SENTRON communication manual - Siemens

SENTRON VL Moulded-Case Circuit-BreakerElectronic Trip Unit (ETU/LCD)COM10 PROFIBUS Module incl. ZSiBreaker Data Adapter (BDA)BDA Plus with Ethernet InterfaceDevice with web-browser (e. g. notebook) SENTRON WL Circuit BreakerCOM15 PROFIBUS ModuleBreaker Status Sensor (BSS) Electronic Trip Unit (ETU)Metering Function or Metering Function PlusZSI (Zone-Selective Interlocking) ModuleDigital Output Module as Relay or Opto-CouplerDigital Output Moduleas Relay or Opto-Coupler *, ConfigurableAnaloge Output ModuleDigitale Input ModuleSwitch ES Power on PCPLC ( SIMATIC S7)Power Management SoftwareTechnological leader amongstthe circuit-breakers:SENTRONC ommunication1234567891011121314151617181 9 SENTRON communication manual 1. Edition SENTRON communication manualSubject to change without prior 10/03 | Bestell-Nr.

Introduction and Overview SENTRON WL SENTRON VL PROFIBUS Profile SENTRON WL und SENTRON VL Switch ES Power Breaker Data Adapter (BDA) Breaker Data Adapter Plus (BDA Plus) Data Dictionary

Tags:

  Manual, Siemens

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SENTRON communication manual - Siemens

1 SENTRON VL Moulded-Case Circuit-BreakerElectronic Trip Unit (ETU/LCD)COM10 PROFIBUS Module incl. ZSiBreaker Data Adapter (BDA)BDA Plus with Ethernet InterfaceDevice with web-browser (e. g. notebook) SENTRON WL Circuit BreakerCOM15 PROFIBUS ModuleBreaker Status Sensor (BSS) Electronic Trip Unit (ETU)Metering Function or Metering Function PlusZSI (Zone-Selective Interlocking) ModuleDigital Output Module as Relay or Opto-CouplerDigital Output Moduleas Relay or Opto-Coupler *, ConfigurableAnaloge Output ModuleDigitale Input ModuleSwitch ES Power on PCPLC ( SIMATIC S7)Power Management SoftwareTechnological leader amongstthe circuit-breakers:SENTRONC ommunication1234567891011121314151617181 9 SENTRON communication manual 1. Edition SENTRON communication manualSubject to change without prior 10/03 | Bestell-Nr.

2 E20001-A210-P307-X-7600 | Dispostelle 27604 | 10815596 | Siemens 2003 | Printed in GermanyThe information provided in [this brochure/product catalog,etc.] containsmerely general descriptions or characteristicsof performance which in case of actual use do not alwaysapply as described or which may change as a result offurther development of the products. An obligation toprovide the respective characteristics shall only exist ifexpressly agreed in the terms of manual forcommunication capable SENTRON WL andSENTRON VL circuit breakersentronSiemens and DrivesLow voltages switch gear for energy Box 3240, 91050 Erlangen, Germanyss12345678101112131415161719918*) only a max. of 2 digital output module can be used ag Ihr Ansprechpartner: Frau Hanek, 39 00-163 NS: P64275: sn, siemens1 Siemens1_Auftr ge A&D MK 2003 08/2003 66809 FrameMaker SENTRON 66809 Buchh Buchh 14:08 Uhr Seite 2 SENTRON VL Moulded-Case Circuit-BreakerElectronic Trip Unit (ETU/LCD)COM10 PROFIBUS Module incl.

3 ZSiBreaker Data Adapter (BDA)BDA Plus with Ethernet InterfaceDevice with web-browser (e. g. notebook) SENTRON WL Circuit BreakerCOM15 PROFIBUS ModuleBreaker Status Sensor (BSS) Electronic Trip Unit (ETU)Metering Function or Metering Function PlusZSI (Zone-Selective Interlocking) ModuleDigital Output Module as Relay or Opto-CouplerDigital Output Moduleas Relay or Opto-Coupler *, ConfigurableAnaloge Output ModuleDigitale Input ModuleSwitch ES Power on PCPLC ( SIMATIC S7)Power Management SoftwareTechnological leader amongstthe circuit-breakers:SENTRONC ommunication1234567891011121314151617181 9 SENTRON communication manual 1. Edition SENTRON communication manualSubject to change without prior 10/03 | Bestell-Nr. E20001-A210-P307-X-7600 | Dispostelle 27604 | 10815596 | Siemens 2003 | Printed in GermanyThe information provided in [this brochure/product catalog,etc.]

4 ] containsmerely general descriptions or characteristicsof performance which in case of actual use do not alwaysapply as described or which may change as a result offurther development of the products. An obligation toprovide the respective characteristics shall only exist ifexpressly agreed in the terms of manual forcommunication capable SENTRON WL andSENTRON VL circuit brakersentronSiemens and DrivesLow voltages switch gear for energy Box 3240, 91050 Erlangen, Germanyss12345678101112131415161719918*) only a max. of 2 digital output module can be used ag Ihr Ansprechpartner: Frau Hanek, 39 00-163 NS: P64275: sn, siemens1 Siemens1_Auftr ge A&D MK 2003 08/2003 66809 FrameMaker SENTRON 66809 Buchh Buchh 14:08 Uhr Seite 2 Introduction and OverviewSENTRON WLSENTRON VLPROFIBUS ProfileSENTRON WL und SENTRON VLSwitch ES PowerBreaker Data Adapter (BDA)Breaker Data Adapter Plus (BDA Plus)Data Dictionary66809 Englisch Seite 4 Dienstag, 14.

5 Oktober 2003 11:45 11 Safety guidelines This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of that death, severe personal injury or substantial property damage will result if proper precautions are not that death, severe personal injury or substantial property damage can result if proper precautions are not that minor personal injury or property damage can result if proper precautions are not your attention to particularly important information on the product, handling the product, or to a particular part of the personnelOnly qualified personnel should be allowed to install and work on this equipment.

6 Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and usageNote the following:WarningThis device and its components may only be used for the applications described in the catalogue or the techni-cal descriptions, and only in connection with devices or components from other manufacturers which have been approved or recommended by product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as , SIMATIC HMI , SIMATIC NET und SENTRON are Brands of Siemens AG. Some other designations used in these documents are also brands; the owner's rights may be violated if they are used by third parties for their own AGBereich Automatisierungs- und AntriebstechnikGesch ftsgebiet Niederspannungs-SchalttechnikD-91050 ErlangenSiemens Aktiengesellschaft Siemens AG 2003 Technical data subject to change without Siemens AG 2003 All rights reservedThe reproduction, transmission or use of this document or its con-tents is not permitted without express written authority.

7 Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are of liabilityWe have checked this manual to ensure that its contents are correctand applicable in relation to the hardware and software it all our endeavors, however, discrepancies cannot be whollyexcluded and so we cannot guarantee complete correctness andapplicability. However, the data in this manual are reviewed regularlyand any necessary corrections included in subsequent editions. Sug-gestions for improvement are Assistance:Telephone: +49 (0) 9131-7-43833 (8 16 MEZ)Fax: +49 (0) 9131-7-42899E-mail: Support:Telephone: +49 (0) 180 50 50 22266809 Englisch Seite 6 Dienstag, 14.

8 Oktober 2003 11:45 11 Additional system manuals and technical books:More information about the technical backgrounds and tips to use and configure PROFIBUS-DP using STEP 7 you find in the Technical book: Weigmann, Josef; Kilian, Gerhard; Decentralization with PROFIBUS-DP; Architecture and Fundamentals,Configuration and Use of PROFIBUS-DP with SIMATIC S7; 2000, ISBN 3-89578-144-4 Informations on the selection criteria for low voltage switchgear in main circuits, installation and operation can be found in: Siemens -Aktiengesellschaft, Berlin und Munich. Authors: Petra Belzner .. Ed. Georg Sch llhorn. Transl. JanDomisse; Switching, protection and distribution in low-voltage networks; 2. rev. ed.; Publicis-MCD-Verl. 1994 For more information regarding the SENTRON WL circuit breaker please refer to the Operating Instructions; Order No.

9 : 3ZX1812-0WL00-0AN0 Further information around the PROFIBUS can be found in: Profibus User Organization; Version October 2002; PROFIBUS Technology and Application, System Descripition;Order No. ; download under Profibus User Organization; Version , December 2002; PROFIBUS profile for Low Voltage Switchgear; Onlyavailable as Acrobat PDF file, only for PROFIBUS members, download under Profibus User Organization; Version September 1998; PROFIBUS Technical Guideline, Installation Guideline for PROFIBUS-DP/FMS; Order No. ; Only available as Acrobat PDF file, only for PROFIBUS members, downloadunder Englisch Seite 7 Dienstag, 14. Oktober 2003 11:45 1166809 Englisch Seite 1 Dienstag, 14. Oktober 2003 11:45 11 Introduction and OverviewContent of the ManualOverview of the Bus SystemsCommunication with circuit breaker66809 Englisch Seite 2 Dienstag, 14.

10 Oktober 2003 11:45 111-1 Introduction and OverviewGeneralThis manual is aimed at those who want to find out more about the different applications of communications-capable circuit-breakers in power distribution systems. It contains a detailed guide to commissioning, operating, diagnosing, and maintaining the new communications-capable SENTRON WL and SENTRON VL of the ManualChapter 1 contains a short introduction to communication in power distribution systems, and provides an overview of the benefits and applications of communications- capable circuit-breakers. The chapter concludes with a short description of the most important bus 2 contains a detailed description of the open, communications-capable SENTRON WL circuit-breaker. It includes information on the ordering and configuration data, and provides commissioning 3 contains the same information, but this time on the moulded-case communications- capable SENTRON VL 4 explains how the SENTRON circuit-breakers are integrated in a PROFIBUS-DP system, and describes the joint profile of both circuit- breakers for the PROFIBUS-DP profile is described in Chapter 4.