A fuel tank elevated on structural : An underground fuel tank anchored to a concrete : An underground fuel tank anchored onto poured-in-place concrete : A typical tie down strap configuration of a horizontal propane tank using : A typical tie down configurati

This chapter applies to new and substantially improved structures that must be built in compli- ... of fire, explosion, water supply contamination, and possible health and envi- ... strapping the tank onto a concrete slab at the top of the raised ground. Figure 3.2.3B shows a tank located atop fill. Figure 3.2.3A: A fuel tank elevated above

Tags:

  Chapter, Water, Ground

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of SECTION Fuel Systems

1 Principles and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel Fuel NFIP Fuel Storage Calculation of Buoyancy Fuel Lines, Gas Meters, Control : An outline of a fuel system with the fuel tank elevated on a platform beside a house on a crawl space in a flood-prone : A fuel tank elevated above the DFE on a platform in a velocity flow area : A fuel tank elevated on structural : An underground fuel tank anchored to a concrete : An underground fuel tank anchored onto poured-in-place concrete : A typical tie down strap configuration of a horizontal propane tank using : A typical tie down configuration of a horizontal propane tank using : Tank lifted by buoyancy : Flow chart of buoyancy force : The vertical runs of fuel piping strapped against vertical non-breakaway.

2 The vertical runs of fuel piping embedded in utility shafts strapped to non-breakaway : Flow chart of flood resistant fuel system : Summary of NFIP : Effective equivalent fluid weight of soil(s) : Soil type definitions based on USDA Unified Soil : Checklist for flood resistant fuel system : Calculation of buoyancy force exerted on a tank (tank buoyancy) : Calculation of net buoyancy : Calculation of number of hold down : Calculation of the volume of concrete necessary to resist : Calculation of allowable load for tank and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel Fuel IntroductionThe components of the fuel Systems in residential and non-residential struc-tures can be organized into two storage lines, meters, and control panelsThere are four major concerns when considering the protection of fuel sys-tem components.

3 They are: Buoyancy Impact Loads Scour of lines Movement of ConnectionThe tank shown in Figure is shown outside of the building. This typeof installation is not the typical installation for all applications. Some tanksmay be located inside a structure to provide additional protection from dam-age during general, the figures in this chapter attempt to illustrate some general prac-tices that meet the requirements of the National Flood Insurance Program(NFIP). Local codes permit many variations that also meet NFIP regula-tions. Please refer to your local code officials for specific practices that maymeet both NFIP regulations and local NFIP RequirementsThe NFIP requires that the fuel system for a new or substantially improvedstructure located in a Special Flood Hazard Area (SFHA) be designed sothat floodwaters cannot infiltrate or accumulate within any component ofthe system.

4 See Table for a summary of compliant mitigation chapter applies tonew and substantiallyimproved structures thatmust be built in compli-ance with the minimumrequirements of theNFIP. Many of thestructures that werebuilt prior to the adop-tion of floodplain man-agement regulations bycommunities havebuilding utility systemsthat are not resistant toflood damages. For ad-ditional information onhow to protect buildingutility Systems in thesestructures, see Chapter4 on Existing and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel SystemsFigure.

5 An outline of a fuel system with the fuel tank elevated on a platform beside a house on a crawl space in a flood-prone areaPrinciples and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel refers to the location of a component above the DesignFlood Elevation (DFE). Protection refers to the implementation of design tech-niques that protect a component or group of components located be-low the DFE from flood damage by preventing floodwater from en-tering or accumulating within the system Fuel Storage TanksWhere a structure is not connected to public gas service, the fuel for a non-electric Heating, Ventilating, and Air Conditioning (HVAC) system and othernon-electric equipment is stored on-site in tanks either underground or aboveground and inside or outside the building.

6 Most modern commercial fueltanks are of double-walled construction while most residential fuel tanks areof single-walled construction. The type of construction of the tank should bedetermined as some of the techniques may not apply to some types of underground and above ground fuel storage tanks are vulnerable todamage by floodwaters, as illustrated by the following: An underground tank surrounded by floodwaters or saturated soil willbe subjected to buoyancy forces that could push the tank upward. Suchmovement of a tank may cause a rupture and/or separation of the con-necting pipes.

7 Above ground tanks in V Zones and A Zones that experience velocityflow are not only subject to buoyancy forces, but they are also exposedto lateral forces caused by velocity flow, wave action, and debris : Summary of NFIP regulations*Allowed only for those items required to descend below the DFE for service of MitigationA ZonesV Zones1. ElevationHighly RecommendedMinimum Requirement2. Component ProtectionMinimum RequirementNot Allowed*Refer to manufactur-ers literature and pro-fessional tank installersfor information regard-ing the proper installa-tion of fuel Design FloodElevation (DFE)

8 Is aregulatory flood ele-vation adopted by acommunity that isthe BFE, at a mini-mum, and may in-clude freeboard, asadopted by the and Practices for the Design and Construction of Flood Resistant Building Utility SystemsNovember and Substantially Improved BuildingsFuel Systems An underground tank in a V Zone can be uncovered and exposed byerosion and scour, making it even more vulnerable to buoyancy forces,velocity flows, wave action, and debris is described in detail later in this SECTION . The effects of buoyancyand/or those of velocity flow can move a tank from its location, break itopen, and cause fuel leakage into floodwaters.

9 Such leakage creates the riskof fire, explosion, water supply contamination, and possible health and envi-ronmental hazards which would delay cleanup and repair work necessary tooccupy the most effective technique for providing flood protection for a fuel storagetank is elevation of the tank on a platform above the DFE. Figure showsa tank on an elevated platform. The depth of the footing will be dependentupon the hazards at the site. The following outlines some additional consider-ations when protecting fuel Systems : The tank should be anchored to the platform with straps, which wouldconstrain the tank in wind, earthquake, and other applicable forces.

10 In coastal zones, the straps should be made of non-corrosive material toprevent rusting. In velocity flow areas, the platform should be supported by posts or col-umns that are adequately designed for all loads including flood and windloads. The posts or columns should have deep concrete footings embedded be-low expected erosion and scour lines. The piles, posts, or columns should be cross-braced to withstand the forc-es of velocity flow, wave action, wind, and earthquakes; cross-bracingshould be parallel to the direction of flow to allow for free flow of debris.