Smart level probe type APC-2000 ALW/L.. Programmable zero shift, range and damping ratio . mA output signal + HART protocol . Accuracy 0,16%.. Local display . Intrinsic safety certificate (ATEX, IECEx). II 1/2G Ex ia IIB T4/T5 Ga/Gb Ex ia IIB T4/T5 Ga/Gb IECEx II 1D Ex ia IIIC T105 C Da Ex ia IIIC T105 C Da 133 18 132 18. working temp.: +80 . Electronic part IP 66 / IP67. Mounting bracket . 4 holes 7. working temp.: +120 . (spacing of holes 38 38 mm). L (up to 25 m). Sensor type IP68. 141. 140. 25.. 25.. 14,5. 60.. Submersible sensor Submersible sensor Thread or flange mounted type type SGE-25 sensor. (Type of flange or thread has to be selected). V/ 10. APC-2000 ALW/L function: Application 4 20 mA output signal + HART protocol, The APC-2000 ALW/L level probe is applicable to measure liquid levels in tanks, deep wells or piezometers. Possibilities of the adjusting both zero point and of the start and end of the measuring range, characteristic The APC-2000 ALW/L probe is applicable to measure levels of the display panel keys, liquids containing contaminants or suspensions.

V/ 10 ˘25 140 ˘25 141 14,5 ˘60 L (up to 25 m) 133 18132 Smart level probe type APC-2000ALW/L Mounting bracket ÐÑ Submersible sensor type SGE-25.S Electronic part IP 66 / IP67 working temp.:

Tags:

  Types, Smart, Levels, Probes, Smart level probe type apc 2000alw, 2000alw

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Smart level probe type APC-2000ALW/L - …

1 Smart level probe type APC-2000 ALW/L.. Programmable zero shift, range and damping ratio . mA output signal + HART protocol . Accuracy 0,16%.. Local display . Intrinsic safety certificate (ATEX, IECEx). II 1/2G Ex ia IIB T4/T5 Ga/Gb Ex ia IIB T4/T5 Ga/Gb IECEx II 1D Ex ia IIIC T105 C Da Ex ia IIIC T105 C Da 133 18 132 18. working temp.: +80 . Electronic part IP 66 / IP67. Mounting bracket . 4 holes 7. working temp.: +120 . (spacing of holes 38 38 mm). L (up to 25 m). Sensor type IP68. 141. 140. 25.. 25.. 14,5. 60.. Submersible sensor Submersible sensor Thread or flange mounted type type SGE-25 sensor. (Type of flange or thread has to be selected). V/ 10. APC-2000 ALW/L function: Application 4 20 mA output signal + HART protocol, The APC-2000 ALW/L level probe is applicable to measure liquid levels in tanks, deep wells or piezometers. Possibilities of the adjusting both zero point and of the start and end of the measuring range, characteristic The APC-2000 ALW/L probe is applicable to measure levels of the display panel keys, liquids containing contaminants or suspensions.

2 A typical use for this probe is the measurement of levels of liquid waste in Configurable display 5 digits with illumination (working intermediate pumping stations, fermentation chambers, settling temperature range 40 +85 C) tanks etc. Because in submersible part of level probe is mount- ed only measuring sensor level probe can be use for measure- Electrical diagrams ment hot liquids max. 120 C. RS-HART converter Configuration Power supply or communicator The following metrological parameters can be configured: The units of pressure;. Start and end-points of set range;. 4 20 damping time constant;. mA. Milliammeter inverted characteristic (output signal 20 4 mA). Communication The communication standard for data interchange with the mA probe is the Hart protocol. Communication with the probe is carried out with: - KAP-03 communicator TEST TEST - Raport 2 software or other Hart communication devices.

3 Jumper SIGNAL. Transmitter 240 hm Measuring range No Nominal range Min. s et range Overpressure limit (FSO). 1 m H2O 2 m H2O m H2O. 2 m H2O 1 m H2O m H2O. 3 ,5 m H2O 0,5 m H2O m H2O. *other measuring ranges on request Technical data*. Metrological parameters Electrical parameters Accuracy 0,16%. L. Power supply VDC. Long-term stability 10 55 VDC (special version). 0,16% for 2 years L Additional voltage drop Thermal error when display illumination switched on 3V. < 0,1% (FSO) / 10 C Output signal mA 2-wires + Hart protocol max. 0,4% (FSO) in the whole compensation range Resistance required for communication min. 240 W. Thermal compensation range C U ZAS [V ] - 12V *. C special version R[W. ]=. Load resistance 0,0225 A. Output actualization time 0,5 s Additional electronic damping s * 15 V when display illumination switched on Error due to supply voltage changes 0,002% (FSO) / V Operating conditions Operating temperature range (ambient temp.)

4 C. * more information about technical data available Medium temperature range: in user 's manual. Version with polyurethane cable C. Version with PTFE shield C. Ordering code Model Code Description APC-2000 ALW/L Smart level probe /SGE-25 . Sensor type /SGE-25S .. /Exia .. II 1/2G Ex ia IIB T4/T5 Ga/Gb II 1D Ex ia IIIC T105 C Da Ex ia IIB T4/T5/T6 Ga/Gb Versions, certificates IECEx Ex ia I Ma /-40 80 C .. Compensation range C. /Teflon . Teflon cable shielding (T= m). Range Min. set range 0 2,5 m H2O 0 2,5 m H2O 0,5 m H2O. Nominal measuring range 0 10 m H2O 0 10 m H2O 1 m H2O. 0 20 mH2O 0 20 mH2O 2 m H2O. Measuring set range / [required units] Calibrated range in relation to 4mA and 20mA output Cable L= m Cable length (max. 25m). Accessories /PC Mounting bracket /F Flange type connection*. *sensor with thread or flange process connection. Avaliable are all process connections offered in Aplisens : M.

5 , G1/2'' , 1/2''NPT, CG1'', CM30, CG1/2''. and all flange connections acc. to chapter III in product catalogue V/ 11. Smart level probes and . Programmable zero shift, range and damping ratio Capillary . mA output signal + HART protocol . Accuracy Black ( ). Red (+).. Integrated internal overvoltage Capillary protection circuit II 1G Ex ia IIC T4/T5/T6 Ga Aplisens . ATEX Intrinsic safety II 1G Ex ia IIB T4/T5/T6 Ga (only for level Black ( ). Red (+). PP I M1 Ex ia I Ma probe with teflon cabel). NEW junction box Aplisens . Titanium version ( ). SG. cable hanger . Marine certificate DNV. Application The level probe is applicable to measure liquid levels in tanks, deep wells or piezometers. 1/2''NPT The probe is applicable to measure levels of liquids containing contaminants or suspensions. A typical use for this probe is the measurement of levels of liquid waste in intermediate pumping stations, fermentation cham- bers, settling tanks etc.

6 156. 25.. Principles of operation, construction The probe measures liquid levels , basing on a simple special relationship between the height of the liquid column Diaphragm option - SGM and the resulting hydrostatic pressure. The pressure measurement is carried out on the level of the separating level diaphragm of the immersed probe and is related to atmospheric pressure through a capillary in the cable. The active sensing element is a piezoresistant silicon sensor separated from the medium by an isolating plastic cup diaphragm. The electronic amplifier, which works in Capillary combination with the sensor, is additionally equipped with Black ( ). Red (+). an overvoltage protection circuit, which protects the probe from damage caused by induced interference from atmos- Black ( ). Red (+). pheric discharges or from associated heavy current engineering appliances. Lifting handle Configuration The following metrological parameters can be configured: The units of pressure.

7 Start and end-points of set range;. damping time constant;. inverted characteristic (output signal 20 4 mA). Calibration It is possible to calibrate the probe in relation to a model pressure. Communication The communication standard for data interchange with the probe is the Hart protocol. 147. Communication with the probe is carried out with: - a KAP-03 communicator, 25.. - some other Hart type communicators, - a PC using an HART/USB/Bluetooth converter and example of mounting RAPORT 2 configuration software. level probe The data interchange with the probe also enables the users to: 60. identify the probe ;. read the currently measured hydrostatic pressure value, output current and percentage of measuring range. V/ 6. Installation, method of use tional Aplisens UZ-2 overvoltage protection circuit in the When lowered to the reference level , the probe may either form of a wall-mounted box which allows the cables connec- hang freely on the cable or lie on the bottom of the tank.

8 Tion. When the probe cable is being wound up, the minimum The cable with the capillary can be extended using a stand- winding diameter should be 30cm and the cable should be ard signal cable. For the cable connection a special protected from mechanical damage. Aplisens SG cable hanger is recommended. The cable connection should be situated in a non-hermetically sealed If there is a possibility of turbulence in the tank (for example, box (the internal pressure inside the box should be equal to because of the mixer operating mixers or a turbulent inflow), the atmospheric pressure), preventing water or other con- the probe should be installed inside a screening tube ( taminants from getting into the capillary. The Aplisens PP made of PVC). The line hooked on the lifting handle can junction box is recommended For systems with long signal simplify the operation of the probe pulling out.

9 Cleaning the transmission lines, it is recommended the using of an addi- probe diaphragm by mechanical means is strictly prohibited. Measuring ranges No. Nominal measuring range Minimum set range Overpressure limit (FSO) (without hysteresis). 1 0 1,5 m H2O 0,15 m H2O 15 m H2O. 2 0 10 m H2O 0,8 m H2O 100 m H2O. 1). 3 0 100 m H2O 8 m H2O 700 m H2O. 1). Range available only is Technical data Metrological parameters Electrical parameters Accuracy 0,1% for nominal range L Power supply 7, VDC (Ex 7, VDC). 0,3% for range FSO. L Output signal mA (two wire transmission). Long term stability 0,1% (FSO) for 2 years L U sup [ V ] - 7,5V. Load resistance R[W. ]L. Accuracy 0,16% for nominal range L 0,0225A. 0,4% for range FSO. L Resistance required for communication >240 W. Thermal error < 0,08% (FSO) / 10 C. max 0,25% in the whole compensation temp. range Operating conditions For the probe the use of a diaphragm seal caus- Medium temperature range es an additional absolute zero error, related to changes in the medium temperature, of up to 80 Pa / 10 C.

10 C for basic range m H2O. C for basic range m H2O. Thermal compensation range C CAUTION: The medium must not be allowed to freeze in the Time Constant 0,3 s immediate vicinity of the probe . Additional electronic damping s Degree of protection IP68. Error due to supply voltage changes 0,002% (FSO) / V. Material of casing and diaphragm SS316L (for SGE-25 Smart Special versions: diaphragm Hastelloy). a Ex ATEX Intrinsic safety Titanium special version a Teflon Teflon cable shielding (only ). a SGM- version with thread on packing gland a Titanium titanium wetted parts Cable shield POLYURETHANE. a MR Marine certificate DNV. a 1,5 m H2O probe for nominal range 0 m H2O. (Accuracy ). Ordering procedure Model Code Description Smart level probe /Exia .. II 1G Ex ia IIC T4/T5/T6 Ga/Gb I M1 Ex ia I Ma II 1G Ex ia IIB T4/T5/T6 Ga/Gb Version with Teflon cable shielding I M1 Ex ia I Ma Versions, certificates /Teflon.