SITRANS F M MAGFLO - Lesman

Order no.: F M MAGFLO Electromagnetic flowmetersTransmitter type MAG 6000 19" &safety barrier [EEx ia/ib] IIBsensor type MAG 1100 Ex & MAG 3100 Ex[]*083R9171*Operating ManualsSITRANS F M MAGFLO of transmitter MAG 6000 .. of sensor .. installation - At the sensor .. installation - Transmitter in 19" insert .. survey according to Directive 94/9/EC (ATEX) .. and intrinsically safe data .. conditions for safe use .. 19 IP 20 version EEx (ia/ib) DN 300 .. 19 IP 20 version EEx e (ib) DN 350 .. 19 IP 66 version EEx (ia/ib) DN 300 .. 19 IP 66 version EEx e (ib) DN 350 .. MAG 6000 .. and weight MAG 1100 Ex .. Sensor MAG 1100 Ex .. and weight MAG 3100 Ex .. Sensor MAG 3100 Ex.

SITRANS F M MAGFLO®®®®® SFIDK.PS.026.C2.02 3 ENGLISH 1. Introduction For safety reasons it is important that the following points, especially the points marked with a warning sign, are read and understood before the system is being installed: • Installation, connection, commissioning and service must be carried out by personnel

Tags:

  Strain, Sitrans f m

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SITRANS F M MAGFLO - Lesman

1 Order no.: F M MAGFLO Electromagnetic flowmetersTransmitter type MAG 6000 19" &safety barrier [EEx ia/ib] IIBsensor type MAG 1100 Ex & MAG 3100 Ex[]*083R9171*Operating ManualsSITRANS F M MAGFLO of transmitter MAG 6000 .. of sensor .. installation - At the sensor .. installation - Transmitter in 19" insert .. survey according to Directive 94/9/EC (ATEX) .. and intrinsically safe data .. conditions for safe use .. 19 IP 20 version EEx (ia/ib) DN 300 .. 19 IP 20 version EEx e (ib) DN 350 .. 19 IP 66 version EEx (ia/ib) DN 300 .. 19 IP 66 version EEx e (ib) DN 350 .. MAG 6000 .. and weight MAG 1100 Ex .. Sensor MAG 1100 Ex .. and weight MAG 3100 Ex .. Sensor MAG 3100 Ex.

2 MAG 6000 .. barrier (ia/ib) DN 300 .. barrier (ia) DN 350 .. IS data sensor .. characteristics MAG 6000 .. and display layout .. Basic settings .. Outputs .. input .. Sensor characteristics .. Language mode .. check list .. shooting MAG transmitter .. of conformity .. type examination certificate .. 29 SITRANS F M MAGFLO safety reasons it is important that the following points, especially the points marked witha warning sign, are read and understood before the system is being installed: Installation, connection, commissioning and service must be carried out by personnelwho are qualified and authorized to do so. It is very important that the same people have read and understand the instructions anddirections provided in this manual and that they follow the instructions and directionsbefore taking the equipment into use!

3 People who are authorized and trained by the owner of the equipment may operate theequipment. The installation must ensure that the measuring system is correctly connected and isin accordance with the connection diagram. The transmitter has to be earthed unlessthe power supply is galvanically isolated. In applications with working pressures/media that can be dangerous to people,surroundings, equipment or others in case of pipe fracture, we recommend that specialprecautions such as special placement, shielding or installation of a security guard ora security valve should be made when the sensor is being installed. Siemens Flow Instruments want to assist by estimating the chemical resistance of thesensor parts that are in connection with the media, but it is at any time the customer sresponsibility, which materials are chosen and Siemens Flow Instruments takes noresponsibility if the sensor corrodes!

4 Equipment used in hazardous areas must be Ex-approved and marked for Europeand UL for is required that the special directions provided in the manual and in the Ex certificatemust be followed! Installation of the equipment must comply with national EN 60079-14 for Denmark. Repair and service can be done by approved Siemens Flow Instruments F M MAGFLO InstallationCategory 2 equipmentSensors may be installed in zone 1 and zone Installation of sensorTransmitter MAG 6000 can be installed in thesafe area only! Installation oftransmitter MAG6000 Safe area only!Hazardous areaThe sensor must always be completely full avoid: Installation at the highest point in the pipesystem Installation in vertical pipes with free outletFor partially filled pipes or pipes with down-ward flow and free outlet the flowmeter shouldbe located in a in vertical pipesRecommended flow direction: upwards.

5 Thisminimizes the effect on the measurement ofany gas/air bubbles in the F M MAGFLO in horizontal pipesThe sensor must be mounted as shown in theupper figure. Do not mount the sensor as shownin the lower figure. This will position the elec-trodes at the top where there is possibility for airbubbles and at the bottom where there is pos-sibility for mud, sludge, sand using empty pipe detection the sensor can betilted 45 , as shown in the upper abrasive liquids and liquids con-taining particlesRecommended installation is in a vertical/in-clined pipe to minimize the wear and depositsin the and outlet conditionsTo achieve accurate flow measurement it isessential to have straight lengths of inlet andoutlet pipes and a certain distance betweenpumps and is also important to centre the flowmeter inrelation to pipe flanges and Installation of sensor(continued)

6 Installation in large pipesThe flowmeter can be installed between tworeducers ( DIN 28545). Assuming that at 8 the following pressure drop curve applies. Thecurves are applicable to :A flow velocity of 3 m/s (V) in a sensor with adiameter reduction from DN 100 to DN 80(d1/d2 = ) gives a pressure drop of InstallationSITRANS F M MAGFLO Remote installation -At the sensorFit and connect the electrode and coil cablesas shown in chapter 7 Electrical connections in the unscreened cable ends must be kept asshort as electrode cable and the coil cable must bekept separate to prevent the cable glands well to obtain opti-mum the SENSORPROM unit from thesensor and mount it on the connection plate inthe Remote installation -Transmitter in 19"insert1.

7 Fit the SENSORPROM memory unit on the connection board supplied with the SENSORPROM unit is supplied with the sensor in the terminal Mount the guide rails into the rack system as shown. Distance between guide rails is 20 rails are supplied with the rack system and not with the Mount the connection board as Connect the cables as shown under "Electrical connection", chapter 7 in the Insert the transmitter into the rack F M MAGFLO Ex survey accordingto Directive 94/9/EC(ATEX)Applies to instruments used in underground miningoperations, as well as their above groundoperations, which can be endangered by mine gasand/or flammable groupsApplies to instruments used in the remaining areaswhich can be endangered by a potentially of this category are for use inareas where ignitable atmospheres, caused bya mixture of air and gasses, vapours or mists orby dust/air mixtures, can exist all of the time orfor long periods of time or else of this category are for use inareas where ignitable atmospheres caused, bya mixture of air and gasses, vapours or mists orby dust/air mixtures, can exist some of the of this category are for use inareas where ignitable atmospheres.

8 Caused bya mixture of air and gasses, vapours or mists orby dust/air mixtures, are not likely to , if they do occur then in all probability,only seldom or for short periods of category(The figures in brackets refer to IEC)Built according to European norm = EExplosion protected electrial equipment = ExEx protection labelling in square brackets refers to "Associated electrical equipment"as an example: II 2G E Ex ia IIB T3-T6 Type of protectiono Oil encapsulatediIntrinsic safety (ia, ib)p Pressurized apparatus nNon-incentive equipmentq Powder fillingm Encapsulationd Flameproof enclosuresSpecial protectione Increased safetyExplosion groupsGases and vapoursMinimumEN/(examples)ignitionIECen ergy [mJ] Ammonia-IIA Acetone, aircraft fuel, benzine,crude oil, diesel oil, ethane, ethanoicacid, ether, gasolines, heating oil,hexane, methane, Ethylene, isoprene, town Acetylene, carbon disulphide, temperature Maximum surface temperatureEN / IEC450 C842 FT1300 C572 FT2200 C392 FT3135 C275 FT4100 C212 FT585 C185 FT6 IIIEN 50014 Directive 94/9/EC (ATEX)Definition1G(0)

9 Labelling with gasesLabellingwith dusts1D(20)2G(1)2D(21)3G(2)3D(22) SITRANS F M MAGFLO Device identificationSensor MAG 1100 Ex orMAG 3100 Ex label2. InstallationCan only be installed in safe area!All MAG 1100 Ex and MAG 3100 Ex sensorshave the following ratings and input Overview andintrinsically safe dataMAG 6000 19" IP 20& IP 65 [EEx ia] IIBC ategory 2 equipmentSensors may be installed in zone 1 and zone intrinsically safe dataSee table 1100 & MAG 3100 EEx ia IIB barriersib coilia electrodeUo28 VIo138 mA40 WLo4 mH23 mHCo100 nF500 nFTerminals85-8682-83 MAG sensorcoilelectrodeUi28 V10 VIi140 mA50 mAPi2 WLi2 mH20 mHCi50 nF50 nFMAG 1100 DN 6 - 100 MAG 3100 DN 15 - 300 Ex ibTerminals85-8682-83 MAG sensorcoilelectrodeUi-10 VIi-50 WLi-20 mHCi-50 nFMAG 3100 DN 350 - 2000 Ex e iaIS data transmitterIS data sensorSpecifications:Supply: 115-230 V or 24 VAmbient temperature: 20 to 50 CEnclosure.

10 IP 20 or IP 65 SITRANS F M MAGFLO F M MAGFLO sensors carry the following approvalsMAG 1100 Ex for mounting in Ex areasDN 6 - DN 100 EEx [ia] [ib] IIB , II 2 (1)(2)SIRA 03 ATEX 1423X CE 0518 Temperature ratings are as follows:T4 (max. surface < 135 C) for liquid temperatures lower than 100 CT5 (max. surface < 100 C) for liquid temperatures lower than 82 CT6 (max. surface < 85 C) for liquid temperatures lower than 67 CFor an ambient temperature of 20 C to + 50 CMAG 3100 Ex for mounting in Ex areasDN 15 - DN 300 EEx-d [ia] [ib] IIB , II 2 (1)(2)SIRA 03 ATEX 1442X CE 0518 Temperature ratings are as follows*):T4 (max. surface < 135 C) for liquid temperatures lower than 100 CT5 (max. surface < 100 C) for liquid temperatures lower than 87 CT6 (max.