1 1 of 6 MArch, 2007 TFP342_ENGeneral Description The 160 K-factor, Series ELO-231B , Standard Response, Standard Coverage, Upright and Pendent Sprinklers (Ref. Figure 1) are auto-matic sprinklers of the frangible bulb type. They are standard response - spray sprin-klers that produce a hemispherical water distribution pattern below the deflector. The K160, ELO-231B Sprinklers were sub-jected to full scale, high-piled storage fire tests to qualify their use in lieu of 80 or 115 K-factor standard spray sprinklers for the protection of high-piled storage. Higher flow rates can be achieved at much lower pressures with the K160, ELO-231B Sprinklers making their use highly ad-vantageous in high density applications, such as the protection of high-piled stor-age.
2 Wax or lead coatings can be used to extend the life of the copper alloy components used in Series ELO-231B sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although wax, lead, and polyester coated sprinklers have passed the standard cor-rosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Con-sequently, it is recommended that the end user be consulted with respect to the suit-ability of these corrosion resistant coatings for any given corrosive environment. The effects of ambient temperature, concentra-tion of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
3 An upright intermediate level version of the Series ELO-231B Sprinklers for in-rack ap-plications can be obtained by utilizing the Series ELO-231B Upright Sprinkler with the WSG-2 Guard & Shield, and a pendent in-termediate level version of the Series ELO-231B Sprinklers can be obtained by utiliz-ing the Series ELO-231B Pendent Sprinkler with the WS-2 Shield. If there is a possibility of the pendent intermediate level version being exposed to mechanical damage, a G-2 Guard can be K160, Series ELO-231B Upright and Pen-dent Sprinklers described herein must be in-stalled and maintained in compliance with this document, as well as with the applicable standards of the National fire Protection As-sociation, in addition to the standards of any other authorities having jurisdiction.
4 Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contrac-tor or manufacturer should be contacted with any questions. Installation of Series ELO-231B Pendent Sprin-klers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the sprinkler s Approvals and/or Listings. IMPORTANTA lways refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can perma-nently damage a sprinkler system or its components and cause the sprin-kler to fail to operate in a fire situa-tion or cause it to operate ELO-231B 160 K-factor Upright and Pendent Sprinklers Standard Response, Standard CoverageGeneralDescriptionThe K-factor, Series ELO-231B ,Standard Response, Standard Cover-age, Upright and Pendent Sprinklers(Ref.)
5 Figure 1) are automatic sprin-klers of the frangible bulb type. Theyare standard response - spray sprin-klers that produce a hemisphericalwater distribution pattern below the K-factor, ELO-231B Sprin-klers were subjected to full scale, high-piled storage, fire tests to qualify theiruse in lieu of or K-factor stand-ard spray sprinklers for the protectionof high-piled flow rates can be achieved atmuch lower pressures with the , ELO-231B Sprinklers making their use highly advantageousin high density applications, such asthe protection of high-piled or lead coatings can be used toextend the life of the copper alloy com-ponents used in Series ELO-231 Bsprinklers beyond that which wouldotherwise be obtained when exposedto corrosive atmospheres.
6 Althoughwax, lead, and polyester coated sprin-klers have passed the standard corro-sion tests of the applicable approvalagencies, the testing is not repre-sentative of all possible corrosive at-mospheres. Consequently, it is recom-mended that the end user be consultedwith respect to the suitability of thesecorrosion resistant coatings for anygiven corrosive environment. The ef-fects of ambient temperature, concen-tration of chemicals, and gas/chemicalvelocity, should be considered, as aminimum, along with the corrosive na-ture of the chemical to which the sprin-klers will be upright intermediate level versionof the Series ELO-231B Sprinklers forin-rack applications can be obtainedby utilizing the Series ELO-231B Up-right Sprinkler with the WSG-2 Guard& Shield, and a pendent intermediatelevel version of the Series ELO-231 BSprinklers can be obtained by utiliz-ing the Series ELO-231B PendentSprinkler with the WS-2 Shield.
7 If thereis a possibility of the pendent interme-diate level version being exposed tomechanical damage, a G-2 Guard canbe K-factor, Series ELO-231 BUpright and Pendent Sprinklers de-scribed herein must be installed andmaintained in compliance with thisdocument, as well as with the applica-ble standards of the National fire Pro-tection Association, in addition to thestandards of any other authorities hav-ing to do so mayimpair the performance of these owner is responsible for maintain-ing their fire protection system and de-vices in proper operating installing contractor or manufac-turer should be contacted with of Series ELO-231B Pen-dent Sprinklers in recessed escutch-eons will void all sprinkler warranties,as well as possibly void the sprinkler sApprovals and/or ELO-231B K-factorUpright and Pendent SprinklersStandard Response, Standard CoveragePage 1 of 6 TFP342 JANUARY, 2005 Technical Services:Tel: (800) 381-9312 / Fax.
8 (800) 791-5500 IMPORTANTA lways refer to Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate 2 of 6 TFP342_ENModel/Sprinkler Identification NumbersTY5151 - Upright K160, 3/4 NPTTY5251 - Pendent K160, 3/4 NPTTY5851 - Upright K160, 1/2 NPTTY5151 is a redesignation for is a redesignation for C5251, G1871, and is a redesignation for Data ApprovalsUL and C-UL Listed. FM and NYC Approved.(Refer to Table A for complete approval information including corrosion resistant status.)
9 The approvals apply to the service conditions indicated in the Design Criteria section.)Maximum Working Pressure12,1 bar (175 psi)Discharge Coefficient161,4 ,5 ( usgpm/psi0,5)Temperature RatingsRefer to Table AFinishRefer to Table APhysical CharacteristicsFrame ..BronzeCap ..BronzeSealing Assembly ..Beryllium Nickel w/Teflon*Bulb (5mm dia.) ..GlassCompression Screw ..BronzeDeflector ..Bronze*Registered trademark of DuPont. Design CriteriaUL and C-UL Listing Requirements The K160, Model ELO-231B (TY5151, TY5251 & TY5851) Sprinklers are to be installed in accordance with NFPA 13 standard sprin-kler position and area/density flow calcula-tion requirements for light, ordinary, or ex-tra hazard occupancies as well as high piled storage occupancies (solid piled, palletized, rack storage, bin box, and shelf storage including but not limited to Class I-IV and Group A plastics) with a minimum residual (flowing) pressure of 0,5 bar (7 psi) for wet or dry pipe systems.
10 FM Approval Requirements The K160, Model ELO-231B (TY5151, TY5251 & TY5851) Sprinklers are to be installed in accordance with the applicable control mode density/area guidelines provided by Factory Mutual. (FM guidelines may differ from UL and C-UL Listing criteria.)SPRINKLER FINISH TYPETEMPERATUREBULB LIQUIDNATURAL BRASSCHROME-PLATEDLEAD COATEDWAX COATEDWAX OVER LEADUPRIGHT (TY5151 & TY5851)68 C (155 F)Red1,2,3,4393 C (200 F)Green141 C (286 F)Blue33(a)PENDENT (TY5251)68 C (155 F)Red1,2,3,4393 C (200 F)Green141 C (286 F)Blue33(a)NOTES:1. Listed by Underwriters Laboratories, Inc. (UL Listed).2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed).3. Approved by Factory Mutual Research Corporation (FM Approved).4.